28
N
No/ineffective cooling
No/ineffective heating
Whether the display panel
display one of the following
signal? "Er En Eo Ed"
Er¡ -indicates room temp. sensor failure
En indicates indoor pipe sensor failure
Eo indicates outdoor pipe sensor failure
Ed indicates that the evap. Is frosting
: For reverse cycle model
Whether the compressor can
start in cooling/heating mode
even if it soon stops?
Yes
No
Yes
Check whether the indoor
outlet/inlet of the unit
is blocked or the vent
door is open
No
Check temperature. setting
Check Wiring
Check compressor capacitor
Check the voltage between
RY9 on main PCB and N
on power cord
Replace the compressor
Replace the main PCB
No voltage
Check whether the indoor
outlet/inlet of the unit
is blocked or the vent
is blocked
Check whether the Evap.is
frosting and the compressor
stops frequently
Check the speed of motor
Check leakage
Recycle refrigerant and
braze the leakage point
Vaccum and recharge
Check the drainage
Check whether the Cond.is
frosting and the compressor
stops frequently
Check the speed of motor
Check the control wire of
the reverse valve
Check whether the temp. of
suction pipe is above 7
℃
Replace the capillary tube
Replace the reverse valve
Replace the compressor
Recycle refrigerant and recharge
Check the voltage between P11
on main PCB and N on power
Replace the reverse valve
Replace the Main PCB
No voltage
Yes
No
In cooling
Yes
Normal
Check the fan capacitor
Replace the motor
Normal
Yes
Leakage
Yes