Intec SM-501 Series Installation And Maintenance Instructions Manual Download Page 4

1      

2      

3      

4      

5     

6     

7     

8      

9     

10 11    

12    

13    

14    

15    

16    

17   

18    

19   

20   

21

SEE

POWER

CONNECTIONS

REMOTE

 ACCESSORIES

ALARM

CONTACTS

12 A

ALARM

CONTACTS

12 A

*TROUBLE

CONTACTS

10-A

*TROUBLE CONTACTS ARE SHOWN

 IN NON-ENERGIZED CONDITION.

UNDER NORMAL OPERATION

CONTACTS WILL BE REVERSED.

FIREX DUCT SMOKE DETECTOR

SM-501 DUCT SMOKE DETECTOR

SEE

POWER

CONNECTIONS

ALARM

CONTACTS

10A

ALARM

CON-

TACTS 10A

*TROUBLE

CONTACTS

10A

REMOTE

ACCESSORIES

*TROUBLE CONTACTS ARE SHOWN IN

NON-ENERGIZED CONDITION. UNDER 

NORMAL OPERATION CONTACTS

WILL BE REVERSED.

FAN SUPPLY SOURCE

7

9

NC           C

NO

ALARM RELAY

5

6

1

DEDICATED INPUT VOLTAGE

115VAC

8

ELECTRICAL INSTALLATION

POWER CONNECTIONS

Prior to connecting input power to the duct unit, determine the correct input voltage/ current availability and ensure it is connected to the correct 

terminals.

In alarm 7 and 8 will 
open, interrupting 

voltage supply to fan

AC/+ /H
AC/- /N

2

3

or

24VAC/VDC

24VAC/VDC INPUTS 

Terminals 5, 6

24VAC

50/60  Hz     0.2A  MAX.

24VDC

0.1A  MAX.

115VAC   50/60 Hz 

0.1A  MAX.

115VAC INPUT

Terminals 1,2,3.

230VAC   50/60 Hz 

0.1A  MAX.

230VAC INPUT

Terminals 1,2,4.

24VDC OPERATION

115VAC OPERATION

230VAC OPERATION

+     -

G       H1

H2

24VAC OPERATION

WIRING

 

CAUTION

:  For terminals 7-15 do not use looped wire under terminals.  Break wire run to provide for proper supervision of connections.

With detector head removed, connect one of the appropriate dedicated power sources to the applicable terminals (see above). Replace detector head and 
the unit will be energized. The green pilot LED will be illuminated, and when pressing the test/reset button, the red alarm LED will be illuminated. This test 

confirms the correct basic operation of the duct smoke unit, excluding the detector head (see functional testing).

In the event of a fire alarm, certain equipment may be required to be shut down. For example, shut down may be achieved by interrupting the fan supply 
source to that particular piece of equipment when wired as indicated below.

EXAMPLE: 

!

4 of 6

150303

Specifications subject to change without notice. | INST APD0191 D140113 | USA 150303 | Page 4 of 7

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

SM-501 – Installation

Summary of Contents for SM-501 Series

Page 1: ...ned in all this document should be considered before installing or using the product Any example applications shown are subject to the most current enforced local national codes standards approvals ce...

Page 2: ...e air stream reach the alarm threshold of the detector head the unit will go into alarm The duct smoke detector units are designed to operate in duct widths from 6 to 10 wide with an air velocity betw...

Page 3: ...10 0 For duct widths of 5 0 to 10 0 FAST TUBE Sectional Tube for duct widths up to 8 0 Standard sampling tubes are steel tubes with air intake holes drilled the entire length of the tube FAST Tubes ar...

Page 4: ...A MAX 115VAC INPUT Terminals 1 2 3 230VAC 50 60 Hz 0 1A MAX 230VAC INPUT Terminals 1 2 4 24VDC OPERATION 115VAC OPERATION 230VAC OPERATION G H1 H2 24VAC OPERATION WIRING CAUTION For terminals 7 15 do...

Page 5: ...tector X SM 501 Detector 1 11 15 12 INTERCONNECTION WIRING FOR COMMON FUNCTIONS MS REMOTE ACCESSORY WIRING C TB P C AL T R 18 20 21 17 19 14 JUMPER A jumper wire must be placed between Terminals 14 an...

Page 6: ...e alarm relays will change state and the alarm related remote accessories if attached will function If no test gas is available to conduct functional testing light a piece of clothesline rope and blow...

Page 7: ...itch MS RH P A Remote Alarm Pilot Horn MS RH KA P A T Remote Alarm Trouble Pilot Horn key operated Test Reset Switch MS RA P T Remote Pilot Trouble MS RA FT P Remote Pilot Trouble push button Test Res...

Reviews: