Instanta UCCH1000 Installation Information & User Instructions Download Page 5

The unit has been placed on a solid floor and the front vent-cover plate removed to allow air-flow in

through the front. The unit has been positioned at least 175mm away from the wall so there is sufficient

space at the back of the unit to allow warm exhaust air to be expelled to atmosphere.

As the installation is open-plan (not enclosed), warm air expelled will simply disperse into the room

space (providing the room is well ventilated and of sufficient size) - there should not be any need to

duct away from the unit.

4)    INSTALLATION INSTRUCTIONS:

Please read the following, referring to scenario/diagram 1 (above):

If the under-counter unit is to be located within an enclosed kitchen cupboard, the standard ventilation

kit (supplied) must be fitted as per the following instructions. This allows cool air to be drawn in from a

vent in the kick-board at the front of the cupboard, and warm air is blown out through the rear panel in

the cupboard into the void between the cupboard and the wall.

NOTE: The rear panel of the cupboard should not be too close to the wall…a gap of 50mm will be

sufficient in most cases. In virtually all installations, the warm air will then be able to escape from this

area easily and no additional ventilation will be necessary. However, if the back of the cupboard is

completely sealed to the wall and there is no way for heat to escape, the chiller will not work correctly

and additional ventilation will be necessary to allow the warm air to escape (see Scenario/diagram-2

above using alternative ducting kit - not supplied).

INSTRUCTIONS (using Standard vent kit):

1)      Before installation, ensure there is an electrical socket in close proximity to the intended site of 

        the chiller. If not it will be necessary to have one fitted by a qualified electrician.

2)      Also ensure there is adequate space at the back of the cupboard and a way for the warm air to

        escape…a 50mm void between the panel and the wall should be sufficient.

3)      Identify the best location for the chiller, water-font and filter. Plan the connection to a water mains

        supply, routing of any tubes and location of components to ensure the installation is as unobtrusive

        as possible.

4)      It is also necessary to ensure that the air inlet duct will not clash with any legs or other obstacles

        in the cupboard kick space.

5)      Using the paper TEMPLATE-A (BASE), mark the position of the chiller sides on the base of the

        cupboard, and the position of the opening for the air-inlet. Using template B, mark the opening for

        the exhaust air in the back of the cabinet.

6)      Referring to the drawing, mark out the position of the opening in the kick-board and cut out the air

        inlet hole in the kick board.

        NOTE: Dimensions are measured from the left-side and bottom of the chiller (see drawing). The

        left side of the chiller should have been marked onto the base (see 5, above).

7)      Insert the right-angled spigot into the hole in the base of the cabinet.

8)      Fit the length of rectangular duct through the cut-out in the kick-board and into the spigot. Ensure

        it is fully engaged into the socket and mark the ducting where it protrudes from the kick board.

        Remove the duct and cut to length.

9)      Refit the rectangular duct, and attach the outlet grill to the kick-board using 4 screws. This will

        retain the duct in position.

10)     Now place the chiller unit in position over the air inlet opening, ensuring the outlet grill on the

        back of the machine aligns with the back of the cabinet.

Important: The ventilation openings must align with the cut-outs in the cabinet to ensure reliable

operation of the chiller, and the chiller should be fixed in position to prevent the chiller being

moved inadvertently.

Failure to provide sufficient ventilation and air-flow will seriously impair the performance of the

chiller and may cause overheating which will invalidate the guarantee.

Summary of Contents for UCCH1000

Page 1: ...FORMATION USER INSTRUCTIONS Instanta Limited Canning Road Southport Merseyside PR9 7SN Tel 01704 501114 Fax 01704 501115 Email info instanta com Website www instanta com Join us at www facebook com instantaltd InstantaLtd IB28a The Professional s Choice ...

Page 2: ...sed space e g kitchen cupboard Flexible water inlet hose assembly c w water purification filter NOTE An alternative ventilation kit is available from Instanta Spares Part No UCC D1 for installations within an enclosed cupboard that don t have a void space see Scenario 2 below 3 IMPORTANT INFORMATION FOR INSTALLATION The Instanta UCCH1000 Dry Chiller is designed to be fitted underneath a counter to...

Page 3: ... base of cupboard Void at back of cupboard minimum of 50mm Use TEMPLATE B to mark the opening for the exhaust air in the back of the cupboard void FRONT VENT COVER PLATE leave in place if vent kit and ducting are used as in this diagram Remove if vent kit is not being used and unit is placed on a solid floor instead Warm air expelled to avoid it being circulated within the cupboard space Use TEMPL...

Page 4: ...being recirculated within the cupboard space and therefore fulfils installation requirements SCENARIO 3 Typical installation NOT enclosed In this scenario the under counter unit is located underneath a work surface but not enclosed by a cupboard VIEW FROM ABOVE WARM AIR EXPELLED to avoid it being circulated within the cupboard space FRONT VENT COVER Remove if unit is placed on a solid COLD AIR INL...

Page 5: ...e space at the back of the cupboard and a way for the warm air to escape a 50mm void between the panel and the wall should be sufficient 3 Identify the best location for the chiller water font and filter Plan the connection to a water mains supply routing of any tubes and location of components to ensure the installation is as unobtrusive as possible 4 It is also necessary to ensure that the air i...

Page 6: ... replace screw Then secure the bracket by driving the self tapping screw to the cabinet base g Cut the blue water feed tube to size if too long and push into the CHILLED WATER OUT coupling It is advisable to fit insulation to the tube between the font and the chiller unit h Plug electrical lead into socket on top of chiller unit marked FONT CONTROL Important The ventilation openings must align wit...

Page 7: ...hiller unit at the back To adjust pull valve adjuster upwards and turn clockwise to increase pressure flow rate and anti clockwise to reduce As a guide a small cup 180ml should take approximately 5 seconds to dispense NOTE If the flow rate is faster than this the water will pass through the cooling block too quickly and the drink may not be as cool as it should be 9 TECHNICAL SPECIFICATIONS Under ...

Reviews: