Section 2b:
Adding a 2300 station to an Ezeio controller:
Notes:
a. More than one 2300 can be added to an Ezeio controller, including a mixture of A16’s and 2300 stations.
b. The Ezeio Controller will accept up to 40 inputs per Ezeio controller, after which, add another Ezeio.
Follow these steps to add one or more A16’s:
Disconnect both the Ezeio Controller and 2300 from the power supply.
Connection to the Ezeio Controller ‘ModBus 485’ port is by using a
standard Ethernet cable plugged into the Ezeio Controller
‘ModBus 485’ port and broken out to twisted pairs.
The 2300 series field stations are
a family of modular I/O
Remote Stations, that add an even lower cost option to Intech’s
already extensive intelligent I/O Remote Station family and
connect directly to
the Ezeio.
The 2300 series I/O stations are made up of stand-alone
Analogue and Digital—Input or Output stations. Communications
between the Ezio and the 2300 series stations is RS485 (1 pair
with screen cable) multi drop as standard
RTD, T/C, mA,mV & V, plus Digital input and relay outputs as
follows:
Model
2300-RTD6 : RTD: Pt100/Pt1000, -200~320°C to -200~800°C.
2300-Tc8 : T/C: B, E, K, J, N, R, S, T, with CJC.
2300-A8II : mA: 4~20mA, 0~2.5mA.
mV: -25~25mV to -200~200mV.
V: 0~1V to 0~15V.
Relay outputs, Contact rating: 240Vac
Eze Controller