Intel® Server D50TNP Family Integration and Service Guide
179
Figure 265. Server Board Installation
10.
Remove the new server board from its anti-static bag.
11.
Carefully lower the server board into the module tray.
12.
Slide the server board slightly toward the front of the module tray until the connectors go through the
cut-out on the front panel and the screw holes in the server board align with the standoffs in the module
tray (see Letter A).
13.
Fasten the server board to the module tray using all the screws (see Letter B). Tighten to 5 in-lb.
14.
Reinstall processors (see
Section 7.4
).
15.
For liquid-cooled module, reinstall the liquid-cooling loop (see
Section 7.9
16.
Reinstall DIMMs (see
Section 7.5
17.
Reinstall riser card assemblies (see
Section 7.8
).
18.
Reinstall all options previously removed from the server board, including the Intel® VROC 7.5 key
(see
Section 3.11
19.
For air-cooled modules, reinstall the air duct (see
Section 7.2.2
).
20.
Reinstall the module in the chassis (see
Section 7.1.2
).