26
5 . S T O R A G E
5.1 Warning indicator
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature)
has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
5.2 Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge
the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
6 . S P E C I F I C A T I O N S
E6 LCD RT EVOLUTION
TX 5000 (S)
E6 LCD RT EVOLUTION
TX 6000 (S)
E6 LCD RT EVOLUTION
TX 8000 (S)
E6 LCD RT EVOLUTION
TX 10000 (S)
5000 VA
6000 VA
8000 VA
10000 VA
4500 W
5400 W
7200 W
9000 W
4500 W
5400 W
7200 W
9000 W
670 x 440 x 133 (3U)
670 x 440 x 133 (3U)
745 x 440 x 133 (3U)
745 x 440 x 133 (3U)
635 x 440 x 133 (3U)
635 x 440 x 133 (3U)
635 x 440 x 133 (3U)
635 x 440 x 133 (3U)
670 x 440 x 133 (3U)
670 x 440 x 133 (3U)
745 x 440 x 133 (3U)
745 x 440 x 133 (3U)
20 + 59
20 + 59
23,5 + 65
23,5 + 65
67
67
90
90
670 x 440 x 133 (3U)
670 x 440 x 133 (3U)
745 x 440 x 133 (3U)
745 x 440 x 133 (3U)
20
20
23,5
23,5
Low Line Transfer
(based o n lo ad percentage 100%-80%/ 80%-70%/ 70%-
60%/ 60%-0%)
230 V
Low line Comeback
230 V
High Line Transfer
230 V
High Line Comeback
230 V
Eco mode
96%
EFFICIENCY
AC Mode
90%
Waveform
Pure sinewave
Output connection
Terminal board
Harmonic distorsion
<= 2% THD (linear load); <= 4% THD (batt mode before shut down)
Transfer Time
Line mode to Battery mode
Zero
Inverter to Bypass
Zero
Frequency Range (Batt. Mode)
50 Hz +/- 0,1 Hz ou 60 Hz +/- 0,1 Hz
Current Crest ratio
3 : 1 (max)
AC Voltage Regulation (Batt, mode)
+/- 1%
Frequency Range (Synchronized Range)
50 Hz : 46 Hz ~ 54 Hz ou 60 Hz : 56 Hz ~ 64 Hz
Allowable Overload : online mode
Power Factor
0,99 at 100% load
Voltage
100 / 104 / 110 / 115 / 120 / 208 / 220 / 230 / 240 VAC
176 VAC to 110 VAC +/-2%
186 VAC to 120 VAC +/-2%
290 VAC
Frequency Range
50 Hz : 46 Hz ~ 54 Hz ou 60 Hz : 56 Hz ~ 64 Hz
Phase
0,9
Long Backup time model
Long Backup time Model
Dimensions D x W x H (mm) - UPS
Net Weight (kg)
Standard Model
Dimensions D x W x H (mm) - UPS
Dimensions D x W x H (mm) - Battery bank
GENERAL CHARACTERISTICS
Technology
On line Double Conversion
VA Capacity
W capacity
Dimensions D x W x H (mm) - Iso Bank
Standard model
Long Backup time model
Power Factor
Standard model
100-110% transfer to bypass after 10 min / 110-130% transfer to bypass after 1 min />130% transfer to bypass
after 1 sec
High Voltage Range
Low Voltage Range
OUTPUT (ISOLATION TRANSFORMER)
INPUT
PHYSICAL CHARACTERISTICS
Net Weight (kg) - UPS + Battery bank
Net Weight (kg) - Iso Bank
Single phase with ground
300 VAC