MANUAL OF ECULED212 MODEL EMERGENCY LIGHTING CONVERSION KITS FOR LED LAMPS

WARNING!  

It is important that these instructions are read throughly before any installation work commences.  They 

must also be retained on file to provide information on use and maintenance by end-user.  All installation work must 
be carried out by a suitable qualified person and must comply with the instructions and all other relevant regulations. 
Before any intervention to the unit, make sure that the mains voltage is disconnected.

INSTRUCTIONS

The environmental temperature and humidity conditions of the luminaire where the unit will be mounted in should be 
suitable to the below indicated specifications. To achieve optimum performance, the unit and the battery pack should 
be placed enough distant from the lamp and driver inside the luminaire and they should be kept at a max ambient 
temperature below 50°C. The cable lengths are recommended max 100 cm. Do not make longer the battery cable. 
First install the module and battery pack.  Connect the LED lamp, driver and  the charging indicator. Connect the 
battery socket.  Connect the mains. 

WARNING ! 

The unswitched line and the switched line should be on the same phase.  For the complete charge of 

the battery, the unit should be left on charge for a minimum period of 24 hours.

OPERATING INSTRUCTIONS

The battery automatically charges through the unswitched line of the luminaire and the green charging indicator 
LED lamp is lit.  At that time the LED lamp could be turned ON/OFF through the wall switch connected to the driver 
circuit driven by the switched line. When the mains goes out, the unit will automatically remove the power supply 
of the switched line and energise the LED lamp (at the emergency lighting level) through the battery and not 
depending on the wall switch position. When the mains is recovered, the luminaire will be energised by the 
switched line through the wall switch and the battery will start the charge.  

TEST INSTRUCTIONS 
Function Test : 

This is a practical test to check shortly the function of the unit. While the test button is pressed  the 

luminaire will run at emergency mode. The Function Test has to be carried out once in a month by pressing the test 
button or removing the mains line fuses. 

Duration Test :

 The mains power of the luminaire has to be disconnected once at every 12 months and the 

Duration Test has to be carried out to check battery backup duration. Before starting the Duration Test the unit 
should be left on charge for a minimum period of 24 hours. If the backup does not extend to the declared duration, 
the battery packs have to be replaced.  The replaced batteries have to be returned to the manufacturer or to be 
left at the special waste containers for recycling.

WARNING ! 

Do not dismantle any part of the unit, do not drill or bore. It does not contain any parts repairable by the 

installer or user. Any of those kind of unauthorized interventions will cancel the warranty conditions.

TECHNICAL SPECIFICATIONS   

Mains Supply 
Battery 

Lamp
Emergency Duration
Operating Mode
Charger 

Charge Indicator 
Battery Protection

Output Protection
Max Output Voltage
Terminals
Temperature
Class
Insulation
Humidity (RH%)
Protection Class
Construction
Standards

: 230 Volt, 50/60Hz, 0.02A max, 2.4VA max
: High Temperature type Ni-Cd Battery Pack with polarised connector, 
  nominal 3.6 Volt (3.0-4.5 Volt), 1.7Ah for 1 hour, 3.5Ah for 3 hours operation
: 1 to 12 serial connected Power LED (min 350mA/1W type) 
: 1 or 3 hours  
: Non-maintained, 

maintained or switchable maintained with external driver.

: Current controlled charger. The ballast is suitable for use only on battery supply 
  not having a trickle or intermittent re-charging circuits.  The charger will charge 
  the battery normally after the test of EN 61347-2-7 Standard, Part 22.3.
: Ø5mm green LED lamp with panel type holder (55~60cm)
: Over charge & deep discharge protection.  The ballast is not proof against supply 
  voltage polarity reversal but have a polarised battery connector.
: Open circuit, short circuit & overload protection

Open Circuit Voltage 50 V DC

Max Vout = 45V DC, 

: 45º entry, quick fit terminal block for 0.2-0.75mm² cross section conductors
: Ambient Temperature ta: 0-45ºC, max Case Temperature tc: 90ºC 
: Class II, no earth wiring required
: Basic insulation 
: 20 - 90% RH
: IP20
: White polycarbonate (Flame rating UL94-V2)
: EN61347-1, EN61347-2-7