Ingersoll-Rand Trane Intellipak General Service Bulletin Download Page 1

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment 

 

by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and 
on the tags, stickers, and labels that are attached to the equipment.

Control Algorithm Tuning Parameters

Intellipak™ Rooftop Units

General Service Bulletin

ATTENTION:

 

Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these 

carefully:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or 
serious injury.

CAUTION

s

Indicates a potentially hazardous situation which, if not avoided, could result in minor or 
moderate injury. It could also be used to alert against unsafe practices.

NOTICE: 

Indicates a situation that could result in equipment or property-damage only accidents

RT-SVB98B-EN

March 2016

Summary of Contents for Trane Intellipak

Page 1: ...and labels that are attached to the equipment Control Algorithm Tuning Parameters Intellipak Rooftop Units General Service Bulletin ATTENTION Warnings Cautions and Notices appear at appropriate sectio...

Page 2: ...plays showing the correct factory preset values Any particular unit will contain only a portion of this list of displays WARNING Personal Protective Equipment PPE Required Failure to wear proper PPE f...

Page 3: ...een shown only for units with Dehumidification Installed SA Reheat Control Gains Proportional XX X F Reset Time XXX Sec Range 0 2 20 0 Range 5 600 Default 3 3 Default 50 Note XXX Sec field becomes DIS...

Page 4: ...Default 1800 Note XXX Sec field becomes DISABLE if 3600 seconds Screen shown only for CV units Zone Control Occupied Cooling Gains Proport Bias XXX Max Cy Rate X X CPH Range 0 400 Range 1 5 6 0 Defaul...

Page 5: ...for the number of configured heat stages If heat stages are not configured it will place 30 F in the field as a default until heat stages are configured This will happen once at power up if needed an...

Page 6: ...pply Air Temp High Limit XX X F Range 80 140 Default 120 Screen shown only for VAV units Supply Air Pressure Gain Proportional XX X IWC Reset Time XXX Sec Range 0 2 20 0 Range 1 60 Default 3 3 Default...

Page 7: ...0 Default 17 s Default 80 Note XXXXs field becomes DISABLE and Prop and Feedforward items are not shown if Reset Time 1000 s on Ipak 1 units only Screen shown only for RT or RT AH units with DX Coolin...

Page 8: ...hen Temp Above Setpoint Disable is displayed when the value is incremented above 255 A selection of Disable disables wheel shutoff changes to screen below and allows continuous wheel operation when co...

Page 9: ...et Time w VSC wo VSC 100 Sec 50 Sec ___________ Setup CV Air Economizer Control Gains Proportional 10 0 F ___________ Setup Reset Time DISABLE ___________ Setup Rate Time 0 Sec ___________ Setup Bias...

Page 10: ...rease industrial productivity and efficiency We are a 13 billion global business committed to a world of sustainable progress and enduring results For more information visit www ingersollrand com Inge...