AirSense
Model I-310en Operator’s Manual
10/16/11
Page:
13
Optional High Limit Contact Relay
The high CO2 limit relay option provides a dry (i.e.
unpowered) contact closure that activates when the detected
concentration rises above the high CO
2
limit. The high limit
is adjustable from 0 to 5000 ppm.
Setting High Limit Contact Polarity
The polarity of the high limit contact is set with jumper JP5
as shown in the table below.
Jumper JP5
Relay Operation
CLOSED
(factory default)
normally open
closes above setpoint
OPEN
normally closed
opens above setpoint
To open jumper JP5 remove the shorting block from the two
pins, and replace it so that it engages only a single pin of the
jumper. The shorting block should not be discarded; it is
required for all field calibration procedures.