37
STATIC BY-PASS LINE
Number of phases
3P+N+PE
Voltage range (line- neutral)
[V]*(1)
220 V /230V /240V ±%10
Frequency range [Hz] *(1)
47-53
Nominal apparent power
[kVA]
10
15
20
30
40
60
80
100
120
Nominal current [A]
15.2
22.7
30.3
45.5
60.6
91
121
151
181
Transfer duration [ms]
0
BATTERIES
Battery type
Sealed lead acid, 12 V
Number of batteries
2x27
Nominal battery voltage [V]
2x324
STANDARDS
Safety
EN 62040-1-2, EN 60950-1
Performance
EN 62040-3
EMC
EN 50091-2
Product Certification
CE
COMMUNICATIONS
Free contact communication (AC failure, battery under voltage, bypass and output failure)
Serial communications (RS232, RS 422)
Two digital inputs for remote shut down of the UPS and generator operation feedback
Isolated auxiliary 5V supply for digital inputs
OTHERS
Manual by-pass with 0 transfer time
Electronic short circuit protection
Over temperature and over current protection
Liquid crystal display (LCD)
Mimic front panel
*(1) These are software parameters. They can be changed upon request
*(2) Batteries shall be fully charged in order to provide these values
23. 03.2009 The manufacturer reserves the rights to change the technical specifications and design without notice.