Specifications

4-20 mA Output Adjustments

4-20 mA Output Adjustments

The outputs must be set for current sourcing configuration. Install 
jumpers at positions 1-2, 3-4 and 5-6 for S2 through S9.

Set Dipswitch S1 as follows for 4 mA adjustment: 

With your ampmeter at each output, adjust the 4 mA with 
Potentiometers P9 through P16.

Set Dipswitch S1 as follows for 20 mA adjustment: 

With your ampmeter at each output, adjust the 20 mA with 
potentiometers P1 through P8.

Once completed, replace the settings to their original places.

Before changing the S1 DIP switch settings for the 4-20 mA 
adjustments,  note the actual setting to reset the dip switch for 
normal operation. After the adjustments are made, replace  
jumpers at S2 through S9 to the correct configuration.

WARNING

Do NOT use Current Sourcing Configuration if there will be 
voltage on the line.

Dip1: OFF

Dip2: OFF

Dip3: ON

Dip4: OFF

Dip1: OFF

Dip2: ON

Dip3: ON

Dip4: OFF

IVA-420I User Manual

Summary of Contents for IVA-420I

Page 1: ...Digital Signal Converter IVA 420I User Manual ERP 511399 2 07 12700 Stowe Dr Ste 100 Poway CA 92064 Ph 858 578 7887 Fx 858 578 4633 Email info inteccontrols com www inteccontrols com...

Page 2: ...ed or lost or may result in the inability to properly operate the process CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be...

Page 3: ...13 Listening Mode 13 Polling Mode 14 Split Address Mode 14 Available Configuration for 301C 15 4 20 mA Configuration 16 4 20 mA Output Loop powered Operation 17 4 20 mA Output Configuration 19 WIRING...

Page 4: ......

Page 5: ...m or packing slip Installation Guidelines Make sure to locate the monitor in an area easily accessible to a technician Avoid any location where temperature changes occur rapidly Verify all the require...

Page 6: ...he controller and the transmitters It does not intervene in network operation The converter transforms the digital signal from the transmitters into a 4 20 mA analog signal Once set the converter prov...

Page 7: ...ough J23 Three statistic values are also available Minimum Maximum and Average with the appropriate settings These values are available with addresses 1 to 8 9 to 16 or 1 to 16 if the converter is con...

Page 8: ...broadcast mode must be activated on the controller side Addresses can be selected in groups of 8 i e 1 8 9 16 and so on until 89 96 See DIP Switch settings for further details There are also three 3...

Page 9: ...ower and output lines Mounting Instructions 1 Select installation location 2 Measure and mark mounting holes as shown 3 Pre drill or prepare as required by mounting surface drywall plugs etc 4 Positio...

Page 10: ...ion the three jumpers must be placed on positions 1 2 3 4 and 5 6 at distinct outputs J16 through J23 WARNING A dedicated power supply must be used with each unit Considerable damage may occur if this...

Page 11: ...nable this configuration the three jumpers must be placed on positions 2 3 4 5 and 6 7 at distinct outputs J16 through J23 Permitted Impedance in the 4 20 mA Loop 3 wire configuration Voltage Source A...

Page 12: ...ough outputs J16 to J23 The output signal is linear to the input The 4 mA output represents the minimum scale from the input and the 20 mA output represents the maximum scale from the input DDC System...

Page 13: ...1 2 3 4 and 5 6 Loop Powered S2 to S9 jumpers at 2 3 4 5 and 6 7 When the output reads 3 33mA the IVA 420I does not see the corresponding transmitter WARNING A dedicated power source must be used wit...

Page 14: ...nge 0 95 RN non condensing Communication cable 2 24 AWG twisted and shielded Belden 9841 or equivalent Dimensions 8 4 in H x 8 6 in W x 2 5 in D 21 3 cm x 13 4 cm x 5 7 cm Weight 3 5 lbs 1 58 kg with...

Page 15: ...0 mA adjustment With your ampmeter at each output adjust the 20 mA with potentiometers P1 through P8 Once completed replace the settings to their original places Before changing the S1 DIP switch sett...

Page 16: ...1 0 0 0 0 Listen mode split adr 1 4 9 12 0 0 1 1 0 0 0 0 Interrogation mode statistic 1 16 0 1 1 1 0 0 0 0 Listen mode statistic 1 16 MODBUS 301C 0 0 0 0 1 1 0 0 0 Modbus listen Adr 1 8 0 0 0 0 1 0 1...

Reviews: