background image

288713230 

 
 

 

 
 

Power rating 

1000VA,2000VA,3000VA 

Voltage 

220V, 

±

25% 

INPUT 

Frequency 

50 or 60Hz   

±

5% 

Voltage 

220V 

±

5% 

Frequency 

50 True 60Hz  

±

0.5% 

Voltage 
regulation 
AVR 

The AVR increase automatically output voltage 15% if the mains voltage falls down –9% or –

25%. 

The AVR decrease automatically output voltage 13%, 

if the mains voltage increase 9% or 25%. 

OUTPUT 

Transfer-time  

2/4 ms. 

Lightning 
Protection 

320 joule, 2ms. 

Overload 
Protection 

The UPS shout down automatically if the load current exceeds %110 for 30 seconds or %130 for 

3 seconds. 

Input 

Fuse agaist overload and short circuit. 

PROTECTION 

AND 

FILTERING 

 

Short circuit 

Automatic shout down of the output and input fuse protection. 

Type 

Informer 1000 Maintenance free 2*12Ah /(External Battery Cabinet 6*12Ah )* 

Informer 2000 Maintenance free 4*7Ah /(External Battery Cabinet 12*7Ah )* 
Informer 3000 Maintenance free 4*7Ah /(External Battery Cabinet 12*7Ah )*

 

Typical  
Charging time 

4 hours (%90 of the full capacity) 

Protection 

Automatic self-test&descharge protection. 

Replace the battery indication. 

Back-up time 

8min.(100%)/1 hour / (63min.(100%)/ 5.5 hour)* 

 (Dependence to the load) 

BATTERY 

Netto weight 
Kg  

Informer 1000 19 kg  ./(External Battery Cabinet 22 kg.)* 
Informer 2000 31 kg.  /(External Battery Cabinet 37 kg.)* 
Informer 3000 32 kg.  /(External Battery Cabinet 37 kg.)*

 

PHYSICAL 

SPECIFICATION

 

Dimensions 

Informer 1000           135x430x390 mm, 

 

Informer 2000,3000  135x470x390 mm 

Acoustical 
noise 

<40dBA (1m far from the UPS ) 

ENVIRONMENT 

 

 

 