DCE (Dry Contact)-B card
The pin assignments of 10-Pin Terminal:
1 2 3 4 5 6 7 8 9 10
Pin 1: UPS on Bypass mode.
Pin 2: Utility Abnormal
Pin 3: Utility Normal
Pin 4: Inverter On
Pin 5: Battery Low
Pin 6: Battery Bad or Abnormal
Pin 7: UPS Alarm
Pin 8: Common
Pin 9: Shutdown UPS positive (+) signal
Pin 10: Shutdown UPS positive (-) signal
The shutdown function will be activated, after a +6~+25Vdc is put between pin9 and
pin10 for 5 seconds.
The capacity of each relay contact is 40Vdc/25mA.
Installation Position: slot1 (CHA-CN7) or slot 2 (CHB-CN8).
Flexible signal output for N.C. (Normal close) or N.O. (Normal Open) contact by
shorting pin1-2 or pin2-3 from JP1-5.
The shutdown function will be enabled in 1 minute after blackout occurs if the pin1-2 of
both CN1 and CN6 be shorted by cap. Or, the shutdown function can only be enabled
by pin9-10 of CN3 if the pin2-3 of both CN1 and CN6 be shorted by cap.
6.5.
SNMP Cards
6.5.1.
SNMP/WEB card
For installation, please refer to the
user’s manual attached with the card.
Installation.
Position: slot 2 (CHB).
6.5.2.
Net Agent II Internal Card
For installation, please refer to the user’s
manual attached with the card.
Installation.
Position: slot 2 (CHB).