Note

The operating modes of the “A2S” and “BR” are not certified.

ED300

Optical-heat detector with heat sensitive element and optical smoke chamber. The combination of
values provides (in accordance with the operating mode selected via the control panel) high immunity to
nuisance alarms and an exceptionally sensitive detector which is capable of swift response to fires cha-
racterized by low smoke emission.

Operating mode

Mode

The operating modes, programmable via the control panel are:

“PLUS”

(pre-set); the detector signals alarm status when smoke in the protected environment

exceeds the programmed threshold (programmed as described for the ED100 model) or when the

temperature within the protected environment exceeds the programmed threshold (programmed as

described for the ED200 model). Furthermore, in the event of a rise in temperature within the pro-

tected environment, the sensitivity of the smoke chamber will be increased. This operating mode, cha-

racterized by high sensitivity, allows detection of fires which produce a large amount of flames but

low smoke emission (e.g. combustion of alcohol or similar highly-inflammable products).

“OR”

; the detector signals alarm status when smoke in the protected environment exceeds the pro-

grammed threshold (programmed as described for the ED100 model) or when the temperature

within the protected environment exceeds the programmed threshold (programmed as described for

the ED200 model). This operating mode, characterized by medium-high sensitivity, allows detection

of fires which generate a substantial amount of smoke but low heat emission (slow burning fires) as

well as fires which generate high temperatures and low smoke emission (chemical products).

“AND”;

the detector signals alarm status when the smoke and temperature in the protected envi-

ronment exceed the programmed thresholds simultaneously (programmed as described for

theED100 model and ED200 model respectively). This operating mode, characterized by a low sen-

sitivity, lowers the false alarm rate and is useful in applications where either the smoke or heat

values in the protected environment may increase without the risk of fire.

Note

Given the limited response, consider the conditions in the protected environment carefully
before selecting this operating mode.

“SMOKE”

; the detector assumes the characteristics of the ED100 model

“HEAT”

; the detector assumes the characteristics of the ED200 model

LED

The three-colour LED (360° viewing) indicates the detector status.

Green blinking at 15-second intervals; the detector is in standby status (i.e. operating properly).

Green On solid; the LED has been activated manually from the control panel. This operation allows

easy identification of the detector.

Yellow On solid; the detector is in fault status or has detected a short-circuit in the succeeding wiring

section (short-circuit isolator open). Further details regarding the fault can be obtained through the

control panel.

Red On solid; the detector is in alarm status. Further details regarding the alarm can be obtained

through the control pane

“R” terminal

The detectors have an output (terminal “R”), for the connection of an alarm repeater LED. This LED will
activate in accordance with programming carried out via control panel.
The detector is also capable of discerning whether its repeater LED has been connected. This function
provides indications (on the control panel) regarding the detectors with connected LEDs, and also fault
signals in the event of disconnection.

Description of the parts

A

Detector

B

Detector notch

C

Thermal probe

D

Red/yellow/green LED

E

Optical chamber

F

Technical specifications/serial-number sticker

G

Removable serial-number stickers

H

Cover removing hooks

I

Optical chambre removing hooks

J

Base

K

Base notch 1

L

Base notch 2

M

“+” terminal

N

“-” terminal

O

“R” terminal

P

Short-circuit reed

Q

Screw locations

Installation

Note

For information regarding device placement, coverage and method of installation, refer to the
established standard regulations and codes relating to Automatic fire-detection systems.
Enea series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered light principle, light transmission or ionization (ED100 and ED300 models only) and
EN54-5: Heat detectors – point detectors (forED200 and ED300 models only), EN54-17 short-
circuit isolators.

The detectors are supplied with protective covers which help to protect them against minor damage and
dust contamination which may occur during the installation phase. The covers should not be removed
until the system is ready to start up.
The detectors can be used with one of the following compatible mounting bases:

EB0010

; standard base

An example of installation using standard bases is shown opposite.

EB0020

; relay base

Appropriate when the detector is to be connected to an intrusion control panel or to a control panel
using 4 wires.

Note

The two removable serial-number stickers should be taken off and one should be attached to
the mounting base and the other to the installation layout.

Once the base is located properly in its placement, place the detector unit onto the base and, with mini-
mum force, turn it clockwise until the detector notch

[B]

aligns with the base notch

[K]

(in order to attach

the detector to the base); turn it still further until notch

[B]

aligns with the second base notch

[L]

(in order

to allow the base to engage with the detector contacts).
When installation of all the loop devices is complete, proceed with the addressing phase. Refer to the
respective section in the control panel installation and programming manual.

Using the EDRV2000 driver

The EDRV2000 driver allows you to change the operating parameters of the detectors, check the con-
tamination level of the smoke chambers and also obtain accurate diagnostic data. It can operate through
the USB port of a computer furnished with the relative software programme, or can function auto-
nomously by way of the battery housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of
the 5 minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information
regarding the onset of the fire by simply connecting the EDRV2000 driver to the detection line.
For further information and details regarding use of the EDRV2000 driver, refer to the respective hand-
book.

Testing and maintenance

After installation and during periodic maintenance inspections, you must carry out the following ope-
rations on each detector:

Optical smoke detector test

; smoke detectors should be tested immediately after installation and perio-

dically during maintenance inspections in accordance with the established standard regulations and
codes in force. To test smoke detectors, use an approved test aerosol strictly in accordance with the
accompanying instructions.
Ensure that the smoke inlet ports to the smoke detection chamber are not blocked. Check the con-
tamination level of the smoke detection chamber via the control panel. If the contamination level is high
(above 50%), detach the detector from its mounting base, open the device and, using a small, soft-bristle
brush or hand-held vacuum cleaner remove all dust particles from inside and around the smoke detec-
tion chamber.
Free the protection mesh from all contaminants.

Heat detector test

; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector,

then work through the steps described in the device instruction sheet. During each periodic maintenance
inspection, ensure that the heat element is intact and that is not obstructed by dust or paint. If it is, using a
small, soft-bristle brush or hand-held vacuum cleaner remove all contaminants.

Technical specifications

Model

ED100

ED200

ED300

Power supply

from19 to 30 V

Current draw in standby

200µA

Current draw in alarm

10mA @27,6V

Current draw by the “R” output
(internally limited)

Max 14mA

Dimensions (DxH, standard base
included)

110 x 46 mm

110 x 54 mm

Weight

160g, standard base included

91g, without base

Environmental conditions

Temperature

from -5 to +40 °C

Relative humidity

95 % without condensation

CE mark

0051

INIM Electronics s.r.l.

Via Dei Lavoratori 10 - Fraz. Centobuchi

63076 Monteprandone (AP) - Italy

10

0051-CPR-1878

EN 54-7:2000 + A1:2002 + A2:2006

EN 54-17:2005

ED100

Intelligent analogue addressable optical smoke detec-

tor with short circuit isolator for fire detection and fire

alarm systems installed in buildings

Essential characteristics

Performance

Nominal activation con-

dition/sensitivity, response delay

(response time) and performance

under fire conditions

PASS

Operational reliability

PASS

Tolerance to supply voltage

PASS

Durability of

operational

reliability:

Temperature resistance

PASS

Vibration resistance

PASS

Humidity resistance

PASS

Corrosion resistance

PASS

Electrical stability

PASS

0051

INIM Electronics s.r.l.

Via Dei Lavoratori 10 - Fraz. Centobuchi

63076 Monteprandone (AP) - Italy

10

0051-CPR-1877

EN 54-5:2000 + A1:2002

EN 54-17:2005

ED200

Intelligent analogue addressable class P heat detec-

tor with short circuit isolator for fire detection and fire

alarm systems installed in buildings

Essential characteristics

Performance

Nominal activation con-

dition/sensitivity, response delay

(response time) and performance

under fire conditions

PASS

Operational reliability

PASS

Tolerance to supply voltage

PASS

Durability of

operational

reliability:

Temperature resistance

PASS

Vibration resistance

PASS

Humidity resistance

PASS

Corrosion resistance

PASS

Electrical stability

PASS

Detector class (EN54-5): A1R or B

0051

INIM Electronics s.r.l.

Via Dei Lavoratori 10 - Fraz. Centobuchi

63076 Monteprandone (AP) - Italy

10

0051-CPR-1876

EN 54-5:2000 + A1:2002

EN 54-7:2000 + A1:2002 + A2:2006

EN 54-17:2005

ED300

Intelligent analogue addressable multicriteria optical

smoke and class P heat detector with short circuit iso-

lator for fire detection and fire alarm systems installed

in buildings

Essential characteristics

Performance

Nominal activation con-

dition/sensitivity, response delay

(response time) and performance

under fire conditions

PASS

Operational reliability

PASS

Tolerance to supply voltage

PASS

Durability of

operational

reliability:

Temperature resistance

PASS

Vibration resistance

PASS

Humidity resistance

PASS

Corrosion resistance

PASS

Electrical stability

PASS

Detector class (EN54-5): A1R or B

Documents for the users

Declarationsof Performance, Declarationsof Conformity
and Certificatesconcerning to Inim ElectronicsS.r.l. pro-
ductsmaybe downloaded free of charge from the web
addresswww.inim.biz, getting accessto Extended
Accessand then selecting "Certifications"or requested to
the [email protected] requested byordi-
narymailto the addressshown in thismanual.

Manualsmaybe downloaded free of charge from the
web addresswww.inim.biz, getting accessto Extended
Accessand then selecting "Manuals".

Warnings and limitations

Enea series detectors must be used exclusively with

fully compliant, compatible controlpanels. Detectors

may not provide timely warning of fire if coverage is

limited by large obstructions (pillars, large machinery,

etc.). When installing or working on a fire detection

system, always refer to and comply with the esta-

blished standard regulations and codes. Appro-

priate fire-risk assessment should be undertaken to

determine the type of detectors required and their

placements.

Manufacturer's details

Manufacturer:

Inim ElectronicsS.r.l.

Production plant:

Centobuchi, via DeiLavoratori10

63076 Monteprandone (AP), Italy

Tel:

+39 0735 705007

Fax:

+39 0735 734912

e-mail:

[email protected]

Web:

www.inim.biz

The personsauthorized bythe manufacturer to repair
or replace the partsof thissystem, hold authorization to
workon Inim Electronicsbrand devicesonly.

About this manual

Manual code:

DCMIIN1PED

Revision:

250

Copyright:

the information contained in thisdocument

isthe sole propertyof Inim ElectronicsS.r.l. No part may
be copied without written authorization from Inim Elec-
tronicsS.r.l.. Allrightsreserved.

WEEE

lnformative notice regarding the disposal of electrical and electronic equipment (applicable in
countries with differentiated waste collection systems)

The crossed-out bin symbolon the equipment or on itspackaging indicatesthat the product must be disposed
of correctlyat the end of itsworking life and should never be disposed of together with generalhousehold
waste. The user, therefore, must take the equipment that hasreached the end of itsworking life to the appro-

priate civicamenitiessite designated to the differentiated collection of electricaland electronicwaste. Asan alternative to

Manuale d'istruzioni/ Instruction manual/ Manualde instrucciones/ Notice d’instructions

Inim ElectronicsS.r.l. © 2020

DCMIIN1PED-250-20200618

Summary of Contents for ED100

Page 1: ...con una maggiore immunità ai falsi allarmi Funzionamento Modalità Le modalità di funzionamento impostabili da centrale di controllo sono PLUS pre impostata il rivelatore segnala una condizione di allarme nel caso in cui venga supe rato il valore di soglia di fumo impostabile come descritto per il modello ED100 o nel caso in cui venga superato il valore di temperatura impostabile come descritto per...

Page 2: ...voltaggio di ali mentazione PASS Durabilità dell affidabilità di fun zionamento Resistenza termica PASS Resistenza alle vibra zioni PASS Resistenza all umidità PASS Resistenza alla cor rosione PASS Stabilità elettrica PASS Classe del rivelatore EN54 5 A1R o B 0051 INIM Electronics s r l Via Dei Lavoratori 10 Fraz Centobuchi 63076 Monteprandone AP Italy 10 0051 CPR 1876 EN 54 5 2000 A1 2002 EN 54 7...

Page 3: ...ction line For further information and details regarding use of the EDRV2000 driver refer to the respective hand book Testing and maintenance After installation and during periodic maintenance inspections you must carry out the following ope rations on each detector Optical smoke detector test smoke detectors should be tested immediately after installation and perio dically during maintenance insp...

Page 4: ... están dotados de una salida el terminal R para la conexión de un LED de repetición de alarma Este LED es activado de acuerdo con la programación efectuado en la central El detector es capaz de detectar si un led remoto efectivamente ha sido conectada esta función permite obtener la indicación en la central de cuáles detectores poseen efectivamente el led conectado a una indi cación de fallo en el...

Page 5: ...me dans le cas où la température dépasse les 72 C ou dans le cas où si celle ci augmente trop rapidement Note Les modalités de fonctionnement A2S et BR ne sont pas certifiées ED300 Capteur optique thermique doté de chambre d échantillonnage optique de fumée de et de l élément sen sible à la température La combinaison des valeurs permet selon les modalités de fonctionnement sélec tionnées depuis la...

Page 6: ... CPR 1876 EN 54 5 2000 A1 2002 EN 54 7 2000 A1 2002 A2 2006 EN 54 17 2005 ED300 Détecteur combiné optique de fumée et de tem pérature de la classe P analogique adressable avec un isolateur de court circuit pour systèmes de détec tion et signalisation de incendie pour les bâtiments Caractéristiques essentielles Performance Conditions nominales de acti vation sensibilité retard de réponse temps de r...

Reviews: