4 Quick Start Guide
After unpacking the server
Inspect the shipping box for evidence of mishandling during transit. If the shipping box is
damaged, photograph it for reference. After removing the contents, keep the damaged box and the
packing materials. If the contents appear damaged, file a damage claim with the carrier
immediately.
Save the shipping boxes and packing materials to repackage the server in the event you decide to
move it to another site.
Installing the server
WARNINGS
Anchor the equipment rack: The equipment rack must be anchored to
an unmovable support to prevent it from falling over when one or more
servers are extended in front of it on slide assemblies. The anchors must
be able to withstand a force of up to 113 kg (250 lbs). You must also
consider the weight of any other device installed in the rack.
Main AC power disconnect: You are responsible for installing an AC
power disconnect for the entire rack unit. This main disconnect must be
readily accessible, and it must be labeled as controlling power to the
entire unit, not just to the server(s).
Grounding the rack installation: To avoid the potential for an electrical
shock hazard, you must include a third wire safety grounding conductor
with the rack installation. If server power cords are plugged into AC
outlets that are part of the rack, then you must provide proper
grounding for the rack itself. If server power cords are plugged into
wall AC outlets, the safety grounding conductor in each power cord
provides proper grounding only for the server. You must provide
additional, proper grounding for the rack and other devices installed
in it.
Overcurrent protection: The server is designed for an AC line voltage
source with up to 20 amperes of overcurrent protection. If the power
system for the equipment rack is installed on a branch circuit with more
than 20 amperes of protection, you must provide supplemental
protection for the server. If more than one server is installed in the
rack, the power source for each server must be from a separate branch
circuit. The overall current rating of a server configured with three
power supplies is under 12 amperes.