background image

SECTION  7 - The HIU Controller first power up and set up

 

SECTION  11 -  Fault and Error Codes / Fault finding guide 

 

code 

Cause 

Effect 

Remedy 

E1 

The measured primary temperature is lower 
than the set point temperature is for heating  
so the HIU will not be able to achieve the set 
temperature. This is after approximately 60 
seconds of flow.  

The function is re-enabled when the primary   
exceeds the setpoint temperature.  

Check the set point in the controller, adjust if the 
set point is set higher than the design supply 
temperature.  
Check that the primary temperature probe is 
correctly connected to the primary pipe. 
When the primary temperature and set point are 
aligned, the error code E1 automatically  
disappears. 

E2 

In installations where Radiators are at very 
high temperatures, then this is a warning 
that the return temperature is higher than 
the maximum allowed in parameter 20.  

As this is a safety function, the PICV closes until the 
sensor on the primary return sees a temperature 
drop of 10C below the parameter 20 set point for 
maximum.  

Check parameter 20 is set correctly, if too low, 
reset this at 5C higher than secondary heating 
flow set temperature. Check the temperature 
probe is positioned correctly. Reset (turn power 
on and off) to recalibrate the PICV actuator. 

E3 

The controller is recognising and warning 
that the HIU performance is not as the  
algorithm predicts. The energy transfer is 
poor, and the HIU is not delivering heat as it 
should be.  

Heat transfer is inefficient, heating capacity      
reduced and temperature control unstable.  

If signs of blockage it could be the strainer is 
blocked or the PHE is partially blocked with lime 
scale. Check PICV fully open and check flow on 
the heat meter. Low flow value would prove that 
a blockage of some sort is the issue. 

E5 

Heating is not reaching the set point so is 
performing poorly or not at all.  

Heating stops after 20 minutes and shows the E5 
code. 
Resets after 30 seconds 
Or Error LEDs on the pump? 
 
Power ON and OFF at the mains switch, this  
allows the PICV to recalibrate, and in doing this will 
allow a small flow into the PHE, which then proves 
the PICV and Diverter not at fault. 

Check the following possibilities. 
-  Primary temperature is too low? 
- Is the  set temperature on the controller higher 
than the incoming primary (network)   
temperature and temperature is impossible to 
reach? Rest set the temperature so it is 10C lower 
than the primary. 
-  PICV blocked / strainer blocked? 
-  Diverter in the wrong posion? 

E6 

Temperature information from the heating 
temperature sensors is wrong or unusual.  

Return temperature is too high with no apparent 
control being seen. 

This error code is showing that either; 
1.The heating temperature sensors have been 
wrongly positioned with the flow on the return 
and the return on the flow, change them to their 
correct position. 
2.The installer has not connected the primary 
connections correctly, with the flow connected to 
the return connection. Check temperatures. 

E7 

The heating return temperature is too high 
and the HIU is warning the operator. Various 
causes may be considered, example all TRVs 
may be closed with only 1 x small radiator 
open, but the room thermostat is still calling 
for heat.  

Various causes may be considered, example all 
TRVs may be closed with only 1 x small radiator 
open, but the room thermostat is still calling for 
heat. The return temperature is much too high, so 
the HIU ceases .The effect is that the controller 
shuts down the pump before re-starting again after 
10 minutes.  

The E7 will automatically reset itself aſt er 10 
minutes. Attention should be paid to the set up of 
the heating radiators and controls.  
Is the room thermostat positioned correctly to 
turn off before all the TRVs shut down? 
Is the radiator circuit balanced correctly at the 
radiator valves? E7 may occur under certain test 
conditions where unnatural operating conditions 
are forced. 

E8 

The PICV actuator cable has 
been  disconnected from the controller or 
there’s a failure on the actuator itself.  
The E8 code appears on the screen.  
Heating  is no longer available. 

To avoid over heating risk , when the HIU detects a 
heating flow temperature 10°C above setpoint for 
more than the programmed time  interval  
(90 seconds factory set, adjustable up to 210   
seconds) the HIU will shut down and show an E8 
error code. Pump will switch off. 

Allow the unit to cool down first! Check PICV 
actuator connection, and that the valve stem pin 
is not jammed (free if possible). 
Power OFF then ON again, check for movement 
in the actuator stem. Replace the actuator if 
found to be seized. Replace the valve cartridge if 
found to be seized. 

Diagnostics - Error code definitions. 

  

When an error code is displayed, the controller is warning of unsuitable operating conditions that may be causing the HIU to operate inefficiently or 

possibly, not at all. If left in that state, these conditions could become a safety issue. 

Page 16

 

e&oe 07/22

Summary of Contents for Hiper II V1

Page 1: ...n and procedures accurate Inta cannot accept responsibility should it be found that in any respect the information is inaccurate or incomplete as a result of future developments Installation and Opera...

Page 2: ...ing installer and a quali ed and competent electrical installer in accordance with the current Building Water and Electrical Regulations Legislation and Standards Do not start installation until you h...

Page 3: ...oved Due care must be given by the installer that the cover heat meter viewing door and components are all accessible Isolation valves ordered separately as accessory pack HIAC03BVPACK Page 3 A C B G...

Page 4: ...lves Strainer with drain valve Pocket for heat meter sensor Isolation valves Pressure independent control valves Plate heat exchanger PHE Expansion vessel Low pressure switch 9 10 11 12 13 14 15 16 Te...

Page 5: ...pendent control valve PICV and fast acting stepper actuator 6 Circulating pump for secondary heating 7 Automatic air vent 8 Safety pressure relief valve 9 Low pressure switch 10 Plate Heat Exchanger 1...

Page 6: ...JIG use as a template for rst x piping use with HIACPFFKIT HI2ACJIG Pack of 4 Secondary straight isolation valves HIAC03BVPACK Prepayment relay for billing systems using a 230v signal HIAC04230KIT Se...

Page 7: ...r maintenance see page 3 The HIU is only for WALL MOUNTING in the orientation shown in this manual Locations where criminal damage or illegal tampering cannot be reasonably preventable Locations where...

Page 8: ...mark up the position for the wall bracket The position of the HIU is to be on a true vertical plane as in 5 3 Drill and plug the wall and secure the HIU with suitable wall xings not provided with the...

Page 9: ...aller The discharge pipe should have a continuous fall and conform to BS6798 Where the pipe empties into a drain then that area must be frost free and consideration as to a trap being included as well...

Page 10: ...e lter mesh by undoing and removing the lter cap Replace the now clean lter mesh and replace the lter cap Remove and store the ushing pipe replace the test plugs and make water tight Do not over tight...

Page 11: ...by 3 x cable glands located beneath the HIU at the rear LHS Live neutral and earth connections as per the diagram below 7 3 Room thermostat connection as per the diagram below This is a 2 core cable c...

Page 12: ...5 OK First start up sequence to ensure the selection of radiators or UFH SET HEATING RADIATOR Change to YES using the UP or DOWN button to initiate the oor drying for a new UFH system SELECT FLOOR HE...

Page 13: ...Heating RETURN The Controller Programming Guide is only for the use of the installer or commissioning engineer and under no circumstances should be left with the user or home owner Incorrect paramete...

Page 14: ...d only as an accessory 00 Manual operation of heating pump overrides room thermostat NO Select type of contact room stat connection switching N OPEN Normally open N CLOSE normally closed N OPEN Descri...

Page 15: ...7 Either the pressure in the heating system is too low or the pressure switch is faulty The HIU will not operate in Heating mode Check the system pressure on the gauge on the HIU The pressure switch w...

Page 16: ...st set the temperature so it is 10C lower than the primary PICV blocked strainer blocked Diverter in the wrong posi on E6 Temperature information from the heating temperature sensors is wrong or unusu...

Page 17: ...applied to the room thermostat connections then the controller maybe damaged beyond repair and will have to be replaced Warranty will not cover this see Installer Controller Parameter Settings Guide Y...

Page 18: ...epayment have NOT been wired to 230V Is there power to the fused spur connecting to the HIU Check power supply and Fuse feeding to the HIU Fused spur requires a 13A Fuse all correct Turn o the potenti...

Page 19: ...SECTION 7 The HIU Controller rst power up and set up SECTION 12 Pump SECTION 7 The HIU Controller rst power up and set up Pump operating and Fault LEDs Page 19 e oe 07 22...

Page 20: ...nimum output 1kW Pump Grundfos UPM3 K FLEX AS 15 75 CIAO2 GFNJB Heating pump nominal head capacity 7 5 kPa Electrical supply 1 ph 50Hz 230v Control method Electronic PID controller with fast acting st...

Page 21: ...h casing base PFAP 1462 00 HIUC PID Controller front cover with touch screen PFFG0652 00 HIUC Controller cable gland CMPD 4066 00 Pump power cable HI29532 025 Pump PWM cable HI29532 035 Power supply c...

Page 22: ...25024045 E 5 M12X1 Drain valve HI29300004 E 8 PICV compact OEM cartridge HI29329005 1 E 7 1 4 test ush port plug HI2602013 E 6 M10 Heat meter temperature probe plug HI225560002 E 9 PICV Cartridge at s...

Page 23: ...in the United Kingdom and Republic of Ireland 3 Except as provided in this extended warranty document and our Standard Terms and Conditions of Sale which can be found online at www intatec co uk which...

Page 24: ...ntatec Ltd Air eld Industrial Estate Hixon Sta ordshire ST18 0PF Tel 01889 272 180 Fax 01889 272 181 Email sales intatec co uk Web www intatec co uk e oe 07 22 Hiper II V1 Heating only single plate HI...

Reviews: