No CPU power
CPS #8
1. Ensure control power is off.
2. Verify approximately 24 VDC is present at J10.
3. Check F100, if F100 is blown the BCM must be replaced, not the fuse.
4. If F100 is not blown, and the BCM is not functioning, the BCM must be replaced.