background image

MECHANICAL INSTALLATION

LOCATION PREREQUISITES

This guideline contains general information on duct smoke detector 

installation, but does not preclude the NFPA and/or ICC 
documents  listed. 

N

o responsibility 

is  assumed 

for

  the

 

improper instal

lation of the

 duct detectors. To determine the correct 

installation  position for an SM-501 Series duct smoke detector, the 

following factors must be considered.

1.

A uniform non-turbulent (laminar) airflow between 500 ft/min. to
4,000 ft/min. must be present in the HVAC duct. To determine duct
velocities, examine the engineering  specifications that define the

expected velocities or use an Alnor model 6000AP velocity meter

(or equivalent).

2.

To minimize the impact of air turbulence and stratification on
performance, a duct smoke detector should be located as far as

possible downstream from any obstruction (i.e. deflector plates,

elbows, dampers, etc.). In all situations, confirmation  of velocity and
pressure differential within specifications is required.

The pressure differential between the input sampling
(high pressure) tube and exhaust (low pressure) tube

for the SM-501 Series smoke duct detector should be
greater than 0.01 inches of water and less than 1.2 inches
of water.

3.

Identify a code compliant location (supply or return side, or
both) for the installation of the duct unit that will permit easy access
for viewing and serviceability.

4.

When installing on the return side, install duct units prior to the air
being exhausted from the building or diluted with outside “fresh”
air.

5.

When installing duct smoke units downstream of filters, fires
occurring in the filters will be detected, but if the filters become
blocked, insufficient air flow through the duct unit will prevent the
correct operation of the duct detector. Duct units installed in the
supply air side may monitor upstream equipment and/or filters.

6.

Where possible, install duct detectors upstream of air humidifiers
and downstream of dehumidifiers.

7.

To prevent false alarms, the duct detector should not be mounted
in areas of extreme high or low temperatures, in areas where high
humidity exists, or in areas where the duct may contain gases or
excessive dust.

SAMPLING TUBE ASSEMBLY

Sampling tubes are to be ordered separately in one of four standard 
lengths.

 

STS-1.0 

For duct widths of 6” to 1.0’

STS-2.5 

For duct widths of 1.0’ to 3.0’

STS-5.0 

For duct widths of 3.0’ to 5.0’

STS-10.0 

For duct widths of 5.0’ to 10.0’

FAST TUBE 

Sectional Tube for duct widths up to 8.0’

Standard sampling tubes are steel tubes with air intake holes drilled 
the entire length of the tube. FAST Tubes are a recognized plastic with 
an open slot along the length. These tubes can be cut to length and 
must span at least 80% of the duct width (spanning the entire width is 

suggested).

Sampling tubes over 3ft must be supported on the opposite side of the 

duct. To ensure correct operation of the sampling tube, the red end cap 
(red stopper in installation kit) must be inserted in the end of the air 

intake. For custom duct widths, always use the next longest standard size 
and cut down to the exact requirement.

Once the airflow direction has been determined, insert the inlet and 
exhaust tubes into the sampling tube connectors fitted to the back of 
the duct smoke detector which are equipped with set screws. These 

connectors will allow the tubes to be correctly orientated and secured 
by tightening the set screw. Ensure air intake sampling tube is positioned 
so that the inlet holes (or FAST Tube slot) directly face the airflow.

DUCT PREPARATION

Remove mounting template from the installation kit. Remove paper 
backing from the mounting template and affix it to the duct at the 
desired location. Using the template as a guide, drill (4) mounting holes 
(3/32” diam.) for the # 12 X 1/2” sheet metal screws packaged in the 
installation kit. Drill or punch (2) 1 3/8” holes for inlet sampling and 
exhaust tubes, using the template as a guide. Clean all holes.

MOUNTING

After securing the sampling and exhaust tubes to the duct smoke unit, 
(or initially placing the tubes through the 1 3/8” holes drilled or punched 
in the HVAC duct to accept the inlet sampling and exhaust tubes and 
then attaching them to the duct unit), hold the duct unit assembly in 
position and use (4) # 12 X 1/2” sheet metal screws (packaged in the 
installation kit) to secure the duct smoke detector to the HVAC duct 
sheet metal.

AIR SAMPLING VERIFICATION

To ensure correct operation of the duct unit use a Magnehelic differential
pressure gauge, Dwyer 2000 or 4000 Series (or equivalent) to determine 
the differential pressure between the inlet (high side) and exhaust (low 
side) tubes. The differential pressure between the two tubes should be 
greater than 0.01 inches of water and less than 1.2 inches of water.

3 of 6

150303

Specifications subject to change without notice. | INST APD0191 D140113 | USA 150303 | Page 3 of 7

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

SM-501 – Installation

Summary of Contents for SM-501 Series

Page 1: ...ned in all this document should be considered before installing or using the product Any example applications shown are subject to the most current enforced local national codes standards approvals ce...

Page 2: ...e air stream reach the alarm threshold of the detector head the unit will go into alarm The duct smoke detector units are designed to operate in duct widths from 6 to 10 wide with an air velocity betw...

Page 3: ...10 0 For duct widths of 5 0 to 10 0 FAST TUBE Sectional Tube for duct widths up to 8 0 Standard sampling tubes are steel tubes with air intake holes drilled the entire length of the tube FAST Tubes ar...

Page 4: ...A MAX 115VAC INPUT Terminals 1 2 3 230VAC 50 60 Hz 0 1A MAX 230VAC INPUT Terminals 1 2 4 24VDC OPERATION 115VAC OPERATION 230VAC OPERATION G H1 H2 24VAC OPERATION WIRING CAUTION For terminals 7 15 do...

Page 5: ...tector X SM 501 Detector 1 11 15 12 INTERCONNECTION WIRING FOR COMMON FUNCTIONS MS REMOTE ACCESSORY WIRING C TB P C AL T R 18 20 21 17 19 14 JUMPER A jumper wire must be placed between Terminals 14 an...

Page 6: ...e alarm relays will change state and the alarm related remote accessories if attached will function If no test gas is available to conduct functional testing light a piece of clothesline rope and blow...

Page 7: ...itch MS RH P A Remote Alarm Pilot Horn MS RH KA P A T Remote Alarm Trouble Pilot Horn key operated Test Reset Switch MS RA P T Remote Pilot Trouble MS RA FT P Remote Pilot Trouble push button Test Res...

Reviews: