Page 37 - INSTALLATION, USE AND MAINTENANCE
AC01
compressor operating hours
Reporting compressors hour
threshold
Only display for maintenance
AP01
plant pump operating hours
Signaling system pump hours
threshold
Only display for maintenance
AP03
Pump operating hours PS
Signaling hours drain pump
threshold
Only display for maintenance
AF01
Fan operating hours
Signaling hours fan threshold
Only display for maintenance
ES01
inlet temperature probe (user)
probe failure
Check the connection and
eventually replace the probe
ES03
outlet temperature probe (user)
probe failure
Check the connection and if necessary replace
the probe
ES10
condensing pressure transducer
probe failure
Check the connection and if necessary replace
the probe
ES12
suction temperature probe
probe failure
Check the connection and if necessary replace
the probe
ES13
evaporation pressure transducer
probe failure
Check the connection and if necessary replace
the probe
ES15
auxiliary probe 1
probe failure
Check the connection and if necessary replace
the probe
AL19
Alarm RTC unloading / broken
internal fault Clock
Resetting the time and date of the electronic
control
AL21
EEV Alarm: Losh (low heat)
Low superheat expansion valve
Verify the operation of the EEV valve Verify
refrigerant charge Verify probe Verify suction
temperature low-pressure transducer
AL22
EEV Alarm: Hish (high heat)
Alto superheat expansion valve
Verify the operation of the EEV valve Verify
refrigerant charge Verify probe Verify suction
temperature low-pressure transducer
AL23
EEV Alarm: LOP
Minimum operating pressure
expansion valve
Verify the operation of the EEV valve Verify
refrigerant charge Verify low pressure
transducer
AL24
EEV Alarm:
Maximum operating pressure
expansion valve
Verify the operation of the EEV valve Check
the inlet water temperature probe Verify
Verify suction temperature low-pressure
transducer
AL26
load valve Alarm
The floats are not activated and
the unit reports the load valve
alarm
Test the input presence of water Check the
operation of the inlet valve
AL27
Maximum water level alarm
Taking Float Maximum water
level
Verify the status of the central float Check the
filling valve that does seep water
AL28
Minimum water level alarm
Taking the float minimum water
level during normal operation
Test the input presence of water Check the
operation of the inlet valve Verify that the
drain pump is in the OFF;
Summary of Contents for CEV+
Page 1: ...INSTALLATION USE AND MAINTENANCE WATER COOLER WITH CONDENSATION EVAPORATIVE CEV ...
Page 20: ...Page 20 INSTALLATION USE AND MAINTENANCE 5 1 3 WIRING UNIT MODELS 007 010 PHASE TERMINAL ...
Page 21: ...Page 21 INSTALLATION USE AND MAINTENANCE MODELS 010 015 PHASE TERMINAL ...
Page 38: ...Page 38 INSTALLATION USE AND MAINTENANCE 9 NOTES AND INFORMATION SERVICE NOTE ...