HEAT PUMP

DUCTLESS SPLITS

OWNER & INSTALLATION 

MANUAL

WARNING

• The information contained in the manual is intended for use by a qualified service technician

familiar with safety procedures and equipped with the proper tools and test instruments

• Installation or repairs made by unqualified persons can result in hazards to you and others.

• Failure to carefully read and follow all instructions in this manual can result in equipment

malfunction, property damage, personal injury and/or death.

• This service is only for service engineer to use.

EIN10H2V32 

EIN13H2V32
EIN18H2V32
EIN24H2V32 

Summary of Contents for Elite EIN10H2V32

Page 1: ...nd equipped with the proper tools and test instruments Installation or repairs made by unqualified persons can result in hazards to you and others Failure to carefully read and follow all instructions in this manual can result in equipment malfunction property damage personal injury and or death This service is only for service engineer to use EIN10H2V32 EIN13H2V32 EIN18H2V32 EIN24H2V32 ...

Page 2: ...2 6 1 Remote Controller Introduction 12 6 2 GREE App Operation Manual 17 6 3 Ewpe Smart App Operation Manual 18 6 4 Brief Description of Modes and Functions 19 Part II Installation and Maintenance 24 7 Notes for Installation and Maintenance 24 8 Installation 27 8 1 Installation Dimension Diagram 27 8 2 Installation Parts checking 29 8 3 Selection of Installation Location 29 8 4 Requirements for el...

Page 3: ... 56 10 1 Indoor Unit 56 10 2 Outdoor Unit 58 11 Removal Procedure 72 11 1 Removal Procedure of Indoor Unit 72 11 2 Removal Procedure of Outdoor Unit 77 Appendix 82 Appendix 1 Reference Sheet of Celsius and Fahrenheit 82 82 Appendix 3 Pipe Expanding Method 83 Appendix 4 List of Resistance for Temperature Sensor 84 SERVICE MANUAL Innovair Elite Mini Split ...

Page 4: ...it Outdoor Unit Remote Controller Part I Technical Information EIN10H2V32 O EIN13H2V32 O EIN18H2V32 O EIN24H2V32 O RCTL ELITE2 EIN10H2V32 I EIN13H2V32 I EIN18H2V32 I EIN24H2V32 I SERVICE MANUAL Innovair Elite Mini Split 1 ...

Page 5: ...1 22 45 079 16 142 13 189 44 291 15 63 12 598 Dimension of Package L W H inch 41 0 14 9 12 2 40 157 14 528 11 614 45 197 16 26 13 78 45 079 15 748 12 992 Net Weight lb 29 8 29 8 36 4 35 3 Gross Weight lb 36 4 36 4 43 0 43 0 Outdoor Unit Model EIN10H2V32 O EIN13H2V32 O EIN18H2V32 O EIN24H2V32 O Compressor Trademark GREE GREE GREE GREE Compressor Model QXAT B121zE070 QXAT B121zE070 QXAT D20zF030 QXA...

Page 6: ... Several Optional Filte rs Optional Optional Optional YES Auto Clean NO NO NO NO Timer YES YES YES YES Auto Restart YES YES YES YES Turbo YES YES YES YES Clock YES YES YES YES Temperature YES YES YES YES Function Soft Start YES YES YES YES Self Diagnosis YES YES YES YES Lock YES YES YES YES CO Detection NO NO NO NO CO2 Detection NO NO NO NO Filter Dirty Alarm NO NO NO NO Intelligent Open Close Pan...

Page 7: ...t A 50 60 70 80 90 100 110 120 130 Capacity ratio Condition Indoor DB81 F WB66 F Indoor air flow Turbo Pipe length 5m Capacity ratio g n i t a e H g n i l o o C 110 120 130 100 90 80 70 60 50 Condition Indoor DB68 F Indoor air flow Turbo Pipe length 5m Cooling Cooling Heating Heating Cooling Capacity ratio Heating 100 105 95 90 85 80 75 70 65 60 55 50 Capacity ratio Condition Indoor DB81 F WB66 F ...

Page 8: ... heat exchanger Fan speed of indoor unit Fan speed of outdoor unit Compressor revolution Hz Indoor Outdoor P MPa T1 F T2 F 68 45 43 362 3 435 in 122 176 out 99 109 in 34 37 out 36 41 Super High High 56 Instruction T1 Inlet and outlet pipe temperature of evaporator T2 Inlet and outlet pipe temperature of condenser P Pressure at the side of big valve Connection pipe length 24 6ft Cooling Heating 2 5...

Page 9: ...2 1 6 Φ2 1 6 3 7 64 6 1 21 32 8 7 64 27 7 21 64 Φ2 3 4 Φ2 3 4 Unit inch 3 7 64 6 1 21 32 8 7 64 27 7 21 64 Φ2 3 4 Φ2 3 4 9 12K Wall Mount Bracket 18 24K Wall Mount Bracket C E D G B F A Size W D H 9K 38 9 11 12K 38 9 11 18K 43 9 12 24K 42 9 12 Size A B C D E F G 9K 32 35 12 15 23 21 13 12K 32 35 12 15 23 21 13 18K 36 39 14 16 37 24 15 24K 36 39 14 16 37 24 15 ...

Page 10: ...iner Capillary D Strainer Intercooler SERVICE MANUAL Innovair Elite Mini Split 7 INDOOR UNIT OUTDOOR UNIT HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR GAS SIDE 3 WAY VALVE LIQUID SIDE 2 WAY VALVE COOLING HEATING Accumlator Discharge Suction 4 Way valve Electron Electron Strainer Strainer expansion expansion valve valve Strainer D Strainer Intercooler 24K 9K 12K 18K Pipe Connections ...

Page 11: ... Name WH White GN Green CAP Jumper cap YE Yellow BN Brown COMP Compressor RD Red BU Blue Grounding wire YEGN Yellow Green BK Black VT Violet OG Orange Note Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model 6361000044202 8 SERVICE MANUAL Innovair Elite Mini Split ...

Page 12: ... Outdoor Unit These wiring diagrams are subject to change without notice please refer to the one supplied with the unit 6361000044501 N 1 2 3 SERVICE MANUAL Innovair Elite Mini Split 9 9K 12K ...

Page 13: ...10 Innovair Elite Mini Split Outdoor Unit These wiring diagrams are subject to change without notice please refer to the one supplied with the unit 18K 24K 63610000440 600007000653 ...

Page 14: ...me 1 Neutral wire 2 Needle stand for indoor fan 3 Detecting plate WIFI 4 Up down swing motor 5 left right swing motor 6 Interface of temperature sensor 7 Terminal for display board connection 8 Terminal of jumper cap 9 Communication wire 10 Wired controller 11 Fuse 12 Live wire interface 5 2 PCB Printed Diagram ...

Page 15: ...ce of electronic expansion valver 6 Neutral wire of electric heater for chassis 10 Power supply neutral wire 14 Temp sensor 3 Interface of fan 7 Neutral wire of 4 way valve 11 Power supply live wire 15 Input of overload 4 Live wire of 4 way valve 8 Live wire of electric heater 12 indoor and outdoor unit Communication wire with 16 U V compressor W three phases of 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 16: ...er supply neutral wire 11 PFC induction wire 18K Outdoor Unit 24K 1 2 3 4 5 6 7 8 9 10 11 12 13 14 No Name 1 Interface of compressor 2 Interface of temperature sensor 3 Terminal of compressor overload protection 4 Low temperature cooling sensor 5 Cooling A valve 6 Cooling B valve 7 Interface of outdoor motor 8 Interface of 2 way valve 9 Interface of 4 way valve 10 Terminal of chassis electric heat...

Page 17: ...Remote Controller Note This is a general use remote controller it could be used for the air conditioners with multifunction For some function which the model don t have if press the corresponding button on the remote controller that the unit will keep the original running status After putting through the power the air conditioner will give out a sound Operation indicator is ON red indicator the co...

Page 18: ...Heat mode press this button can turn on or turn off the Turbo function After the Turbo function turned on the signal of Turbo will display The signal will Press this button to set left right swing angle cycling as below be automatically cancelled if changing the mode or fan speed button 6 7 7 OFF 3 MODE button Press this button Auto Cool Dry Fan Heat mode can be selected circularly Auto 4 button t...

Page 19: ...mbient the displaying range is 0 60 When it goes beyond the range it keeps the threshold data the smallest 0 and the largest 60 Warm tips When operating buttons on the cover please make sure the cover is closed completely button 11 Press this button once to turn on the I FEEL function then the figure of I FEEL will be displayed after every press of other function button every 200ms to send I FEEL ...

Page 20: ...re setting finished Introduction for special function About AUTO RUN When AUTO RUN mode is selected the unit will be in accordance with the room temp automatically to select thesuitable running method and to make ambient comfortable About turbo function If start this function the unit will run at super high fan speed to cool or heat quickly so approachs the preset temp as soon as possible that the...

Page 21: ...e no obstacles between them remote controller should be close to indoor unit during operation Replace new batteries of the same model when replacement is required When you don t use remote controller for a long time please take out the batteries If the display on remote controller is fuzzy or there s no display please replace batteries 5 1 2 3 4 5 Pressing and button to select the swing battery Co...

Page 22: ...plication market to download and install it When Ewpe Smart App is installed register the account and add the device to achieve long distance control and LAN control of smart home appliances For more information please refer to Help in App iOS system Support iOS7 0 and above version Android system Support Android 4 4 and above version Internet Cellular Other Wi FI Home Wi Fi Home wireless router H...

Page 23: ...w its simple step by step instructions to register your account and complete setup STEP 3 Let the app be your guide You are well on your way to controlling the unit through your smartphone You will find operation to be simple and easy allowing you to adjust comfort levels even without the remote from anywhere you have WIFI access COMMON NETWORK SETTING PROBLEMS If WIFI control fails check the foll...

Page 24: ... protection is detected the compressor will stop the outdoor fan will stop after 30 seconds and the indoor fan and swing motor will keep running in the original mode When antifreezing protection is eliminated and the compressor has stopped for 3 minutes the compressor will resume running in the original mode 2 Dehumidifying Mode Working conditions and process of dehumidifying If Tamb Tpreset the u...

Page 25: ...and H1 will be displayed at temperature display area on the display panel Defrost frequency is 85Hz Protection Cold air prevention The unit is started under heating mode the compressor is ON In the case of T indoor amb 24 C 75 2 F if T tube 40 C 104 F and the indoor fan is at stop state the indoor fan will begin to run at low speed with a time lag of 2 minutes Within 2 minutes if T tube 40 C 104 F...

Page 26: ...ssor will resume its operation If module protection occurs six times in succession the compressor will not be started again Overload protection If temperature sensed by the overload sensor is over 115 the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds If temperature is below 95 the overload protection will be relieved DC bus voltage protection If voltage on the DC...

Page 27: ...25 25 24 25 26 26 26 26 26 25 25 25 26 27 27 27 27 27 26 26 26 27 28 28 28 28 28 27 27 27 28 29 29 29 29 29 28 28 28 29 29 29 29 29 29 28 28 29 30 30 30 30 30 30 29 29 30 30 30 30 30 30 30 29 29 2 In heating mode 2 1 When the initial set temperature is 16 C 60 8 F the unit will keep on running at this temperature 2 2 When the initial set temperature is 17 20 C 62 6 68 F the temperature will decrea...

Page 28: ...ontrol by remote controller Stay at position B control by remote controller Stay at position C control by remote controller Stay at position D control by remote controller Swing between L and D control by remote controller Stop at any position between L and D angles between L and D are equiangular control by remote controller OFF When turning off the unit vertical louver will close at position O S...

Page 29: ...ve the unit adequately grounded The grounding wire can t be used for other purposes 6 Must apply protective accessories such as protective boards cable cross loop and wire clip 7 The live wire neutral wire and grounding wire of power supply must be corresponding to the live wire neutral wire and grounding wire of the air conditioner 8 The power cord and power connection wires can t be pressed by h...

Page 30: ...nt recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe If compressor starts running when stop valve is open and connection pipe is not yet connected air will be sucked in and cause pressure rise or compressor rupture resulting in injury When installing the unit make sure that connection pipe is securely connected before...

Page 31: ...eakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 Torque wrench open end wrench inner hexagon spanner 9 Pressure meter 12 Soldering appliance refrigerant container 28 SERVICE MANUAL Innovair Elite Mini Split ...

Page 32: ...ast 98 7 16 inch At least 5 7 8 inch At least 5 7 8 inch At least 118 inch Space to the obstruction Drainage pipe Space to the wall Space to the obstruction Space to the obstructio Space to the obstruction At least 19 11 16 inch Atleast1113 16inch At least 19 11 16 inch At least 11 13 16 inch At least 78 5 8 inch SERVICE MANUAL Innovair Elite Mini Split 29 ...

Page 33: ...e wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installation Note this flow is only for reference please find the more detailed installation steps in this section Select outdoor unit installation location Install the support of outdoor unit select it according to the actual situation Install drainage...

Page 34: ...cation where the condensation water can be dispersed easily and wont affect other people 3 Select a location which is convenient to connect the outdoor unit and near the power socket 4 Select a location which is out of reach for children 5 The location should be able to withstand the weight of indoor unit and wont increase noise and vibration 7 Dont install the indoor unit right above the electric...

Page 35: ...n Fig 9 4 Outlet Pipe 1 The pipe can be led out in the direction of right rear right left or rear left As show in Fig 3 2 When selecting leading out the pipe from left or right please cut off the corresponding hole on the bottom case As show in Fig 4 2 Open a piping hole with the diameter of 2 1 6 or 2 3 4 on the selected outlet pipe position In order to drain smoothly slant the piping hole on the...

Page 36: ...hen binding them When binding to a certain degree separate the indoor power and then separate the drain hose As show in Fig 15 3 Bind them evenly 4 The liquid pipe and gas pipe should be bound separately at the end 9 Hang the Indoor Unit 1 Put the bound pipes in the wall pipe and then make them pass through the wall hole 2 Hang the indoor unit on the wall mounting frame 3 Stuff the gap between pip...

Page 37: ... must set a U shaped curve in the pipe before pipe goes into the room in order to prevent rain from getting into the room As show in Fig 24 2 Install Drain Joint Only for cooling and heating unit 1 Connect the outdoor drain joint into the hole on the chassis 2 Connect the drain hose into the drain vent As show in Fig 19 3 Fix Outdoor Unit 1 Place the outdoor unit on the support 2 Fix the foot hole...

Page 38: ...r for more than 3min If there are air bubbles coming out of this position there s a leakage 8 7 Vacuum Pumping and Leak Detection 1 Check after Installation installation 2 Test Operation 1 Preparation of test operation The client approves the air conditioner installation Specify the important notes for air conditioner to the client 2 Method of test operation Put through the power press ON OFF butt...

Page 39: ... and outdoor fan stop while indoor fan operates During heating operation all loads stop 1 Supply voltage is unstable 2 Supply voltage is too low and load is too high 3 Evaporator is dirty 6 Communi cation Malfunction E6 During cooling operation compressor stops while indoor fan motor operates During heating operation the complete unit stops Refer to the corresponding malfunction analysis 7 High te...

Page 40: ... F3 During cooling and drying operating compressor stops while indoor fan operates During heating operation the complete unit will stop operation Outdoor temperature sensor hasnt been connected well or is damaged Please check it by referring to the resistance table for temperature sensor 15 Outdoor condenser temperature sensor is open short circuited F4 During cooling and drying operation compress...

Page 41: ...after the supply voltage is increased to the normal range 2 If the AC input is normal measure the voltage of electrolytic capacitor C on control panel AP1 if its normal theres malfunction for the circuit please replace the control panel AP1 22 Voltage of DC bus bar is too low PL During cooling and drying operation compressor will stop while indoor fan will operate During heating operation the comp...

Page 42: ...ation compressor will stop while indoor fan will operate During heating operation the complete unit will stop Replace outdoor control panel AP1 30 Module high temperature protection P8 During cooling operation compressor will stop while indoor fan will operate During heating operation the complete unit will stop After the complete unit is de energized for 20mins check whether the thermal grease on...

Page 43: ...tecting circuit 38 Desynchro nizing of compressor H7 During cooling and drying operation compressor will stop while indoor fan will operate During heating operation the complete unit will stop operation Refer to the malfunction analysis IPM protection loss of synchronism protection and overcurrent protection of phase current for compressor 39 PFC protection HC During cooling and drying operation c...

Page 44: ...ion U5 During cooling and drying operation the compressor will stop while indoor fan will operate During heating operating the complete unit will stop operation Theres circuit malfunction on outdoor units control panel AP1 please replace the outdoor units control panel AP1 47 The four way valve is abnormal U7 If this malfunction occurs during heating operation the complete unit will stop operation...

Page 45: ...mal communica tion 54 55 Defrosting U8 56 JF OFF 3S and blink once during blinking ON 10s and OFF 0 5s Defrosting will occur in heating mode Compressor will operate while indoor fan will stop The complete unit stops operation Its the normal state 1 Power supply is abnormal 2 Detection circuit of indoor control mainboard is abnormal Malfunction of detecting plate WIFI 42 SERVICE MANUAL Innovair Eli...

Page 46: ...the wiring terminal between the temperature sensor and the controller loosened or poorly contacted Start Insert the temperature sensor tightly Yes Yes Yes Yes Yes Yes No No No No No No Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace it with a temperature sensor with the same model Make the parts upright Is there short circuit due to trip over of the parts Is t...

Page 47: ... indoor fan It s the malfunction of main board Replace a new main board that is of the same model It s the malfunction of main board Replace a new main board that is of the same model Replace a new main board that is of the same model It s the malfunction of main board Then check whether the voltage between terminal 2 and terminal 3 of the motor interface is 15VDC Connect power and restart the uni...

Page 48: ...s there jumper cap on the mainboard Is the jumper cap inserted correctly and tightly Replace the jumper cap with the same model Appearance of the jumper cap Assemble the jumper cap with the same model Insert the jumper cap tightly Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace the mainboard with the same model End Yes Yes Yes Yes Yes No No No No No SERVICE MA...

Page 49: ...load Is the indoor outdoor heat exchanger dirty or are the air inlet and outlet blocked The fan is abnormal Fan speed is too low or fan doesn t rotate Measure the current of live wire on the main board with a clamp ampere meter Is the current higher than the value of the overcurrent protection Is there blockage inside the system Filth blockage ice plug greasy blockage the cut off valve hasn t been...

Page 50: ... of IDU matches with that of ODU Communication cord is damaged Replace IDU s main board Malfunction eliminated End Connect the line according to wiring diagram Match correctly according to product specification Replace communication cord Replace ODU s main board Malfunction eliminated Malfunction eliminated Malfunction eliminated Yes Yes Yes Yes No no No Yes Yes Yes No No No No SERVICE MANUAL Inno...

Page 51: ...on eliminated The end check if the connection wire are correctly connected Replace the detecting plate with the same model Replace the mainboard with the same model Yes Yes No 5 Malfunction of detecting plate WIFI JF 48 SERVICE MANUAL Innovair Elite Mini Split ...

Page 52: ...ce outdoor mainboard Measure the voltage input with AC voltmeter see fig 30 Voltage within 180VAC 260VAC Shut down the power and wait 20 minutes or use DC voltmeter to measure the voltage on the two ends of electrolytic capacitor until the voltage is lower than 20V Check the connection of reactor and connection wire If the wiring of reactor L is normal Replace outdoor mainboard AP1 End Power suppl...

Page 53: ...ctly connect the wires of compressor according to the electric wiring diagram and then turn on the unit Check the connection between the control board and the compressor by referring to the electric wiring diagram Check whether wires of compressor UVW are connected correctly Measure the resistance value among three terminals UVW of compressor with a resistance measuring meter Whether the resistanc...

Page 54: ...erature is higher than 53 Normal protection please use it after improving the outdoor ambient temperature Unit restarts normally Unit restarts normally If the radiating of indoor and outdoor unit is good Improve the radiating environment of unit clean the heat exchanger and remove surrounding obstacles If the indoor and outdoor fan are running normally Connect normally Adjust the connection Replac...

Page 55: ...ystem is not balanced please start the unit after 3min If the compressor wire COMP UVW is well connected and connection sequence is correct Check the connection situation of outdoor mainboard AP1 and compressor COMP and the connect it according to wiring diagram If the refrigerant charging amount is too much Does the unit start up normally Charge the refrigerant according to service manual Does th...

Page 56: ... valve damaged If the refrigerant is leaked The compressor overload protection terminal is not connected well with the mainboard If the overload protector is damaged Heat exchange of unit is not good heat exchanger is dirty and unit radiating environment is bad Too much load of the system causes high temperature of compressor after working for a long time Malfunction of discharge temperature senso...

Page 57: ...nual Compressor overload protection terminal is not connected well with the mainboard reconnect them correctly Heat exchange of unit is not good heat exchanger is dirty and unit radiating environment is bad improve the radiating environment and clean the heat exchanger Too much load of the system causes high temperature of compressor after working for a long time decrease the load for operation Is...

Page 58: ...before malfunction Check built in wiring of indoor and outdoor unit If the wiring is damaged Replace the wire Check the malfunction type with communication malfunction detector Malfunction of outdoor communication circuit Replace outdoor mainboard AP1 Replace indoor mainboard AP2 Is the malfunction eliminated Is the malfunction eliminated End Check the connection wire according to the wiring diagr...

Page 59: ...d for details Malfunction of compressor Compressor can t operate Refer to point 5 of maintenance method for details 9 3 Troubleshooting for Normal Malfunction 1 Air Conditioner Can t be Started Up 2 Poor Cooling Heating for Air Conditioner 3 Horizontal Louver Can t Swing Possible Causes Discriminating Method Air conditioner Status Troubleshooting No power supply or poor connection for power plug A...

Page 60: ...pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor Can t Operate Possible causes Discriminating method air conditioner status Troubleshooting Wrong wire connection or poor connection Check the wiring status according to circuit diagram Connect wires according to wiring diagram to make sure all w...

Page 61: ...10 Exploded View and Parts List EIN10H2V32 I 9K Indoor unit The component picture is only for reference please refer to the actual product 58 SERVICE MANUAL Innovair Elite Mini Split ...

Page 62: ...porator Support 1 24212177 15 Evaporator Assy 1 011001000457 16 Cross Flow Fan 1 10352060 17 Fan Motor 1 15012136 18 Motor Press Plate 1 26112511 19 Wall Mounting Frame 1 01362026 20 Connecting pipe clamp 1 2611218801 21 Crank 1 73012005 22 Stepping Motor 1 1521240210 23 Drainage Hose 1 05230014 24 Electric Box Assy 1 100002071889 25 Lower Shield of Electric Box 1 01592139 26 Electric Box 1 201122...

Page 63: ...60 SERVICE MANUAL Innovair Elite Mini Split EIN10H2V32 O 9K Outdoor Unit The component picture is only for reference please refer to the actual product ...

Page 64: ...8 Cut off Valve 1 07130239 9 Cut off Valve 1 2 1 0710307901 10 Big Handle 0 none 11 Right Side Plate 1 0130510002P 12 4 Way Valve Assy 1 03073360 13 Capillary Sub assy 1 030006060038 14 Condenser Assy 1 011002060037 15 Stationary Barrier 1 01703179 16 Flash Vaporizer Sub assy 1 07223057 17 Tube Clip 1 02143030 18 Reactor 1 43130185 19 Coping 1 012049000006 20 Electric Box Cover Sub Assy 1 02603096...

Page 65: ...10 Exploded View and Parts List EIN13H2V32 I 12K Indoor unit The component picture is only for reference please refer to the actual product 62 SERVICE MANUAL Innovair Elite Mini Split ...

Page 66: ...porator Support 1 24212177 15 Evaporator Assy 1 0100200001401 16 Cross Flow Fan 1 10352060 17 Fan Motor 1 15012136 18 Motor Press Plate 1 26112511 19 Wall Mounting Frame 1 01362026 20 Connecting pipe clamp 1 2611218801 21 Crank 1 73012005 22 Stepping Motor 1 1521240210 23 Drainage Hose 1 05230014 24 Electric Box Assy 1 100002071899 25 Lower Shield of Electric Box 1 01592139 26 Electric Box 1 20112...

Page 67: ...64 SERVICE MANUAL Innovair Elite Mini Split EIN13H2V32 O 12K Outdoor Unit The component picture is only for reference please refer to the actual product ...

Page 68: ...Cut off Valve 1 07130239 9 Cut off Valve 1 2 1 0710307901 10 Big Handle 0 none 11 Right Side Plate 1 0130510002P 12 4 Way Valve Assy 1 03073360 13 Capillary Sub assy 1 030006000624 14 Condenser Assy 1 011002000728 15 Stationary Barrier 1 01703179 16 Flash Vaporizer Sub assy 1 03007000001 17 Tube Clip 1 02143030 18 Reactor 1 43130185 19 Coping 1 012049000006 20 Electric Box Cover Sub Assy 1 0260309...

Page 69: ...10 Exploded View and Parts List EIN18H2V32 I 18K Indoor unit The component picture is only for reference please refer to the actual product 66 SERVICE MANUAL Innovair Elite Mini Split ...

Page 70: ...00007301 15 Cold Plasma Generator 0 none 16 Wall Mounting Frame 1 01252229 17 Motor Press Plate 1 26112515 18 Fan Motor 1 15012136 19 Connecting pipe clamp 1 26112514 20 Drainage Hose 1 0523001405 21 Stepping Motor 1 1521240210 22 Crank 1 73012005 23 Guide Louver 1 20000400001301 24 Axile Bush 2 10542036 25 Electric Box 1 2011221105 26 Terminal Board 1 42011233 27 Electric Box Cover2 1 2011221001 ...

Page 71: ...68 SERVICE MANUAL Innovair Elite Mini Split EIN18H2V32 O 18K Outdoor Unit The component picture is only for reference please refer to the actual product ...

Page 72: ... 1 22245003 12 Cut off Valve 1 0713517901 13 Cut off Valve 1 07130239 14 Big Handle 1 02115005 15 Electric Expand Valve Fitting 1 07200206002232 16 Temperature Sensor 1 3900030901 17 Condenser Assy 1 011002000242 18 Reactor 1 43130024 19 Top Cover Sub Assy 1 000051000026 20 Condenser Support Plate 1 01175092 21 Motor Support Sub Assy 1 017012000017 22 Left Side Plate 1 01305043P 23 Handle 1 262330...

Page 73: ...10 Exploded View and Parts List EIN24H2V32 I 24K Indoor unit The component picture is only for reference please refer to the actual product 70 SERVICE MANUAL Innovair Elite Mini Split ...

Page 74: ...1000095 15 Cold Plasma Generator 0 none 16 Wall Mounting Frame 1 01252229 17 Motor Press Plate 1 26112515 18 Fan Motor 1 15012136 19 Connecting pipe clamp 1 26112514 20 Drainage Hose 1 0523001405 21 Stepping Motor 1 1521240210 22 Crank 1 73012005 23 Guide Louver 1 20000400001301 24 Axile Bush 2 10542036 25 Electric Box 1 2011221105 26 Terminal Board 1 42011233 27 Electric Box Cover2 1 2011221001 2...

Page 75: ...72 SERVICE MANUAL Innovair Elite Mini Split EIN24H2V32 O 24K Outdoor Unit The component picture is only for reference please refer to the actual product ...

Page 76: ...er 1 22245003 12 Cut off Valve 1 0713517901 13 Cut off Valve 1 07130239 14 Big Handle 1 02115005 15 Electric Expand Valve Fitting 1 07200206002234 16 Temperature Sensor 1 3900030901 17 Condenser Assy 1 011002000340 18 Reactor 0 none 19 Top Cover Sub Assy 1 000051000026 20 Condenser Support Plate 1 01175092 21 Motor Support Sub Assy 1 017012000015 22 Left Side Plate 1 01305043P 23 Handle 1 26233053...

Page 77: ...lters to make them break away from the groove on the front case Then remove the left and right filters one by one Left filter Groove Right filter Front case Front panel Screws Display Screw off the 2 screws that are locking the display board Note This display can be disassembled only after removing the front case refer to step 5 of disassembly 74 SERVICE MANUAL Innovair Elite Mini Split ...

Page 78: ...tor Screw off the screws that are locking the swing motor and take the motor off it out 4 Remove detecting plate and electric box cover2 Remove the screws fixing detecting plate and remove detecting plate Remove the screws fixing electric box cober2 and remove electric box2 Detecting plate 2 SERVICE MANUAL Innovair Elite Mini Split 75 ...

Page 79: ...f one grounding screw Remove the wiring terminals of motor and stepping motor Remove the electric box assy Screw off the screws that are locking each lead wire S crew Wire clip Power cord Rotate the electric box assy Twist off the screws that are locking the wire clip and loosen the power cord Remove the wiring terminal of power cord Lift up the main board and take it off 76 SERVICE MANUAL Innovai...

Page 80: ...ase assy First remove the left side of evaporator from the groove on the rear case assy Then remove the right side from the clasp on the rear case assy Groove Clasp SERVICE MANUAL Innovair Elite Mini Split 77 ...

Page 81: ...78 SERVICE MANUAL Innovair Elite Mini Split ...

Page 82: ...ssy valve cover panel grille Remove the screws connecting top cover left and right side plate as well as panel to remove the top cover Remove the screws fixing panel to remove the panel Remove the screws connecting panel grille and panel loosen the clamp to remove the panel grille Remove the screws connecting cable cross plate sub assy and right side plate to remove the cable cross plate sub assy ...

Page 83: ...r support boa rd to remove the left side plate Remove the screws fixing right side plate and valve support to remove the right side plate Remove the screw nut fixing cross fan blade remove the gasket and spring cushion to remove the cross fan blade left side plate cross fan blade right side plate Steps Procedure 80 SERVICE MANUAL ...

Page 84: ...the wiring terminal lift to remove the electric box assy Remove the four tapping screws fixing motor pull out the contact tag of motor wiring to remove the motor Remove the two tapping screws fixing motor support and chassis lift to remove the motor support Remove the screws fixing electric reactor to remove the electric reactor electric box assy electric box cove r electric reactor motor support ...

Page 85: ...crews connecting mid isolation board chassis and condenser assy to remove the mid isolation Welding cut the spot weld of four way valve assy compressor air suction discharging valve and condenser pipe outlet lift to remove the four way valve assy Note release the refrigerant before welding cutting mid isolation board four way valve assy flash vaporizer assy Steps Procedure 82 SERVICE MANUAL ...

Page 86: ...remove the compressor Remove screws connecting condenser assy and chassis to remove the chassis sub assy Remove screws connecting condenser assy and chassis to remove the condenser assy Remove the screws fixing big and small valve to remove the valves condenser assy small valve big valve Steps Procedure SERVICE MANUAL Innovair Elite Mini Split 83 ...

Page 87: ...0 55 56 55 4 13 79 80 78 8 26 34 35 33 8 1 57 58 57 2 14 81 80 6 27 36 35 6 2 59 60 59 15 82 83 82 4 28 37 38 37 4 3 61 62 60 8 16 84 85 84 2 29 39 40 39 2 4 63 62 6 17 86 87 86 30 41 42 41 5 64 65 64 4 18 88 89 87 8 31 43 44 42 8 6 66 67 66 2 19 90 89 6 32 45 44 6 7 68 69 68 20 91 92 91 4 33 46 47 46 4 8 70 71 69 8 21 93 94 93 2 34 48 49 48 2 9 72 71 6 22 95 96 95 35 50 51 50 10 73 74 73 4 23 97 ...

Page 88: ... following steps A Cut the pip Cut the required pipe with pipe cutter B Remove the burrs Remove the burrs with shaper and prevent the burrs from getting into the pipe C Put on suitable insulating pipe D Put on the union nut Remove the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe E Expand the port Expand the port with expander A is different according ...

Page 89: ...2 2 28 235 4 0 697 26 6 57 18 96 8 9 382 167 2 206 237 2 0 678 28 4 54 31 98 6 9 003 168 8 2 133 239 0 66 30 2 51 59 100 4 8 642 170 6 2 064 240 8 0 642 32 49 02 102 2 8 297 172 4 1 997 242 6 0 625 33 8 46 6 104 7 967 174 2 1 933 244 4 0 608 35 6 44 31 105 8 7 653 176 1 871 246 2 0 592 37 4 42 14 107 6 7 352 177 8 1 811 248 0 577 39 2 40 09 109 4 7 065 179 6 1 754 249 8 0 561 41 38 15 111 2 6 791 ...

Page 90: ...96 8 12 51 167 2 94 237 2 0 904 28 4 72 41 98 6 12 168 8 2 844 239 0 88 30 2 68 79 100 4 11 52 170 6 2 752 240 8 0 856 32 65 37 102 2 11 06 172 4 2 663 242 6 0 833 33 8 62 13 104 10 62 174 2 2 577 244 4 0 811 35 6 59 08 105 8 10 2 176 2 495 246 2 0 77 37 4 56 19 107 6 9 803 177 8 2 415 248 0 769 39 2 53 46 109 4 9 42 179 6 2 339 249 8 0 746 41 50 87 111 2 9 054 181 4 2 265 251 6 0 729 42 8 48 42 1...

Page 91: ... 2 10 54 217 4 3 04 8 6 323 9 78 8 47 08 149 10 18 219 2 2 955 10 4 306 2 80 6 45 07 150 8 9 827 221 2 872 12 2 289 6 82 4 43 16 152 6 9 489 222 8 2 792 14 274 84 2 41 34 154 4 9 165 224 6 2 715 15 8 259 3 86 39 61 156 2 8 854 226 4 2 64 17 6 245 6 87 8 37 96 158 8 555 228 2 2 568 19 4 232 6 89 6 36 38 159 8 8 268 230 2 498 21 2 220 5 91 4 34 88 161 6 7 991 231 8 2 431 23 209 93 2 33 45 163 4 7 72...

Page 92: ...esign and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the latest version 36 ...