8
Load type
PF 0.5~1, lagging
THDV
< 2% @ full linear load
<5% @ full non linear load
Overload
In Line mode**:
10 min 105~125%
1 min 125~150%
10 s >150%
1 s >170%
In Battery mode:
2 min 105~125%
30 s 125~150%
1 s >150%
*Derating to 90% when the output voltage is adjusted to 208VAC.
**The overload capacity should be derated in Line mode while the circumstance
temperature is larger than 35 degree.
BATTERIES
Model No.
6K
10K
Internal BAT
number and type
20×12V 7Ah
20×12V 9Ah
Current of external
BAT pack
30Amax
50Amax
3.3 Operating Environment
Operating Temperature
0
o
C to 45
o
C
Operating humidity
< 95%
Altitude
< 1000m*
Storage temperature
-15
o
C to 50
o
C
*The load capacity should be derated 1% every 100m heightened on the basis
of 1000m.