26
11-AC40D1-1E-EN
Troubleshooting
Is contactor
engergized?
(contacts closed)
Compressor fails to start
Contactor check
YES
YES
YES
YES
NO
NO
NO
NO
NO
If applicable, check
TDR input
voltage
Go To: Compressor won’t run
Check for 24 volts AC
across contactor coil
Is voltage
present at
contactor coil?
Replace contactor
Check control
transformer and
control fuse
Is the control
transformer
and fuse good?
Jumper R to Y low
voltage terminals
at thermostat sub
base.
Does the
contactor
energize?
Replace the room
thermostat
Repair or replace
transformer or fuse.
Investigate cause for
failure (possible short in
field wiring)
Repair or replace
connecting wiring
NO
Check ID Low
voltage
transformer
YES
Wait 3 minutes and
check contactor
coil again