288713230
Power rating
1000VA,2000VA,3000VA
Voltage
220V,
±
25%
INPUT
Frequency
50 or 60Hz
±
5%
Voltage
220V
±
5%
Frequency
50 True 60Hz
±
0.5%
Voltage
regulation
AVR
The AVR increase automatically output voltage 15% if the mains voltage falls down –9% or –
25%.
The AVR decrease automatically output voltage 13%,
if the mains voltage increase 9% or 25%.
OUTPUT
Transfer-time
2/4 ms.
Lightning
Protection
320 joule, 2ms.
Overload
Protection
The UPS shout down automatically if the load current exceeds %110 for 30 seconds or %130 for
3 seconds.
Input
Fuse agaist overload and short circuit.
PROTECTION
AND
FILTERING
Short circuit
Automatic shout down of the output and input fuse protection.
Type
Informer 1000 Maintenance free 2*12Ah /(External Battery Cabinet 6*12Ah )*
Informer 2000 Maintenance free 4*7Ah /(External Battery Cabinet 12*7Ah )*
Informer 3000 Maintenance free 4*7Ah /(External Battery Cabinet 12*7Ah )*
Typical
Charging time
4 hours (%90 of the full capacity)
Protection
Automatic self-test&descharge protection.
Replace the battery indication.
Back-up time
8min.(100%)/1 hour / (63min.(100%)/ 5.5 hour)*
(Dependence to the load)
BATTERY
Netto weight
Kg
Informer 1000 19 kg ./(External Battery Cabinet 22 kg.)*
Informer 2000 31 kg. /(External Battery Cabinet 37 kg.)*
Informer 3000 32 kg. /(External Battery Cabinet 37 kg.)*
PHYSICAL
SPECIFICATION
Dimensions
Informer 1000 135x430x390 mm,
Informer 2000,3000 135x470x390 mm
Acoustical
noise
<40dBA (1m far from the UPS )