Thermal Specifications
6.1.2
Thermal Metrology
The minimum and maximum TTV case temperatures (T
CASE
) are specified in
and
and are measured at the geometric top center of the thermal test vehicle
integrated heat spreader (IHS).
illustrates the location where T
CASE
temperature measurements should be made. For detailed guidelines on temperature
measurement methodology and attaching the thermocouple, refer to the appropriate
processor Thermal and Mechanical Design Guidelines (see
).
Notes:
1.
Figure is not to scale and is for reference only.
2.
B1: Max = 45.07 mm, Min = 44.93 mm.
3.
B2: Max = 42.57 mm, Min = 42.43 mm.
4.
C1: Max = 39.1 mm, Min = 38.9 mm.
5.
C2: Max = 36.6 mm, Min = 36.4 mm.
6.
C3: Max = 2.3 mm, Min = 2.2 mm
7.
C4: Max = 2.3 mm, Min = 2.2 mm.
8.
Refer to the appropriate Thermal and Mechanical Design Guide (see
) for instructions on
thermocouple installation on the processor TTV package.
Figure 6-2. Thermal Test Vehicle (TTV) Case Temperature (T
CASE
) Measurement Location