Cable length, wire gauge and power conditioning devices play a major role
in the performance of your IMS Driver and Motor.
NOTE: The length of the DC power supply cable to the IMS Driver should
not exceed 50 feet.
Example A demonstrates the recommended cable configuration for DC
power supply cabling under 50 feet long. If cabling of 50 feet or longer is
required, the additional length may be gained by adding an AC power
supply cable (see Examples B & C).
Correct AWG wire size is determined by the current requirement plus cable
length. Please see the IMS Driver Supply Cable AWG Table in this
Appendix.
Shield to Earth Ground
on Supply End Only
DC Voltage from
Power Supply
500 µf
Per Amp
+
-
Braided
Shield
Ferrite
Beads
π
Type RFI Filter
≥
Required Current
+
-
To IMS Driver
Cable Length
less then 50 Feet
Shielded/Twisted Pair
(Wire Size from
IMS Driver Supply Cable AWG Table)
E x a m p l e A – C a b l i n g U n d e r 5 0 F e e t , D C P o w e r