‑75‑
Table 5–24 Selection of Schaffner AC input reactors (three phase 200‑240 V)
Structure
Model
Applicable Reactor
Inductance
(mH)
Loss (W)
T1
MD520‑2T0.4B(S)
RWK 3044‑3.5‑88‑E0XXX
8.3
32
MD520‑2T0.7B(S)
RWK 3044‑6.5‑88‑E0XXX
4.6
47
MD520‑2T1.1B(S)
RWK 3044‑6.5‑88‑E0XXX
4.6
47
MD520‑2T1.5B(S)
RWK 3044‑12‑88‑E0XXX
2.44
69
T2
MD520‑2T2.2B(S)
RWK 3044‑12‑88‑E0XXX
2.44
69
MD520‑2T3.7B(S)
RWK 3044‑18‑89‑E0XXX
1.67
103
T3
MD520‑2T5.5B(S)
RWK 3044‑35‑92‑E0XXX
0.83
151
T4
MD520‑2T7.5B(S)
RWK 3044‑48‑92‑E0XXX
0.61
172
T5
MD520‑2T11(B)(S)
RWK 3044‑59‑92‑E0XXX
0.5
206
T6
MD520‑2T15(B)(S)
RWK 3044‑59‑92‑E0XXX
0.5
206
MD520‑2T18.5(B)(S)
RWK 3044‑72‑99‑E0XXX
0.41
294
T7
MD520‑2T22(B)(S)
RWK 3044‑59‑92‑E0XXX
0.5
206
MD520‑2T30(B)(S)
RWK 3044‑120‑99‑E0XXX
0.24
324
T8
MD520‑2T37(B)(S)
RWK 3044‑140‑99‑E0XXX
0.2
399
MD520‑2T45(S)
RWK 3044‑180‑99‑E0XXX
0.17
456
MD520‑2T55(S)
RWK 3044‑210‑99‑E0XXX
0.14
553
T9
MD520‑2T75(S)
RWK 3044‑320‑99‑E0XXX
0.092
747
T10
MD520‑2T90(S)
RWK 3044‑400‑99‑E0XXX
0.073
1055
MD520‑2T110(S)
RWK 3044‑510‑99‑E0XXX
0.058
1069
T11
MD520‑2T132(S)
RWK 3044‑510‑99‑E0XXX
0.058
1069
T12
MD520‑2T160(S)
RWK 3044‑570‑99‑E0XXX
0.052
1181
MD520‑2T200(S)
RWK 3044‑800‑99‑E0XXX
0.037
1280
5.4.3 EMC filter
Overview
To comply with the radiated and conducted emission requirements of EN IEC 61800‑
3, install the EMC filter. The following EMC filters can be used.
For 132 kW to 400 kW AC drives, built‑in filters can meet requirements of EN 618003
C3. Therefore, external filters are not required.
Summary of Contents for MD520 Series
Page 1: ......
Page 16: ...Components 15 Figure 2 2 Components of T5 to T6 models...
Page 19: ...Components 18 Figure 2 5 Components of T10 to T12 models with AC output reactor...
Page 27: ...System Structure 26 Figure 3 9 Control circuit terminals...
Page 43: ...Options 42 Figure 5 2 Dimensions of MD500 AZJ A1T2 through hole mounting bracket and holes mm...
Page 44: ...Options 43 Figure 5 3 Dimensions of MD500 AZJ A1T3 through hole mounting bracket and holes mm...
Page 45: ...Options 44 Figure 5 4 Dimensions of MD500 AZJ A1T4 through hole mounting bracket and holes mm...
Page 46: ...Options 45 Figure 5 5 Dimensions of MD500 AZJ A1T5 through hole mounting bracket and holes mm...
Page 47: ...Options 46 Figure 5 6 Dimensions of MD500 AZJ A1T6 through hole mounting bracket and holes mm...
Page 49: ...Options 48 Figure 5 8 Dimensions of MD500 AZJ A1T8 through hole mounting bracket and holes mm...
Page 54: ...Options 53 The following figures shows the installed copper busbar...
Page 115: ...Options 114 Figure 5 48 Dimension drawing of ferrite clamp...
Page 120: ...Expansion Cards 119 Figure 6 1 Installation position of expansion cards...