Mechanical Specifications and Installation Diagram

6.0  Testing Procedure

Make the following resistance measurements with a digital multimeter with all wires removed from the 

SSC3.

1.  Measure the resistance between the two power terminals (BAT+ to LOAD).  The resistance should 

be 150-160 kOhms in either direction.

2.  Measure the resistance from the control INPUT terminal to the GND terminal. The “+” probe should 

be on the INPUT and “-” probe on the GND. The resistance should be 130 kOhms.

3.  Measure the resistance to ground of each power terminal to a GND terminal with the “+” probe on 

the power terminal and “-” probe on the GND.       

4.  The resistance should be 104K 

(BAT+) 

and 50K 

(LOAD)

 Ohms.

0.20

INPUT

BAT +

LOAD

12V  200 AMP SOLID STATE CONTACTOR

4.125

0.375

LED

GND

2.375

4.125

3.40

2.50

1.688

1.125

3.125

3.775

0.75

0.875

Double Crimp Lugs

Customer Supplied

0.813

1.4375

3.775

3.40

www.InPowerLLC.com

Lot Code

I

n

P

OWER 

the systems people

SSC3-200A

7.0-18Vdc

INPUT 

8.0-18Vdc

0.625

Patented

www.InPowerLLC.com/Patents

Electronic

Switch

0.20

INPUT

BAT +

LOAD

5.125

0.375

GND

4.125

3.775

2.50

1.688

1.125

3.125

4.775

3.40

3.375 2.375

I

n

P

OWER 

the systems people

www.InPowerLLC.com

Lot Code

SSC3-200B

7.0-18Vdc

INPUT 

8.0-18Vdc

LED

Double 

Crimp Lugs

Customer 

Supplied

Double Crimp Lugs 

Brass Bolt and Copper Washer 

Torque 10 to 15 Ft Lbs.

Ground Wire

To a good quality ground

(Optional User supplied) Small amount of Silicon Thermal Compound

METAL MOUNTING SURFACE

Mounting Bolt

Torque 8-32 mount-

ing bolts to 4-5 Inch 

Pounds

4-5 Inch Pounds

Do Not Stack Lugs!

If Multiple Terminations are necessary,

 please refer to the SSC3-200B

Dimensions are in Inches

Optional Input 

Control Wire 

(Boost)

12V  200 AMP SOLID STATE CONTACTOR

Electronic

Switch

Same Dimensions as 

SSC3-300

Summary of Contents for SSC3

Page 1: ...ith starting up into resistive loads inductive loads capacitive loads incandescent loads and identifies dead short faults The status LED indicator is on when the SSC3 is ON off when OFF and flashes to indicate a fault shutdown Automatic fault shutdown occurs for over current loss of ground high low battery voltage and or over temperature In a fault condition the contactor is latched in the off sta...

Page 2: ...rational Temperature Range 40 o to 185 o F 40 o to 85 o C Over temperature Shutdown 185 o F 85 o C Operational Voltage Range 7 0 to 18 0 Volts Fault Reset Remove Voltage 4 0V and then reapply a voltage 8 0V if no faults exist LED Indicator Switch on LED ON Switch off LED Off Faults exist LED Flash INPUT Signal Voltage Range 8 0 to 18 0 Volts True ON 4 0 Volts False OFF Standby Current 3 8mA Enviro...

Page 3: ...mal ef ficiency the mounting surface should be a thick metal surface such as an aluminum plate 1 8 x 16 x 16 inches or larger To facilitate heat transfer please apply a thin layer of silicon thermal material user supplied to the metal plate on the bottom of the SSC3 Smooth this out with a flat edge to insure there are no gaps Secure the contactor to the flat metal surface using four screws and tig...

Page 4: ...K LOAD Ohms 0 20 INPUT BAT LOAD 12V 200 AMP SOLID STATE CONTACTOR 4 125 0 375 LED GND 2 375 4 125 3 40 2 50 1 688 1 125 3 125 3 775 0 75 0 875 Double Crimp Lugs Customer Supplied 0 813 1 4375 3 775 3 40 www InPowerLLC com Lot Code InPOWER the systems people SSC3 200A 7 0 18Vdc INPUT 8 0 18Vdc 0 625 Patented www InPowerLLC com Patents Electronic Switch 0 20 INPUT BAT LOAD 5 125 0 375 GND 4 125 3 77...

Reviews: