Keep the following distances free of obstacles.
50 cm
30 cm
30 cm
30 cm
5.2. Environmental conditions
Environmental operating conditions indicated in section
must be taken into account
when choosing the location of the unit.
The surrounding atmosphere must be clean and at temperatures above 40 ºC, the relative humidity must be
between 4% and 50%. Higher percentages of relative humidity up to 95% are tolerated at temperatures below
30 ºC.
Take into account that moderate condensation may occasionally occur as a consequence of temperature variations.
For this reason, apart from the unit's own protection, it is necessary to monitor these units once they have been
started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.
5.3. Supporting Surface and Fastening
These inverters must be installed in accordance with the specifications in the following figure. The minimum
positive or negative inclination permitted will be
85
º in relation to horizontal.
90
º
<8
5º
<8
5º
Reserve a solid wall to which to attach the unit. It must be possible to drill the wall and fit suitable wall anchors
and self-tapping screws to support the unit’s weight.
5.4. Protection of the connection to the electricity grid
It is necessary to install protection elements in the connection between the inverter and the electricity grid.
Thermomagnetic circuit breaker
A thermomagnetic circuit breaker and/or fuse must be installed on the connection between the inverter and the
electricity grid.
62
Preparation for installing the unit
Ingeteam
ABE2011IQM01_B - Installation and Operation Manual
Summary of Contents for INGECON SUN 1Play 2.5TL
Page 48: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 90: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 132: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 258: ...Anmerkungen Notes Notas Remarques Note Notas...
Page 260: ...Ingeteam Power Technology S A www ingeteam com ABE2011IQM01_B 04 2015...