Page 4 of 4
October 2013 Rev 1
The shutters are clipped to the pan and tilt module as shown in
Figure 5. Each vertical section of the Fresnel lens gives a
coverage pattern of approximately 10 degrees.
An additional set of shutters is provided for further adjustment.
Figures 7, 8 and 9 show typical beam patterns. A pet alley can
be created my applying the lens mask as shown in Figure 9.
Programming
Figure 10 shows the position of the programming button (2)
and the programming LED (1).
Table 1: Programming settings
Option
1
2
3
1.
Range (m)
10
20
30*
2.
Pulse count
1*
2
•
Default settings
Pulse count is the number of detections before signalling an
alarm. Pulse count 1 is most sensitive.
Changing settings:
1. Press the programming button once for range and twice
for pulse count.
2. Wait until the programming LED turns off (typically
4 seconds).
3. Count the number of times the LED flashes to determine
the current value for that option.
4. Press the programming button to select the value number
for the new setting. E.g. to change the range to 20m,
press twice.
The LED blinks twice to indicate that the new value was set.
Programme settings are stored in non-volatile memory.
Resets
1. Remove the batteries.
2. Press and hold the programming button (See Figure 10,
item 2).
3. Refit the batteries.
4. After the programming LED has flashed, release the
programming button.
Learning to control panels/receivers
When the control panel/receiver is in learn mode press the
detector programme button once. After about 10 seconds the
wireless detector will be learnt on to the control panel.
Walk test
In walk test mode, the detection LED option is set to ‘ON’ and
the detection LED will illuminate on detection.
To enter the walk test mode, press the programming button
once. The unit can now be aligned.
Walk test mode ends automatically five minutes after the last
detection.
Do not conduct walk tests with the cover removed.
The range of the detector increases without the protective front
cover. Therefore the front cover must be fitted to establish the
correct beam pattern. Adjust the range as necessary. Pan and
tilt the detector module over the field of view to obtain the
correct coverage.
Specifications
Detection range
Programmable: 10, 20 or 30m
Coverage
10 to 70° detection angle, 30 x 25m
coverage max.
Adjustment
180° pan, 90° tilt
Fresnel lens
28 zones for each detection element, which
can be masked with the curtain sliders
Optics
Double silicon shielded quad element
eliminates 50,000 Lux of white light
LED
Red alarm
Batteries
2x 3 V CR123
Current
30
µ
A
Pulse count
1 or 2
Control
Digital micro. with non-volatile memory
Walk test
Output test mode with LED indication
Operating temperature
−
25 to +65°C
Housing
High impact ABS plastic with HDPE cover,
UV stabilised
Dimensions W x H x D
145 x 145 x 120mm
Weight
268g Net, 425g Gross
Mounting height
Variable up to 6m
Optimum height 3m
Compliance
Manufacturer
GJD Manufacturing Limited, Unit 2, Birch Business
Park, Whittle Lane, Heywood, Lancashire, OL10
2SX, UK
Certification
R&TTE
This device is in compliance with the essential
requirements and other relevant provisions of
Directive 1999/5/EC.
Environmental
class
IP65
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper
recycling, return this product to your local supplier
upon the purchase of equivalent new equipment, or
dispose of it at designated collection points. For
more information see: www.recyclethis.info.