9. Mute the buzzer
1)
Touch “SETTING”
and select “BASIC” i
tem. There are two events available to mute. Refer to
“SETTING” scree
n.
2) Some warning alarms
can’t be muted unless the
error is fixed. Please refer to section 3-3 for
details.
10. Operation in warning status
1) When warning code flashes and the buzzer beeps once every second, it means that a
warning event occurs on UPS. Users can read the warning message(s) from
“DATA LOG”
menu. Please refer to the Chapter 4 for details.
2) Some warning alarms
can’t be muted unless the
error is fixed. Please refer to section 3-3 for
details.
11. Operation in Fault mode
1) When fault code lights on the LCD screen and the buzzer beeps continuously, it means that
there is a fatal error with the UPS. Users can get the fault code
from “DATA LOG”
menu.
Please refer to the Chapter 4 for details.
2) Please check the loads, wiring, ventilation, mains, battery and so on after the fault occurs.
Don’
t try to turn on the UPS again before solving the issues. If the problems persist, contact
the distributor or service personnel immediately.
3) In case of an emergency, shut off connections from mains, external battery, and output
immediately to avoid possible damage to the UPS or equipment.
12. Operation in maintenance bypass mode
This operation should only be performed by maintenance personnel or qualified technicians.
When the UPS needs to repair or service and the load could not be shut off, the UPS needs to be
put into maintenance mode.
1) First, switch off the UPS.
2) Then, remove the cover of maintenance bypass switch on the panel.
3) Turn the maintenance
switch to “BPS” position.
13. 3/3 model set to 3/1 model (For 10K-20K Only)
This operation should only be performed by maintenance personnel or qualified technicians.