88
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
Screen 9
This screen displays a histogram of the power output from each of the inverters configured in the master-slave system.
9.5. Reasons for shutdown
This menu shows the last five inverter shutdowns, with reasons and corresponding date and time.
10:22
14/04/11
REASONS FOR SHUTDOWN
13:43 (08/01) -> MANUAL SHUTDOWN
17:22 (08/01) -> POT CURRENT
19:35 (07/01) -> POT CURRENT
12:21 (05/01) -> FRED
15:51 (04/01) -> POT CURRENT
Meaning of reasons for shutdown:
MP VIN
High input voltage from the panels.
MP FRED
Incorrect grid frequency.
MP VRED
Incorrect grid voltage.
MP VARISTORES
Varistor fault.
MP AISL.DC
DC insulation fault.
MP INT AC RMS
Continuous overvoltage on AC output.
MP TEMPERATURA
Overtemperature in the power electronics.
MP CONFIG
Shutdown for configuration change.
MP PARO MANUAL
Manual shutdown.
MP B VPV MED
Low input voltage from the panels.
MP HW_DESCX2
Internal fault.
MP IAC INST
Voltage surge on AC output.
MP CR.FIRMWARE
Shutdown due to firmware change.
MP LEC ADC
AD converter (internal) reading fault.
MP CONSUMO POT
Insufficient solar radiation. Does not trigger alarm.
MP FUSIBLE DC
Input fuse fault.
MP TEMP AUX
Redundant temperature sensor fault.
MP PROTECCION AC
AC Protection.
MP MAGNETO AC
Thermomagnetic circuit breaker error.
MP CONTACTOR
Contactor failed to close.
MP RESET_WD
Stopped for Watch Dog reset (internal).
MP LAT ADC
Converter (internal) fault.
MP ERROR FATAL
Fatal error in the inverter.
MP FALLO RAMA1
Power electronics fault.
MP FALLO RAMA2
Power electronics fault.
MP FALLO RAMA3
Power electronics fault.
MP PI CORR SAT
PI current saturation (internal).
MP LATENCIA SPI
Communication fault with redundant system.
MP REDUNDANTE
The redundant system has caused a shutdown.
MP PROTECCIÓN PIB
The PIB has caused a shutdown.