Ingersoll-Rand R30-37ie Operator'S Manual Download Page 6

 

 

4 - 30 

2. INSTALLATION 

2.1 ACCEPTANCE, UNPACKING AND HANDLING 

Upon receiving your Ingersoll Rand air dryer, please inspect the unit closely. If rough handling is detected, please note it 
on  your  delivery  receipt,  especially  if  the  dryer  will  not  be  uncrated  immediately.  Obtaining  the  delivery  person's  signed 
agreement to any noted damages will facilitate any insurance claims by the customer. 

It is mandatory to keep the dryer  always  in  vertical position, as  indicated by the  symbols present on the packaging. For 
handling, use devices having sufficient capacity for the weight of the machine. 

Remove the packaging after having positioned the dryer in the installation site. Dispose the various packaging materials in 
compliance with the relevant rules locally in force. 

If not in use, the dryer can be stored in its packaging in a dust free and protected site between 32°F (0°C) and 120 °F (50 
°C), and a specific humidity not exceeding 90 %. Should the stocking time exceed 12 months, please contact your local 
Ingersoll Rand authorized distributor. 

Under no circumstances should any person attempt to lift heavy objects without proper lifting equipment (i.e., crane, hoist, 
slings  or  fork  truck).  Lifting  any  unit  without  proper  lifting  equipment,  may  cause  serious  injury.  Use  fork  lift  channels 
where provided. 

 

 

 

 

 

 

The dryer is supplied packed into a suitable cardboard box to be always handled in an upright position using a 
means with a suitable lifting power (see technical data). 

IMPORTANT : to lift or to move the unit follow the procedures shown here below, pic. 2.1 & 2.2. The dryer 
must be lifted and moved slightly. 

After cutting straps (always wear safety gloves and eye protection and cut either with scissors or cutting nippers), 
remove the carton from the top. 
Lift the dryer as shown on Pic. 2.1 – 2.2 and remove the wooden protection from the feet, then move the dryer to 
the choosen position.

 

 

 

 

 

 

Pic. 2.1 

Pic. 2.2 

 

 

2.2 INSTALLATION SITE 

 

 

While  preparing  a  proper  site  for  the  installation  of  the  dryer,  please  take  into  account  the  following 
requirements 

 

The machine must be protected from atmospheric agents and not directly exposed to sun light. 

 

A seating base flat and capable to hold the weight of the machine. 

 

Ambient temperature complying with the nominal data of the dryer. 

 

The  dryer  should  be  located  in  a  clean  area,  without  forced  air  draft  that  can  affect  the  fan  control 
system. 

 

Make  sure  to  leave  sufficient  clearance  (20  inches,  500  mm)  around  the  dryer  in  order  to  allow  an 

adequate cooling of the machine and for maintenance and/or control operations. 

 

The incoming air must be free from smoke or flammable vapours which could lead to explosion or fire risks. 

 

Cod. 710.0048.24.01 Rev0H – 02.2015

Summary of Contents for R30-37ie

Page 1: ... EN DIRECT EXPANSION COMPRESSED AIR DRYERS Operators Manual R30 37ie R37 45 kW R55 75 kW Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 2: ...1 28 ...

Page 3: ...Installation site 4 2 3 Installation 5 3 START UP 3 1 Before start up 5 3 2 Start up 5 4 MAINTENANCE TROUBLESHOOTING AND DISMANTLING 4 1 Maintenance 6 4 2 Troubleshooting 6 4 3 Dismantling 7 ATTACHMENTS TO THIS MANUAL A Refrigerant circuit 9 B Electric circuit diagram 10 C Technical data sheet 26 D Dryer dimensions 27 Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 4: ...lified personnel must be trained and certified in accordance with local laws and regulations WARRANTY The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen months from the date of shipment from the factory whichever shall fir...

Page 5: ...tection degree IP 42 Improper grounding can result in electrical shock and can cause severe injury or death This product must be connected to a grounded metallic permanent wiring system or an equipment grounding terminal or lead on the product All grounding must be performed by a qualified electrician and comply with national and local electrical codes In the event of an electrical short circuit g...

Page 6: ...e serious injury Use fork lift channels where provided The dryer is supplied packed into a suitable cardboard box to be always handled in an upright position using a means with a suitable lifting power see technical data IMPORTANT to lift or to move the unit follow the procedures shown here below pic 2 1 2 2 The dryer must be lifted and moved slightly After cutting straps always wear safety gloves...

Page 7: ...ch a way that all the control instruments of the machine will result easily visible A suitably sized prefilter must be installed before the dryer Failure to install and maintain a proper prefilter will void the dryer warranty The rating for this filter must be at least 10 micron 3 START UP 3 1 BEFORE START UP Before starting the machine make sure that all operating parameters correspond to the nom...

Page 8: ...ons must be performed by qualified personnel For maintaining the refrigerating circuit of the machine contact a refrigeration engineer TROUBLE POSSIBLE CAUSE REMEDY WATER IN THE SYSTEM No power in the line Restore the power in the line Problems with cabling Check cabling if the trouble persists replace it Compressed air inlet outlet inverted Check if the compressed air inlet outlet is connected pr...

Page 9: ...istributor LOW PRESSURE IN THE LINE Ice formation in the evaporator Contact our Service Centre to check the gas charge Clog Check if the compressed air inlet outlet is connected properly Check if the connecting tubing is clogged in case proceed accordingly Check if any valves are closed Check the condition of any filter Air flows continuously through the condensate drainage Drainage jammed clean o...

Page 10: ...nt EVA Evaporator F1 F2 Fuses FD Air filter 10 micron FF Filter dryer FH Air filter 0 01 micron FP Air filter 1 micron FQ Air filter 5 micron FR Drain screen FV Fan motor fuse G Grid IM Moisture indicator KM5 Contactor switch KM6 Fan contactor switch PCP Thermal protection PR Air air heat exchanger PSC Air air heat exchanger D__IT RBF Tap with strainer RR Rotalock cock RT1 Temperature probes SC He...

Page 11: ...NT CIRCUIT Cod 713 0058 01 00 Rev 01 Models R30 37ie R37 45kW R55 75kW Condensate drain Refrigerant line Air inlet Compressed air line Air outlet Condensate drain line Equalization line Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 12: ...10 30 B WIRING DIAGRAM Cod 714 0211 01 00 Rev 0A Models R30 37ie R37 45 kW 400 3 50 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 13: ...11 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 14: ...12 30 Cod 714 0199 01 00 Rev 1C Models R30 37ie R37 45 kW 460 3 60 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 15: ...13 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 16: ...14 30 Cod 714 0199 02 00 Rev 00 Model R37 45 kW 230 3 60 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 17: ...15 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 18: ...16 30 Cod 714 0199 03 00 Rev 00 Model R37 45 kW 380 3 60 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 19: ...17 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 20: ...18 30 Cod 714 0186 01 00 Rev 0D Model R55 75 kW 400 3 50 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 21: ...19 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 22: ...20 30 Cod 714 0174 01 00 Rev 1A Model R55 75 kW 460 3 60 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 23: ...21 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 24: ...22 30 Cod 714 0174 02 00 Rev 1A Model R55 75 kW 230 3 60 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 25: ...23 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 26: ...24 30 Cod 714 0174 03 00 Rev 0B Model R55 75 kW 380 3 60 Power wiring diagram Control circuit diagram Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 27: ...25 30 Terminal blocks Component layout Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 28: ... C 53 AMB T F 77 C 25 AMB T MIN MAX F 36 115 C 2 46 AIR W PRESS psi 109 bar 7 5 AIR PRESS MAX psi 174 bar 12 DEW POINT F 37 ISO CLASS 4 C 3 ISO CLASS 4 REF REFRIGERANT TYPE R134a LB 2 87 2 87 2 87 2 87 OZ 45 9 45 9 45 9 45 9 KG 1 30 1 30 1 30 1 30 W WEIGHT LB 236 236 236 236 KG 107 107 107 107 EVAP TEMP F 34 37 4 C 1 3 SUCTION TEMP F 35 6 61 C 2 16 DISCH PRESS psig 203 247 barg 14 17 HP SWITCH SET...

Page 29: ... BSP 1 BSP 1 BSP DN51 DN51 DN51 DN51 AIR T F 95 C 35 AIR T MAX F 127 C 53 AMB T F 77 C 25 AMB T MIN MAX F 36 115 C 2 46 AIR W PRESS psi 109 bar 7 5 AIR PRESS MAX psi 174 bar 12 DEW POINT F 37 ISO CLASS 4 C 3 ISO CLASS 4 REF REFRIGERANT TYPE R404a LB 2 76 2 76 2 76 2 76 3 97 3 97 3 97 3 97 OZ 44 1 44 1 44 1 44 1 63 5 63 5 63 5 63 5 KG 1 25 1 25 1 25 1 25 1 8 1 8 1 8 1 8 W WEIGHT LB 231 231 231 231 ...

Page 30: ...point RLA Nominal Current REF Refrigerant FLA Full load current W Weight LRA Locked rotor current EVAP TEMP Evaporation Temperature TOTAL A Total current SUCTION TEMP Suction Temperature CONNECTION Air connections DISCH PRESS Discharge Pressure AIR T Air inlet temperature HP SWITCH SETTING High pressure switch setting AIR T MAX Max air inlet temperature FAN PRESSURE SWITCH SETTING Fan pressure Swi...

Page 31: ...29 30 R55 75 kW 609 997 136 5 AIR OUTLET 180 77 40 80 AIR INLET 108 37 644 Cod 710 0048 24 01 Rev0H 02 2015 ...

Page 32: ......

Reviews: