POWER UP :
At power on, following sequence will be prompted on the display till it reaches to Home display mode.
In home display mode, by pressing SET key once user can view SP value.
MODEL
HOME
PV
VERSION
INPUT
User can change SP value using UP/ DOWN keys. Holding the key, will change the
value at a faster rate. Press SET key to store the value & move on to next parameter.
o
0 C
LSPL ~ HSPL
CONTROL
SET POINT
PROGRAMMING
USER LIST :
To access the user list Press & Release SET key once.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
CONTROL LIST :
SET & DOWN key simultaneously
To enter in this mode, press
for 3 sec. User can then set
all the control related parameters as shown below.
0
1 ~ 9999
Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in Config.
List.
0.5
to
99.9°C
o
1 to 25 C
0.5
to
100.0 Sec.
0
to
500 Sec.
-25
to
o
25 C
This parameter will appear only if selected control action is T.P. It sets
bandwidth over which the output power is adjusted depending upon the error
(SV-PV).
This parameter will appear only if selected control action is T.P. User can set
this value based on process being controlled & type of output being selected.
For Relay O/P, cycle time should be more than 12 Sec & for SSR O/P, cycle time
should be less than 5 Sec.
This parameter will appear only if selected control action is ON-OFF. It sets the
main output restart time. If set to '0', O/P will be switched without delay. Also,
Delay will be considered in case of every power ON.
This parameter will appear only if selected control action is ON-OFF. It sets the
dead band between ON & OFF switching of the Output. Larger value of
hysterisis minimize the number of ON-OFF operation of the load. This
increases life of actuators like Relay but, also produces large errors.
o
5.0 C
16.0 Sec.
0 Sec.
2°C
P.BAND
CYCLE
TIME
CONTROL
HYS.
DELAY
LOCK
CODE
CONFIGURATION LIST :
key simultaneously
(1) To enter in this mode, Press and hold SET & UP
for 3 sec.
(2) Press UP or DOWN key to scroll between parameter options.
(3) Press SET key to store the current parameter & move on to the next parameter.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
J
INPUT
TYPE
This parameter value is set according to the type of sensor (Thermocouple or RTD Input)
connected to the Controller's Input Terminals.
PARA
METER
DESCRIPTION
DEFAULT
DISPLAY
0
LOCK
CODE
Set this parameter to 15 (Default LOCK CODE) to access Config. List.
User has a choice to set different Lock Code in the range
via USER LOCK CODE
in Config. List.
1 ~ 9999
MANUAL
OFF SET
o
0 C
This parameter will appear only if selected C.A is time proportional.
(For more details refer User guide.)
Fe-k(J) T/C
Cr-AL(K) T/C
Sensor Type
Accuracy
o
± 1 C
o
0 ~ 1700 C
o
0 ~ 1700 C
o
-100 ~ 450 C
Resolution
Range
o
1 C
o
1 C
o
1 C
}
(R) T/C
(S) T/C
Pt-100(RTD)
Pt-100(RTD 0.1)
o
0
~
760 C
o
-99
~
1300 C
o
-99.9 ~ 450.0 C
o
1 C
o
1 C
o
0.1 C
o
± 0.3 C