background image

ENGLISH

 

 

 

Quick Installation Guide 

MRX LTE 

 

 

www.insys-icom.com 

These short operating instructions apply for the following devices of INSYS icom: 

 

MRX3 LTE 

 

MRX5 LTE

 

 

www.insys-icom.com/manual 

 

 

It is intended for a quick commissioning by the operator. Refer to the associated manual for further information. 
This and other associated manuals can be found on our website in the menu Support and Downloads > 
Documentation. Scan the QR code above or enter the URL into your web browser.

 

 

Defects liability terms 
A use other than the intended use, an ignorance of the safety instructions and the documentation, the use of insufficiently qualified 
personnel as well as unauthorised modifications exclude the liability of the manufacturer for damages resulting from this. The liability of the 
manufacturer ceases to exist. 

Intended Use 
The product may only be used for the purposes specified in the function overview of the manual. In addition, it may be used for the 
following purposes: 

 

Usage and mounting in an industrial cabinet. 

 

Switching and data transmission functions in machines according to the machine directive 2006/42/EC. 

 

Usage as data transmission device, e.g. for a PLC. 

The product may not be used for the following purposes and used or operated under the following conditions: 

 

Use, control, switching and data transmission in machines or systems in explosive atmospheres. 

 

Controlling, switching and data transmission of machines, which may involve risks to life and limb due to their functions or when a 
breakdown occurs. 

Technical Boundaries 
Max. line length for antennas, power supplies, serial interfaces, inputs and outputs as well as other signals: 30 m 
Max. line length of USB connection lines: 3 m 
Cable cross-section: 0.25 … 1.5 (2.5) mm² (depending on terminal size), flexible lines require end sleeves 

Support 
If you need further support, please contact your sales partner or INSYS icom support. You can contact our support department via e-mail 
under [email protected]

Technical Data 
The product is only intended for the use within the permissible technical limits specified in the data sheets. These limits must be observed. 
 

Operating voltage (redundant) 

12 V … 24 V DC (±20%) 

GSM/GPRS frequencies (2G) 

900, 1800 MHz 

Power consumption 

typ. 2.5 W, max. 8 W 
fully equipped: max. 20 W 

UMTS/HSPA frequencies (3G) 

900, 1800, 2100 MHz 

Level input IN1 

HIGH level = 2 ... 24 V 
LOW level = 0 ... 1 V  
Contact open condition: HIGH 

LTE frequencies (4G) 

800, 900, 1800, 2100, 2600 MHz 

Current consumption input IN1 
at LOW potential 

typ. 0.1 mA when connecting 
to GND 

Real-time clock (RTC) buffer 
time 

typ. 2 days 

Level input IN2 

HIGH level = 10 ... 24 V 
LOW level = 0 ... 5 V  
Contact open condition: LOW 

Temperature range 

-30 °C … 70 °C 
(75 °C restricted) 

Power consumption input IN2 
at HIGH potential 

max. 3 mA at 24 V DC 

Maximum permissible humidity 

95% non-condensing 

 

 

IP rating 

Housing IP40  
Connectors IP30  

 

Summary of Contents for MRX3 LTE

Page 1: ...on in machines or systems in explosive atmospheres Controlling switching and data transmission of machines which may involve risks to life and limb due to their functions or when a breakdown occurs Technical Boundaries Max line length for antennas power supplies serial interfaces inputs and outputs as well as other signals 30 m Max line length of USB connection lines 3 m Cable cross section 0 25 1...

Page 2: ...4 TCP IP and Properties Enable DHCP client 9 Obtain an IP address automatically It is recommended to unplug the network cable briefly and plug it again upon activation of the DHCP client Configure a static IP address Use the following IP address example IP address 192 168 1 2 Subnet mask 255 255 255 0 Standard gateway 192 168 1 1 Preferred DNS server 192 168 1 1 Please note the previous values bef...

Page 3: ...mer name and Device code Then the IP address in the local network will be assigned by the icom Connectivity Suite VPN The WAN LED flashes green during connection establishment as soon as an Internet connection has been established it is illuminated green and the Signal LED flashes orange E Configuration of access data User name and password for web interface access of the existing user in the defa...

Page 4: ...ation Reset 2 Click on Reboot device now Alternatively press reset key on the device front once for a short time soft reset Resetting the router to default settings If the router is to be reset to default settings it can be reset to delivery state 1 Menu Administration Reset check all options 2 Click on Reset now Alternatively press reset key on the device front three times for a short time within...

Reviews: