![Intellinet 163682 User Manual Download Page 8](http://html1.mh-extra.com/html/intellinet/163682/163682_user-manual_2074308008.webp)
19" Intelligent 8-Port PDU
User Manual
8
④
. ON and OFF Time Delay
Click “PDU” in the configuration box on the left side of the interface. The screen displays the following:
•
This function allows for the adjustment of the delay time in the start-up and shut-off sequences for
connected equipment. In the factory settings shown here, power will be supplied to and shut off from
ports one through eight in one-second intervals after five seconds have passed. Once new values have
been entered, click Apply.
NOTE
: When input power is disconnected from its source, the OFF Delay
function is ignored and power shuts off immediately to all equipment. Shutting off the time-delay
function is only able to control the eight-way output through a network.
⑤
. Threshold Value Setting
Click “Threshold value” in the configuration box on the left side of the interface. The screen displays the
following:
The meaning of each input is as follows; adjust values here and click Apply when finished :
•
Current Warning
value
(5.0 A) — if total current exceeds 5 A, the PDU will beep twice;
•
Current Overload
value
(6.0 A) — if total current exceeds 6 A, the PDU will shut off power to all output
ports;
•
Warning Voltage
value
(250) — if input voltage exceeds 250 V, the PDU will beep twice;
•
Voltage Overload
value
(300) – if input voltage exceeds 300 V, the PDU will shut off power to all
output ports;
•
Temperature is Under
(5
℃
) or
Above
(50
℃
): if the built-in temperature sensor reads temperatures
under or over these thresholds, the PDU will beep twice;
•
Humidity Warning
value
(80%): if the built-in humidity sensor reads humidity at more than 80%, the
PDU will beep twice.