Commissioning

Important:

-  The following instructions must be read and understood prior to commissioning the

    thermostatic shower valve. If under any circumstances there are aspects to the installation / 
    system which do not comply with the specification laid down, the valve 

MUST NOT

be put

     into operation until the system / installation complies with the specification. However if all 
    these conditions are met, proceed to set the temperature as follows;

   1.  Ensure that the system is thoroughly cleaned and free from any debris prior to 
        commissioning the thermostatic shower valve.

   2.  Commissioning the temperatures must be carried out using a suitably calibrated 
        thermometer, preferably a digital thermometer. The sensing part of the thermometer probe 
        must be fully submerged in the water when testing.

   3.  The valve must be commissioned taking into consideration any fluctuations, which may 
        occur within the system due to simultaneous demands.  It is advisable that any outlets which 
        are connected to the same supply as the shower valve are open during setting of the mixed 
        water temperature. It is advisable to ensure that the water temperatures are established 
        before any attempt to commission.

   4.  Once the supply temperatures are stable and the normal operating conditions are 
        established, the shower valve can be commissioned. The following sequence should be 
        followed when commissioning the valve;

        4.1 The first step in commissioning a thermostatic shower valve is to check the following:

        

• The designation of the thermostatic shower valve matches the application

        

• The supply pressures are within the valve’s operating range.

        

• The supply temperatures are within the valve’s operating range.

        

• Isolating valves (and ‘Y’ strainers preferred) are provided.

        4.2 If all these conditions are met, proceed to set the temperature following the procedure 
        

described earlier in the Calibration section. 

        4.3 Measure and record the temperature of the hot and cold water supplies at the 
        

connection to the valve.

        4.4 Measure and record the temperature of the water discharging from the valve. 

        4.5 Isolate the cold water supply to the valve and monitor the mixed water temperature.

        4.6 Measure and record the maximum mixed water temperature and the final temperature.
        

The final temperature found during the test should not exceed the values quoted.

        4.7 Record all the equipment used during the commissioning.

        4.8 The mixed water temperature at the terminal fitting must never exceed 2˚C above the 
        

set temperature.

Summary of Contents for Kiko DELUXE KIKOD20

Page 1: ...ate as possible We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or otherwise In...

Page 2: ...ealed Shower with ceiling arm and soaker flexible slide rail kit 5 function handset and wall elbow KIKO23 Kiko DELUXE Options Kiko DELUXE Rinse Station with smooth hose and push button hand set KK7000...

Page 3: ...The shower is pre set using ideal conditions to 38 C at the stop with a manual push button override to 46 C can be re set to suit site conditions or user preference see calibration page 13 The maximu...

Page 4: ...hower Valve Item Qty Component 1 1 Valve body and flow controller body 2 1 Flow controller 3 1 Thermostatic cartridge 4 2 Cap and check valve 5 2 Angled male x compression adaptor 6 2 Straight male x...

Page 5: ...aling plate gasket 8 1 Concealing plate 9 2 Sealing ring 10 1 Temperature control concealing sleeve 11 1 Flow control concealing sleeve 12 1 Temperature stop ring 13 1 Flow control stop ring 14 2 Gear...

Page 6: ...Plaster Guard and Insulation 17 18 19 20 21 22 Item Qty Component 17 1 Preformed body insulation shell 18 2 Extension piece 19 1 Thermostatic cartridge extension 20 1 Flow controller cover 21 1 Plast...

Page 7: ...ng cold water prior to the hot water storage vessel This means that the hot and cold pressures can be significantly different Most unvented systems use an inlet manifold located directly after the pre...

Page 8: ...not available a negative head kit may be required to operate the pump Please consult the pump manufacturer s installation requirements Modulating Combi Boiler Instantaneous Gas Water Heater The drawi...

Page 9: ...he vent or a draw off pipe as close as possible to the top of the cylinder For equal tank fed pressures there is no need to fit the flow regulators This installation is the recommended minimum for gra...

Page 10: ...nstalled The supply pipes can come from below above the side or through the wall The shower valve must be installed securely into the wall If not embedded into the wall with plaster the shower valve m...

Page 11: ...s to be fitted see dimension drawing Cavity wall The shower valve must be fixed securely to the structural members of the stud wall and or an additional member may need to be included where the shower...

Page 12: ...20 over the flow control valve and secure with retaining screw 22 Fit the plaster guard 21 over the valve and secure with two retaining screws 22 For a solid wall embed the pipes and shower valve wit...

Page 13: ...rectified before proceeding further Finish tiling the wall around the shower valve Fit the gasket into the concealing plate with a bead of mastic Place the concealing plate and gasket with a bead of m...

Page 14: ...stop ring must align with the temperature position symbol 10 on the temperature control concealing sleeve Refit the gear drive 14 Refit the temperature control knob in the reverse order ensuring that...

Page 15: ...mp cloth followed by a thorough rinsing is all that is required The nozzles in the hand set should be cleaned periodically to remove any build up of debris or deposits which may affect the performance...

Page 16: ...t at cold the showering temperature is too hot The hot and cold supply connections have been made in reverse Thermostatic cartridge movement limited due to lime scale build up The maximum showering te...

Page 17: ...he fitting used should not protrude beyond the surface of the ceiling Other fittings may be required to make the connection between the fitting fixed to the structural member and the water outlet Appl...

Page 18: ...lide Rail Components 1 6 3 2 6 3 8 7 4 5 9 10 11 12 11 Final position Item Qty Component 1 1 Bottom Wall Bracket 2 1 Top Wall Bracket 3 2 Cover 4 1 Flexible Tidy 5 1 Handset Holder 6 2 Screw Plug 7 1...

Page 19: ...6 3 2 6 3 8 7 4 5 9 10 11 12 11 Smooth Hose Item Qty Component 1 1 Bottom Wall Bracket 2 1 Top Wall Bracket 3 2 Cover 4 1 Flexible Tidy 5 1 Handset Holder 6 2 Screw Plug 7 1 Wall plate 8 1 Rail cap 9...

Page 20: ...il 9 and position in the bottom wall bracket 1 Position the upper bracket onto the wall ensuring the rail is vertical Mark round the wall plate 7 onto the wall with a removeable marker Position the wa...

Page 21: ...ns 200 200 250 250 350 350 G B G B G B G B G B G B 15 15 15 15 20 20 170 160 Position of concealing plate adjustable KK70004CP KK70008CP KK70003CP KK70007CP Wall elbow part of KK70001CP rinse station...

Page 22: ...erating outside these conditions cannot be guaranteed by the Scheme to operate as type 2 valves The valves designation of use HP tested against BS EN 1111 For valves designated for use HP only if a wa...

Page 23: ...99 and also be aware of their responsibility and duty of care to ensure that all aspects of the installation comply with the regulations It has been brought to our attention that flushing water system...

Page 24: ...e s to within the limits as quoted previously 8 Any thermostatic shower valve must be fitted with a back flow prevention device such as check valves to prevent the cross contamination of supplies The...

Page 25: ...eratures are established before any attempt to commission 4 Once the supply temperatures are stable and the normal operating conditions are established the shower valve can be commissioned The followi...

Page 26: ...g performance checks shall be carried out 1 Measure the mixed water temperature at the outlet 2 Carry out the cold water supply isolation test by isolating the cold water supply wait for five seconds...

Page 27: ...Intatec Ltd 2017 26 Notes...

Page 28: ...Intatec Ltd 2017 27 Notes...

Page 29: ...Intatec Ltd 2017 28 Notes...

Page 30: ...n Staffordshire ST18 0PF Tel 01889 272 180 Fax 01889 272 181 email sales intatec co uk web www intatec co uk E O E 14 08 17 To activate your product warranty please visit www intatec co uk and click o...

Reviews: