ELECTRICAL CONNECTIONS
IMPORTANT
During installation, maintenance and cleaning, the appliance must be disconnected from the power supply.
The appliance must be attached to a 230 VAC power supply only. Follow the colours indicated:
Brown
Phase
Blue or grey
Neutral
Black
Pilot Wire
Note:
If the (black) pilot wire is not in use, regulations require that it be isolated. Never connect it to any earth terminal.
A multi-pole circuit breaker must be installed. The distance between the contacts must be at least 3 mm.
The appliance’s power circuit must be protected by a RCD high sensitivity differential protection device.
The power cord must be connected to the power supply using a shunt box located 25 cm from the ground, without the use of an electrical plug.
Never insert metal objects into or attempt to pierce the side of the radiator containing the regulation system (right side).
If the power cord is damaged, it must be replaced by a qualified electrician only.
5.1.
Details of bathroom installation
The appliance must be installed according to current regulations and laws in the country of use.
The radiator is class II and has IP24 electrical protection. In bathrooms, it can be installed in area/zone 3 (see figure 1) on condition that the control
device is not within reach of people using the shower or bathtub.
For your safety, installation should only be undertaken by a competent person in accordance with current I.E.E. Regulations.
In the bathroom, protect the power line with a 30 mA high sensitivity differential device.
Install a multi-pole circuit breaker. The distance between the contacts must be at least 3 mm.
2,5 m
fig. 1
AREA 0
AREA 0
AREA 1
AREA 2
AREA 3
Please contact your INTELLI HEAT Representative for further assistance or information.