INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line
– Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - [email protected] – 04 15 AA 59 205 04
13
1 1 . T E C H N I C A L S P E C I F I C A T I O N S
X 2 L C D T o u c h F R / S C H U K O
– I E C - U N I V E R S A L
X2 LCD
Touch
500
X2 LCD
Touch
700
X2 LCD
Touch
1000
X2 LCD
Touch
1250
X2 LCD
Touch
1600
X2 LCD
Touch
2000
GENERAL CHARACTERISTICS
Technology
Line interactive
Power
500 VA/240W
700 VA/360W
1000 VA/480W
1250 VA/600W
1600 VA/900W
2000 VA/1200W
Power factor
0,5
0,5
0,5
0,5
0,56
0,6
FR/SCHUKO or UNIVERSAL
models : Number of protected
UPS outlets
2
2
2
4
4
4
IEC models : surge protected UPS
outlets / protected UPS outlets
1/3
2/4
PROTECTION & FILTERING
Output form - Protection
Modified sinewave - Discharge / overcharge / overload
FR/SCHUKO models : input
protection
Circuit breaker
IEC models : input protection
Fuse
Universal models : input
protection
Fuse
Circuit breaker
PHYSICAL CHARACTERISTICS
Dimensions -
DxWxH (mm)
300 x 101 x 142
320 x 132 x 182
Net weight
kg
3,7
4,4
5
8,2
10,4
11
INPUT TECHNICAL CHARACTERISTICS
Voltage
220/230/240 V
Voltage range - Frequency
162-290 VAC - 50/60 Hz (auto sensing)
OUPUT TECHNICAL CHARACTERISTICS (battery mode)
Voltage
220/230/240 V
Automatice voltage regulation
± 10 %
Frequency
50 ou 60 Hz ± 1 Hz (auto sensing)
Crest ratio
03:01
Output current (A)
2
3
3,9
4,5
6,8
9,1
BATTERY
Battery charger
Operates when the UPS is connected to mains
Cold start (no mains)
Yes
Batteries type & number
12V/4,5AH*1
12V/7AH*1
12V/9AH*1
12V/7AH*2
12V/9AH*2
12V/9AH*2
Recharging voltage
13.7s Vdc
27.4 Vdc
Recharging time
4 to 6 hours to 90 % after complete discharge
Backup time
6-40 min. depending on connected load
INDICATORS
Touch LCD
Touch LCD : Input voltage, output voltage, battery capacity, load level and UPS status
AUDIBLE ALARMS
Battery mode
Sounding every 10 seconds
Low battery
Sounding every second
Overload
Sounding twice every second
Battery replacement
Sounding every 2 seconds
Default
Continuously sounding
COMMUNICATION
Communication port
USB
ENVIRONMENT
Ideal environment
0-40°C, 0-90% of relative humidity (without condensation)
Noise level
<40dB
NORMS (FR/SCHUKO / IEC models)
Standard
CE RoHS
EMC (Electromagnetic
compatibility)
EN62040-2:2006, EN61000-4-2:2009, EN61000-4-3:2006+A1:2008+A2:2010,
EN61000-4-4:2004+A1:2010, EN61000-4-5:2006, EN61000-2-2:2002
Low voltage (Safety)
EN60950-1:2006+A11:2009+A1:2010, EN62040-1:2008
SALES INFO
Warranty
2 years
Gencods – FR/SCHUKO models
3700085
65998 4
3700085
65999 1
3700085
66000 3
3700085
66001 0
3700085
66002 7
3700085
66003 4
Gencods – IEC models
3700085
66036 2
3700085
66037 9
3700085
66038 6
3700085
66039 3
3700085
66040 9
3700085
66041 6
Gencods – UNIVERSAL models
3700085
66004 1
3700085
66005 8
3700085
66006 5
3700085
66007 2
3700085
66008 9
3700085
66009 6