24
MS-SVX039A-EN
Configuration
14
External control
0: Disabled
1: On/Off control
2: Off-only control
15
External control output
(c)
16
Not available.
Factory set to 0.
17
Buzzer
0: Enabled
1: Disabled
18
Filter timer (hours of use)
2: 1000
6: 2000
N/A
19
Factory set to 3
Cannot be changed. Not seen in configuration mode.
20
Associating wireless remote
control with indoor unit(s)
0, 1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
21
Heat setting compensation
0: Default
1: 3.6°F (2°C)
2: 9°F (5°C)
22
Not available.
Factory set to 0.
23
Not available.
Factory set to 0.
24
Not available.
Factory set to 0.
(a) Cassette-type indoor units are set to “Enabled (3-minute delay)” regardless of digit 8 setting.
(b) For heat pump systems, the master indoor unit controls whether the system operates in heating or cooling. If the master indoor unit calls for heating
and slave indoor units calls for cooling, the master indoor unit (and any other slave indoor units that call for heating) will operate in heating mode. The
slave indoor units that call for cooling will do nothing.
(c) Digit 15 requires that an external contact interface module be connected. Refer to VRF-SVN54.
Table 1.
Installation option #1: Digit 2 = 2 (continued)
Display
screen
(mode and
On/Off)
Digit
Option description
Set digit to...
External control output
0: Thermal on
1: Operation on
2: N/A