Instructions

Switching power supply/Battery charger providing 160W @ 27.6V

5

En

gl

is

h

Signalling

The LED indicators [

H

] signal the presence of the mains voltage on the input terminals

and the proper operating capacity of the switching power-supply unit and its batteries.
The Fault signal can be obtained through the “

STATUS

” input [

F

] via the two Open-

Collector outputs “

OC1

” and “

OC2

”.

Removal of the jumper from the Earth fault signalling connector [

I

] deactivates the

Earth fault check.
If this appliance is used with a control panel all the obligatory status and fault signals

must be provided for and made available.

Installation

IPS24160G must be installed inside a fireproof enclosure (e.g. the control panel metal

case).
Using the two mounting holes [

J

], secure the device into its housing.

Connect the mains wiring to the input terminal board [

A

].

ATTENTION!

This appliance must be earthed.

Using the plastic cable band, bunch the mains wires and fasten them close to the mains

wire entry on the Switching power-supply unit.

The cables used for the wiring of the product must have an adequate section and

comply with the IEC 60332-1-2 or IEC 60332-2-2 standards.

For an installation that meets standard requirements, it is necessary to fit a suitable

sectioning device (bipolar) and protection on the electrical-wiring upstream of the

switching power-supply unit in accordance with the laws in force (DM37/08).

The output voltage can be drawn from either terminals [

C

] (“

+V

-V

”), or from the

connector [

D

] (“

+V

-V

”).

The output connector is also has “

FAULT

” and “

RTH

” terminals which are reserved for

connection to INIM control panels.
If you are installing a ProbeTH thermal probe, connect it to connector [

E

].

Attach the thermal probe to one of the batteries in such a way as to achieve an optimal

level of thermal conductivity.

Note

The backup batteries of the equipment power supply are not included. The installer must use only

valve regulated lead-acid batteries (VRLA) for stationary use, compliant with IEC 60896-21 and

IEC 60896-22 standards.

The battery casing must have V-2 flame rating or higher.

If this appliance is used with a fire detection control panel, it is obligatory to fit it with a thermal

probe.

Maintenance

The following maintenance operations must be performed regularly:

Check that all wiring and connections are intact.

Check that the appliance is operating properly.

Check the battery efficiency.

Note

These maintenance operations must be performed by qualified persons only.

Signalling

Off

On

Blinking

fast

slow

Green LED (DL1)

Switching power-supply unit 

Off

Switching power-supply unit 

operating

Overheated

Output overload

Yellow LED (DL2)

Mains operating properly

Mains operating fault

Earth fault

/

Yellow LED (DL3)

Batteries operating properly

Battery fault

/

/

Output OC1

Operating properly

Switching power-supply unit 

fault

/

/

Output OC2

Mains operating properly

Mains operating fault

/

/

Summary of Contents for IPS24160G

Page 1: ...carica pi efficiente A Morsettiera ingresso rete B Connettore batterie BAT BAT C Morsettiera uscita V V D Connettore uscita RTH FAULT V V V V E Connettore per sonda termica NTC F Connettore per uscite...

Page 2: ...tatore in accordo con le norme vigenti DM37 08 La tensione di uscita pu essere prelevata o dai morsetti C V V o dal connettore D V V Sul connettore di uscita inoltre sono presenti i terminali FAULT e...

Page 3: ...riportato sull apparecchiatura o sulla sua confezione indica che il prodotto alla fine della propria vita utile deve essere raccolto separatamente dagli altri rifiuti L utente dovr pertanto conferire...

Page 4: ...cient battery charging A Mains input terminal board B Battery connector BAT BAT C Output terminal board V V D Output connector RTH FAULT V V V V E Thermal probe connector NTC F OC output connector STA...

Page 5: ...ower supply unit in accordance with the laws in force DM37 08 The output voltage can be drawn from either terminals C V V or from the connector D V V The output connector is also has FAULT and RTH ter...

Page 6: ...be disposed of correctly at the end of its working life and should never be disposed of together with general household waste The user therefore must take the equipment that has reached the end of it...

Page 7: ...batteries A Bornes pour entr r seau B Connexion de la batterie BAT BAT C Bornes pour sortie V V D Connecteur de sortie RTH FAULT V V V V E Connecteur sonde thermique NTC F Connecteur de sortie OC STA...

Page 8: ...rtie peut tre pris la fois sur les bornes C V V ou du connecteur D V V Le connecteur de sortie poss de aussi un raccordement FAULT et RTH ceux ci sont uniquement pour les panneaux d alarme incendie IN...

Page 9: ...de la poubelle barr e sur l appareil ou sur son emballage indique que le produit la fin de sa dur e de vie utile doit tre collect s par ment des autres d chets L utilisateur devra donc confier l appa...

Page 10: ...er a eficientemente A Tarjeta de terminales de entrada de red B Conector de la bater a BAT BAT C Bornes de salida V V D Conector salida RTH FAULT V V V V E Conector para sonda t rmica NTC F Conector p...

Page 11: ...te DM37 08 El voltaje de salida se puede extraer de cualquiera de los terminales C V V o desde el conector D V V El conector de salida tambi n dispone de terminales FAULT y RTH que se reservan para la...

Page 12: ...el embalaje indica que el producto al final de su vida til debe ser desechado por separado de los dem s residuos El usuario deber por tanto llevar el equipo llegado al final de su vida a los centros...

Reviews: