87
INFOSEC UPS SYSTEM
–
15, rue du Moulin
–
44880 Sautron
–
France
–
www.infosec-ups.com
hotline : +33 (0)2 40 76 15 82
–
fax : +33(0)2 40 94 29 51
–
–
07 19 AA 59 205 03
3-7. LCD Setting
There are three parameters to set up the UPS. Refer to diagram 13.
Parameter 1
is for program alternatives. There
are 20 programs to set up. Refer to the table
below.
Parameter 2 and parameter 3
are the setting
options or values for each program.
NOTE:
Select “Up” or “Down” buttons to
change the programs or parameters.
List of 20 programs available for parameter 1:
Code Description
Bypass
AC
Eco CVCF Battery
Battery
Test
01
Output voltage
Y*
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
Frequency range for ECO mode
Y
08
Bypass mode setting
Y
Y
09
Maximum battery discharge time setting
Y
Y
Y
Y
Y
Y
10
Reserved
Reserved for future options
11
Hot standby function Setting
Y
12
Neutral loss detection
Y
Y
Y
Y
Y
Y
13
Battery voltage calibration
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter A voltage adjustment
Y
Y
Y
16
Inverter B voltage adjustment
Y
Y
Y
17
Inverter C voltage adjustment
Y
Y
Y
18
Output A voltage calibration
Y
Y
Y
19
Output B voltage calibration
Y
Y
Y
20
Output C voltage calibration
Y
Y
Y
*Y (YES) means that this program can be set in this mode.
NOTE:
All parameter settings will be saved only when UPS shuts down normally with internal or external
battery connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode).
Diagram 13 :
LCD Settings
Parameter 1
Parameter 2
Parameter 3