Intel® Server D50TNP Family Integration and Service Guide
111
7.3.2
Closing the Top Tray
Figure 141
.
Removing the Air Duct
1.
Push up the front edge of the top tray just slightly until the lock releases
2.
Push the handle bar down (see Letter A) with one hand. Hold the front edge of the top tray with the other
hand and lower it (see Letter B).
3.
Lock the latches on both sides of the top tray (see Letter C)
7.4
Processor Replacement
7.4.1
Processor Replacement for Standard Air-Cooled Heat Sinks
Components Required for each faulty processor:
•
New 3
rd
Gen Intel® Xeon® Scalable pro included shipping tray
•
Existing processor carrier clip
•
Existing processor heat sink + new thermal interface material (TIM)
Required Tools and Supplies:
•
Anti-static wrist strap and conductive workbench pad (recommended)
•
ESD Gloves (recommended)
•
T-30 Torx* screwdriver
Note:
The installation figures in this section only display the 1U front heat sink. However, the processor
installation procedure is the same, regardless of the size of the heat sink.