background image

Start Up

24

 RT-SVX50F-EN

"On" and "Off" as required to maintain the zone 
temperature setpoint.

Electromechanical Control Heating Operation 
(for Gas Units)

When the system switch is set to the "Heat" position and 
the zone temperature falls below the heating setpoint, the 
Ignition module (IGN) initiates a heat cycle.

Ignition Module Low, Medium and 
High Heat

Two-stage (IGN) runs self-check (including verification that 
the gas valve is de-energized). (IGN) checks the high-limit 
switches (TC01 &TC02) for normally closed contacts, the 
pressure switch (PS) for normally open contacts, and the 
flame rollout (FR) switch for continuity. (IGN) energizes 
inducer blower on high speed to check pressure switch 
closure. If the pressure switch is closed, the inducer blower 
starts a 20 second pre-purge (15 seconds on high speed 
followed by 5 seconds on low speed).

If the pressure switch (PS) is still open, the inducer blower 
will continue to be energized on high speed until pressure 
switch closure.

After pre-purge completes, the (IGN) energizes the first 
stage of the gas valve, initiates spark for 2 seconds 
minimum, 7 seconds maximum (ignition trial) and detects 
flame and de-energizes spark. From this point, a fixed 45 
second indoor blower delay on timing starts.

After the indoor blower delay on is completed, the (IGN) 
energizes the indoor blower. The (IGN) enters a normal 
operating loop where all inputs are continuously 
monitored. If the first stage of gas heat cannot satisfy the 
heating requirement, the thermostat closes W2. The (IGN) 
energizes the second stage of the gas valve and the second 
stage of inducer blower.

When the zone thermostat is satisfied, the (IGN) de-
energizes the gas valve. The (IGN) senses loss of flame. 
The (IGN) initiates a 5 second inducer blower post purge 
and 90 second indoor blower delay off at current speed. 
The (IGN) de-energizes the inducer blower at the end of the 
post purge. The (IGN) de-energizes the indoor blower at 
the end of the selected indoor blower delay off. 

Drain Pan Condensate Overflow Switch 
(Optional)

The Condensate Overflow Switch (COF) is utilized to 
prevent water overflow from the drain pan. The float 
switch is installed on the corner lip of the drain pan. When 
the condensate level reaches the trip point, the COF relay 
energizes and opens the 24VAC control circuit which 
disables the unit. Once the 24VAC control circuit is opened, 
a delay timer will prevent unit start-up for three minutes.

Low Ambient Operation (Optional)

During low ambient operation, outside air temperature 
below 50°F, the Low Ambient Controller will cycle the 
outdoor fan motor "Off" and "On" based on discharge 
pressure. The indoor fan motor (IDM) will continue to 
operate and the outdoor fan will return to normal 
operation once the ambient temperature is above 50°F. 

10 Horsepower Motor Overload

10HP indoor fan motors are not internally protected. For 
proper protection, ensure the adjustable dial on the front 
of the overload (located in the control box) is set to the 
nameplate FLA value of the indoor motor. 

Two-Speed Indoor Fan Control

For units equipped with two-speed indoor fan control, 
standard unit operation for cooling and heating will 
continue and all unit functions will operate normally, 
except for the control of the indoor fan speed. All units 
configured with any type of heating will heat the supply air 
and space as normal utilizing full speed indoor fan by 
energizing the appropriate outputs. The two-speed indoor 
fan unit will only utilize two speeds during the cooling 
operation modes described below.

Cooling Operation

For cooling operation, the unit will operate at Low Fan 
Speed during Fan Only, Economizer Only, and the first 
stage of compressor unit modes by Default. When the unit 
receives a call for cooling, if the economizer is enabled, the 
unit will energize the associated Low Speed output and 
begin to modulate the OA Damper open above minimum 
position up to 100% as necessary. By default, the supply 
fan will remain at low speed for the duration of 
Economizer-Only cooling. If the supply fan is on when the 
first stage compressor is energized, it will remain 
energized or energize at low speed for the duration of Cool 
1.

Table 4.

Ignition module diagnostics

Steady light

Module is powered up, but no active call for 
heat.

Blinking at 
continuous steady rate

Active call for heat.

One blink

Loss of communication.

Two blinks

System lockout (failure to ignite, no spark, low/
no gas pressure, etc.)

Three blinks

Pressure switch (no vent air flow, bad CBM, 
closed at initial call for heat). Auto reset.

Four blinks

High limit (excessive heat in combustion 
chamber, low airflow). Auto reset.

Five blinks

Flame sensed and gas valve not energized or 
flame sensed and no call for heat.

Six blinks

Flame rollout (CBM failure, incorrect gas 
pressure, and incorrect primary air). Requires 
manual reset of the switch.

Seven blinks

W1& W2 swapped (electromechanical 3-10 
tons units).

Table 4.

Ignition module diagnostics

Summary of Contents for EBC180-300

Page 1: ...ining Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...n minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents WARNING Proper Field Wi...

Page 3: ...ir respective owners Revision Summary Added Third Side Condenser Fork Access option Updated Model Number Description and Unit Weights Sections WARNING Follow EHS Policies Failure to follow instruction...

Page 4: ...21 Unit Disconnect FIYUDC 21 Pre Start 22 Verifying Proper Air Flow Units with Belt Drive Indoor Fan 22 Electromechanical Controls Test Procedure 22 Start Up 23 Sequence Of Operation 23 Standard Econo...

Page 5: ...Low Leak Economizer Dry Bulb w o Barometric Relief4 L Low Leak Economizer Reference Enthalpy w o Barometric Relief4 N Low Leak Economizer Comparative Enthalpy w o Barometric Relief4 Digit 15 Supply Fa...

Page 6: ...porary heat is provided in the building Isolate all side panel service entrances and base pan openings e g conduit holes S A and R A openings and flue openings from the ambient air until the unit is r...

Page 7: ...or the discharge line thermostat open the 24VAC signal from the thermostat is interrupted and the compressor is disabled There is no automatic lockout Power Exhaust Control Optional The power exhaust...

Page 8: ...SOR wire and R terminal at customer connections The occupancy sensor must utilize a normally open contact for proper operation If an occupancy sensor is not used another option to controlling occupied...

Page 9: ...nimum distances necessary to assure adequate serviceability cataloged unit capacity and peak operating efficiency Providing less than the recommended clearances may result in condenser coil starvation...

Page 10: ...Dimensional Data 10 RT SVX50F EN Figure 2 Cooling with optional electrical heat units overview Figure 3 Cooling with optional electrical units front side views 15 25 tons standard efficiency...

Page 11: ...al Data RT SVX50F EN 11 Figure 4 Cooling with optional electrical heat units plan view 15 25 tons standard efficiency Figure 5 Foundation units back view horizontal configuration 15 25 tons standard e...

Page 12: ...ndard efficiency Figure 7 Downflow duct connections field fabricated 15 25 tons standard efficiency 9 1 25 4 MM CURB FLANGE LONG SIDES SHORT SIDES Notes Duct flanges mount 7 7 16 down inside the curb...

Page 13: ...re 8 Downflow unit clearance 15 25 tons standard efficiency Figure 9 Barometric relief and economizer 15 25 tons standard efficiency MOTORIZED DAMPER BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONO...

Page 14: ...Dimensional Data 14 RT SVX50F EN Figure 10 Manual damper 15 25 tons standard efficiency...

Page 15: ...EBC180 2146 1826 621 475 365 365 56 37 17 EBC210 2155 1835 624 477 367 367 55 37 20 EBC240 2180 1860 632 484 372 372 55 37 25 EBC300 2206 1886 641 490 377 377 55 36 a Weights are approximate Horizont...

Page 16: ...askets must be installed around the curb perimeter flange and the supply and return air opening flanges General Unit Requirements The checklist listed below is a summary of the steps required to succe...

Page 17: ...mostat with or without switching subbase Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel Condensate Drain Configuration An...

Page 18: ...ustrated below Refer to the customer connection diagram that is shipped with the unit for specific termination points The termination points depending on the customer option selected would be a factor...

Page 19: ...Line Voltage reading that deviates the farthest from the average voltage Example If the voltage readings of the supply power measured 221 230 and 227 the average volts would be VD reading farthest fr...

Page 20: ...o position Close the main power disconnect switch and the unit mounted disconnect switch if applicable Checklist Use the following checklist in conjunction with the general checklist General Unit Requ...

Page 21: ...ty found on the unit nameplate and the N E C 4 Route low voltage class II control wiring through hole in base of unit but not through high voltage conduit Feedcontrolwiringthroughbushingprovided on si...

Page 22: ...using the setpoint potentiometer located on the Economizer Control ECA if applicable Electromechanical Controls Test Procedure See unit schematic for correct wire numbers Fan Test and Minimum Ventila...

Page 23: ...energizes the indoor fan relay coil F to start the indoor fan motor IDM The fan relay F de energizes after the cooling requirement has been satisfied When the heating cycle is terminated the indoor fa...

Page 24: ...timer will prevent unit start up for three minutes Low Ambient Operation Optional During low ambient operation outside air temperature below 50 F the Low Ambient Controller will cycle the outdoor fan...

Page 25: ...Building Design Min Position pot with a range of 0 50 If the Building Design Min Position is set to be higher than the DCV Min Position the setpoints will be capped at the DCV Min Position and the se...

Page 26: ...eed fan DCV OA Good to economize Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below CO2 set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v...

Page 27: ...e Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v On 24 v On VENTMIN Closed Yes Off...

Page 28: ...omize Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below set No Off Off Low 0 v Off 0 v Off VENTMIN L Closed On Off Low 24 v On 0 v Off VENTMIN L Closed On On High 24 v On 24 v On VENTMIN H Closed...

Page 29: ...onomize Y1 I Y2 I FAN SPD Y1 O Y2 O Occupied Unoccupied Below set No Off Off Low 0 v Off 0 v Off VENTMIN L Closed On Off Low 24 v On 0 v Off VENTMIN L Closed On On High 24 v On 24 v On VENTMIN H Close...

Page 30: ...elay is defaulted to 5 minutes and can be changed in the Advanced Setup menu 2SP FAN DELAY When the unit has a call for Y1 In and in the free cooling mode and there is a call for Y2 In the 2 speed fan...

Page 31: ...connect switch to the Off position or proceed to the next component start up procedure Remove electro mechanical test mode connections if applicable LLE Controls Test Procedure See unit schematic for...

Page 32: ...ter contactor if applicable 4 Verify that the heater stage is operating properly 5 To stop the SERVICE TEST turn the main power disconnect switch to the Off position or proceed to the next component s...

Page 33: ...s number represents the force in pounds required to give the needed deflection 6 Compare the force scale reading Step 5 with the appropriate force valuelistedin Table 16 p 33 Ifthe force reading is ou...

Page 34: ...data on an operator s maintenance log like the one shown in Table 17 p 35 If the operating pressures indicate a refrigerant shortage measure the system superheat For guidelines refer to Compressor St...

Page 35: ...zzle and the microchannel coil is 1 3 Final Process For future reference you may find it helpful to record the unit data requested below in the blanks provided 1 Complete Unit Model Number ___________...

Page 36: ...ll exists after you clear it it re displays within 5 seconds Low Leak Economizer Fault Codes Low Leak Economizer Alarms CO2 Sensor Error SYS Alarm Actuator Undervoltage Actuator Overvoltage Actuator S...

Page 37: ...hen the condensate overflow switch is closed a drain pan overflow condition is indicated and it will shut unit operations down Unit Economizer Control ECA Verify Economizer Status by Economizer Actuat...

Page 38: ...matic Type Voltage Diagram Number Description Constant Volume Power 208 575 1213 2717 EBC180 300 60Hz Cooling only Electric Heat Control 208 575 1213 2724 EBC180 300 60Hz Cooling only Electric Heat Mu...

Page 39: ...0 This warranty is for commercial usage of said equipment and not applicable when the equipment is used for a residential application Commercial use is any application where the end purchaser uses the...

Page 40: ...t and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Inge...

Reviews: