ingersollrandproducts.com
23
13.0 REPLaCEMENT PaRTS
PaRTS FOR WaTER COOLED DRYERS
NVC MODEL
CONDENSERS
VaLVES
200
683492
600561
300
683493
600562
400
683493
600562
COMPRESSORS
NVC MODEL
230/1/60
230/3/60
230/3/50
380/3/50
460/3/60
575/3/60
200
682558
682595
682605
682559
682559
682559
300
-
682560
682561
682562
682443
682443
400
-
682606
682563
682564
682562
682562
14.0 ENgINEERINg SPECIFICaTIONS
aIR COOLED CONDENSERS
MODEL
NO.
VOLTS/
PH/HZ
WEIgHT
R-404a
MaX.
FUSE
SIZE
MIN.
CIRCUIT
aMPaCITY
COMPRESSOR
RaTINgS
FaN RaTINgS
LBS. Kg. LB-OZ Kg.
HP RLa LRa QTY HP RLa LRa
NVC200 230/1/60 540 245
2-4
1.02
20
13.7
1
9.7
40
1
1/6
1
3
NVC200 460/3/60 540 245
2-4
1.02
6
3.9
1
2.4
13
1
1/6
0.5
1.2
NVC200 230/3/60 540 245
2-0
.907
15
9.6
1
6.4
38
1
1/6
1
3
NVC200 575/3/60 540 245
2-4
1.02
5
3.0
1
2.4
13
1
1/6
0.5
1.2
NVC250 460/3/60 570 259
3-8
1.588
8
5.3
1 1/2
3.6
16
1
1/6
0.5
1.2
NVC250 230/3/60 570 259
3-8
1.588
15
9.6
1 1/2
6.4
38
1
1/6
1
3
NVC250 575/3/60 570 259
3-8
1.588
7
4.3
1 1/2
3.6
16
1
1/6
0.5
1.2
NVC300 460/3/60 630 286
4-0
1.814
10
6.2
2
4.3
16
1
1/6
0.5
1.2
NVC300 230/3/60 630 286
4-0
1.814
18
11.5
2
7.9
38
1
1/6
1
3
NVC300 575/3/60 630 286
4-0
1.814
8
4.9
2
4.3
16
1
1/6
0.5
1.2
NVC400 460/3/60 670 304
4-0
1.814
12
7.6
2 1/2
5.4
23
1
1/6
0.5
1.2
NVC400 230/3/60 670 304
4-0
1.814
25
15.9
2 1/2 11.4
57
1
1/6
1
3
NVC400 575/3/60 670 304
4-0
1.814
10
6.0
2 1/2
5.4
23
1
1/6
0.5
1.2
MAXIMUM ALLOWABLE WORKING PRESSURE: 230 psig
NOTICE
Specification information above accurate at time of publication. Refer to equipment
serial label for actual refrigerant charges and specifications for units.