Appendix-1: Technical Specifications
Apparent power [kVA]
10
15
20
30
40
60
80
100
120
MODELS
Apparent Power [kVA]
10
15
20
30
40
60
80
100
120
ENVIRONMENTAL
Storage Temperature
Range [°C]
-25 to +55 (15 - 40 recommended for longer battery life)
Operating Temperature
Range [°C]
0 to +40 (20 - 25 recommended for longer battery life)
Relative Humidity Range
% 0 - % 95 (non condensing)
Max. Altitude without
Derating [m]
1000
Protection Level
IP 20
Maximum
Power
Ddissipation
[W]
800
960
1280
1920
2560
3840
5120
6400
7680
[Btu]
2730
3277
4369
6553
8737
13106
17475
21843
26212
[kcal/h]
688
825
1100
1650
2200
3302
4403
5503
6604
ELECTRICAL
Mains Input
Number of Phases
3P+N+PE
Nominal Voltage [V]
380 / 400 / 415 (line-line)
Voltage
range for
normal
operation
(line to
neutral) [V]
Lower
limit
(depends
on the
load
level)
187 @ %100 load ( line- neutral )
120 @ %64 load ( line- neutral )
80V@ %42 load ( line- neutral )
-
Upper
Limit
280
Nominal Frequency [Hz]
50 / 60
Frequency Range [Hz]
+/-10%
Nominal
Current [A]
wave
Form
sinusoidal
rms
Value
*(2)
13
20
26
40
54
80
106
132
158
Maximum
Current [A]
wave
form
sinusoidal
rms
Value
18
25
33
49
69
101
133
167
199
OUTPUT @ 3PH OUTPUT UPS’S
Performance
Classification
VFI-SS-111
Number of Phases
3P+N+PE
Nominal Voltage [V]
380 / 400 / 415 (line-line)
Static
Voltage
Regulation
Normal
<%1
@ %100
Linear Load
Battery
Nominal Frequency [Hz]
50 / 60