INSYS Powerline GP
Assembly
23
8
Assembly
This chapter describes how to mount the INSYS Powerline GP to a DIN rail,
connect the power supply, connect the communication line and uninstall it
again. Observe the instructions in the "Safety" section of this manual, in
particular the "Safety Instructions for Electrical Installation" for that purpose
unconditionally.
Danger!
Exposed electrical components!
Risk of fatal injury from electric shock.
Prior to the installation, switch the power supply of the
cabinet off and secure it against being switched on again.
Danger!
Potentially lethal operating voltage!
Risk of death through shock hazard when touching it.
The INSYS Powerline GP is an electronic device, which
may only be used for fixed installation. The INSYS
Powerline GP must be installed that it cannot be touched
by the user after installation. An access to the installed
device may only be possible using tools, keys or removing
an internal cover. Moreover, a warning sign must be
attached, which warns against potentially tangible
energised components.
Danger!
Potentially lethal operating voltage!
Risk of death through shock hazard when touching it.
The power line used for communication must provide an
easily accessible, fixed installed cut-off device and a an
automatic cutout. The automatic cutout must be designed
for a maximum nominal current of 16A. The cut-off device
must be designed bipolar for ungrounded power supply
networks (e.g. IT network or DC supply without PE
reference).