background image

© MASS ELECTRONICS Pty Ltd  2011

Models

:

ISS01 – innTOUCH Smart Sensor

ISS02 – innTOUCH Smart Sensor with Real Time Clock (RTC)

ISS03 – innTOUCH Smart Sensor with Universal Inputs (UI)

ISS04 – innTOUCH Smart Sensor with RTC and UI 

Overview

The Innotech innTOUCH Smart Sensor is a wall mounted remote 

Human Machine Interface (HMI) panel that provides a user interface 

for supported Innotech MiniMAX, VAVMax, MicroMAX, Omni C20x and 

Omni C40x controllers.   

The innTOUCH Smart Sensor has a single communications channel, 

with data transfer occurring through the power supply interface.  

Power and communication are provided through the 2-way 

Combicon connector.  

One innTOUCH Smart Sensor can interface with a supported 

controller.  All data points on the innTOUCH Smart Sensor are 

updated at the same rate as the controllers.  

DS 13.05

October 2018

innTOUCH Smart Sensor

Applications

The innTOUCH Smart Sensor extends the capabilities of the 

supported controllers.  innTOUCH provides an easy to read visual 

display of control values, and allows modifications to certain 

parameters using the intuitive LCD and push button interface. 

• 

Provides a HMI for the controller to which it is connected 

• 

Immediate access for programming parameters

Features

• 

Icon based backlit Liquid Crystal Display (LCD) 

• 

Modern, attractive enclosure design

• 

Four universal inputs (optional)

• 

One integrated thermistor input

• 

Real Time Clock (optional)

• 

Push button interface

• 

Direct interface with the MM01C, MM02C, VM01C, UM01C, OMC20, 

OMC20D, OMC40 and OMC40D controllers 

• 

Two wire single twisted pair, shielded or unshielded connection 

from controller provides both comms and power

• 

Wall mounted device

Model designations

Thermistor Input

Universal Inputs

Real Time Clock

ISS01

ISS02

ISS03

ISS04

Installation / Wiring

The innTOUCH Smart Sensor should be installed in an environment 

that does not exceed the maximum operating parameters of the 

device.  It should be mounted in a clean and dry environment free of 

vibration, and properly ventilated.

The cable providing both power and communication must be 2 core 

shielded twisted pair cable. Polarity (+/–) MUST be observed when 

connecting power.

The recommended cable length is maximum 30 metres. The cable 

should not be run in parallel with conductors carrying high current.