Ingersoll-Rand TRANE NEXIA TZEMT500BB32MAA Installation And User Instructions Manual Download Page 22

22

The Installer Settings screen is a hidden screen designed for use by qualified installers and service technicians. Do not change any 
settings in these screens unless you are a qualified installer or service technician.

Installer Settings

Display Lock 

N

System Settings

Max Heat SP 

90

Min Cool SP 

60

Done

+

-

Changing these settings will affect the operation of the heating/cooling system. To view and edit these settings:
1.  Press the 

MENU

 button.

2.  Press and hold the two middle buttons simultaneously until the 

Installer Settings

 menu is displayed.

3.  Scroll to the setting you want to change. Press the plus (+) or minus (-) button to adjust the setting.
4.  Press the 

Done

 button when you are finished. 

Setting

Range

Default

Description

Display Lock

Y or N

N

Locks or unlocks the thermostat buttons. When the buttons are 
locked, the main menu can still be accessed, but no menu options 
may be selected. The Installer Settings hidden button operation is 
always operational, allowing Display Lock to be turned off. 

System Settings

See next page

Max Heat SP

55F to 90F 
(12C-32C)

90F (32C)

Sets the maximum heating setpoint value. Will not ramp or accept 
setpoints higher than this maximum.

Min Cool SP

 60F to 99F 
(15C-37C)

60F (15C)

Sets the minimum cooling setpoint value. Will not ramp or accept 
setpoints lower than this minimum.

Minimum Run 
Time (MRT)

1- 9 Minutes

3

Sets the minimum run time before a heating/cooling cycle can 
turn off to prevent rapid cycling. Thermostat screen will display 

Cool ON

 or 

Heat ON

 while the minimum run time is being 

enforced.

Minimum Off Time 
(MOT)

5-9 Minutes  

5

Sets the minimum off time before another heating/cooling 
cycle can begin to provide compressor short cycle protection. 
Thermostat screen will display 

WAIT

 when minimum off time is 

being enforced.

T-Sense

1-6

2

Sample rate of temperature sensor 
Low Sample Rate = Less sensitive (slower response) 
High Sample Rate = More sensitive (faster response)

Fan Cycler 

1

Fan ON Time

0-120 minutes

0 (= OFF)

The fan cycler function cycles the HVAC system fan for an ON 
period followed by an OFF period continuously.  Used to provide 
minimum air ventilation requirements.  While the Fan ON time is 
set to a value greater than 0, an additional Cycler FAN mode is 
present when pressing FAN button.

Fan Cycler 

1

Fan OFF Time

10-120 minutes

10

Remote Sensors

IN or OUT

IN

Used to enable remote temperature sensing, averaging, or for 
outdoor temperature setting for display and/or dual fuel restricted 
mode.

Dehumidification 
Options

See Dehumid Option table

Restore Defaults

n/a

n/a

Sets all of the thermostat settings back to the factory defaults.

 

1  

NOTE: CONTINUOUS fan mode during COOLING operation may not be appropriate in humid climates. If the indoor air exceeds 60% 

relative humidity or simply feels uncomfortably humid, it is recommended that the fan only be used in the AUTO mode.

Installer Settings

Summary of Contents for TRANE NEXIA TZEMT500BB32MAA

Page 1: ...8 7707 Contents Physical Installation and Wiring 2 Field Wiring Diagrams 4 Enhanced Dehumidification Mode 7 Optional Remote Temperature Sensors Installation 8 System Settings at Thermostat 10 Perform...

Page 2: ...ions regarding recycling and proper disposal of the old control A listing of heating ventilating and air conditioning wholesalers that participate in the Thermostat Recycling Corporation s recycling p...

Page 3: ...information from step 6 carefully to ensure the control is wired properly After wires are secure bare wires MUST NOT touch each other See the Field Connection Wiring Diagrams on the following pages f...

Page 4: ...eturn R 24VAC Common B C Compressor Stage 2 Y2 BK Heat Stage 2 W2 RED GREEN WHITE YELLOW BLUE BROWN Remote Temperature Sensor Connections and Operation Indoor sensor connected to RS1 Replaces internal...

Page 5: ...24VAC Return R 24VAC Common B C Compressor Stage 2 Y2 BK RED GREEN WHITE YELLOW BLUE BROWN Remote Temperature Sensor Connections and Operation Indoor sensor connected to RS1 Replaces internal sensor...

Page 6: ...1 24VAC Return R 24VAC Common B C Compressor Stage 2 Y2 BK RED GREEN WHITE YELLOW BLUE BROWN Remote Temperature Sensor Connections and Operation Indoor sensor connected to RS1 Replaces internal sensor...

Page 7: ...ot connected Indoor sensor connected to RS2 Averages temperature with internal sensor RS1 not connected Indoor sensors connected to RS1 and RS2 Averages RS1 and RS2 sensor temperatures Internal sensor...

Page 8: ...to indoor location IN Default selection in the thermostat installation set up menu and a sensor is attached to the RS2 sensor terminals of the thermostat the RS2 temperature is averaged with the ther...

Page 9: ...ling system back on The thermostat display should turn on and begin displaying information If the thermostat display does not come on go back through the installation steps and look for problems 10 At...

Page 10: ...then press the Select button c Scroll up or down to Set Clock it is the first option then press the Select button Done Select User Settings Set Clock Filter Service Maint Service Screen Timeout Selec...

Page 11: ...ess the button to change the setting to Y for Yes f Press the Done button 4 times and go to Perform System Checkout Heat Pump Mechanical Settings a Scroll to system Type b Press the button to change t...

Page 12: ...to access the Menu Selection screen b From the Menu Selection screen press and hold the two inner buttons down for 4 seconds to reach the Installer Settings menu c From the Installer Settings screen...

Page 13: ...s the Select button e Press the Yes button to enroll the thermostat f Observe the lights on the bridge The orange light will blink while enrollment is taking place Enrollment is complete when the oran...

Page 14: ...while exclusion is taking place Exclusion is complete when the orange light becomes solid Z Wave controllers from various manufacturers may support the Z Wave Thermostat General V2 Device class used...

Page 15: ...ng setpoint In AUTO mode the buttons change the last call s heating or cooling setpoint The setpoints will push each other if they are adjusted to within the minimum heat cool separation setting This...

Page 16: ...de Sensor Calibration Internal Remote 1 Remote 2 Outside Backlite Display Backlite Timeout ON Level OFF Level Contrast Usage Graph Heat Cool ESM Setpoints ESM Heat ESM Cool Zwave Install Thermostat In...

Page 17: ...eatpump DF DF Type Nonrestrict Restrict C O Type w Heat w Cool 2nd Stage Heat Aux Heat HP 2nd Stage Cool Balance Point if DF Restrict Sched Enable Recovery Enable H C Delta H Delta Stg1 ON H Delta Stg...

Page 18: ...e and press the Select button 4 Make choice from the following options A C A To View Reset Filter Runtime 5 The Filter Runtime is displayed in hours 6 To reset the Filter Runtime counter press the Res...

Page 19: ...d Screen Timeout This is the time before any screen reverts to the Minimized Screen temperature display only after you stop pushing buttons Minimized Screen feature is disabled by setting this time to...

Page 20: ...rature is 77 and the number of degrees of offset being applied is 1 Change the Sensor Calibration 1 Press the MENU button 2 Scroll to User Settings and press the Select button 3 Scroll to Sensor Calib...

Page 21: ...cklight 5 Scroll to Backlite Timeout 6 Press the plus or minus buttons to change the number of seconds The backlight time out can be set between 0 and 120 seconds Thirty 30 is the default setting When...

Page 22: ...me MRT 1 9 Minutes 3 Sets the minimum run time before a heating cooling cycle can turn off to prevent rapid cycling Thermostat screen will display Cool ON or Heat ON while the minimum run time is bein...

Page 23: ...time When the thermostat is in Recovery mode the display will show Recov Recovery works for all scheduled periods 1 4 and in HEAT COOL or AUTO modes While in Recovery the Aux Heat stage will not engag...

Page 24: ...tricted Non restricted mode will follow thermostat demand for each heating stage Restricted mode will lock out the compressor at a selectable outdoor temperature Default balance point is 40 F C O Type...

Page 25: ...3 Scroll to Systems Settings and press the Select button 4 Scroll to Sched Enable and press the plus button to enable scheduling or the minus button to disable scheduling When scheduling is enabled in...

Page 26: ...hange to Copy 6 Press the Copy button 7 For each day to which you want to copy the day schedule change the N no to Y yes Use the left or right arrow buttons to scroll to the day and the use the Yes or...

Page 27: ...t control if it is damaged while in your possession including but not limited to 1 damage caused by unreasonable use of the low voltage room comfort control 2 damage from failure to properly maintain...

Page 28: ...icular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to corr...

Reviews: