ETR EVO UPS User Manual (Ver. 1.0)
Page 55
9.2. High Inrush Current Load at the Output
Some loads absorb more current than their nominal current value for a short period of time when
they are energized. Ordinary UPS’s either switch off their output and they cause all the loads to
remain without energy or they pass to bypass, transferring all the loads to the mains.
ETR EVO UPS behaves like a current source in such a situation. (As long as the over current is drawn,
it decreases the output voltage keeping the output current constant at a certain value). Thus none of
the loads on the output are affected from this situation.
9.3. Bypass voltage bad shape Alarm
It means that Bypass mains voltage is different than the inverter reference signal. (e.g. it’s out of its
limits or the total harmonic distortion > %10)
Make sure that the bypass circuit breaker is “I" (if the UPS has no separate bypass mains input, make
sure that the input circuit breaker is "I ").
9.4. Bypass phase sequence wrong Alarm
It means that phase sequence of bypass mains voltage is not OK. Phase sequence of the separate
bypass mains input should be changed.
9.5. Bypass not synchronized Alarm
Frequency of bypass mains voltage is out of the frequency range for bypass operation or bypass mains
voltage is very low. Check if the bypass mains voltage is within the specified limits.
9.6. Input phase sequence wrong Alarm
It means that phase sequence of input mains voltage is not OK. Phase sequence of input mains input
should be changed.
9.7. Input not synchronized Alarm
Frequency of input mains voltage is out of the frequency range for input operation or input mains
voltage is very low. Check if input mains voltage is within specified limits.
9.8. DC voltage low/DC not equal to input voltage Alarms
Any of the DC bus voltage is lower than its lower limit. It means that the batteries had been
discharged. It is removed when the rectifier resets. If you encounter this alarm during start-up,
check if the inrush circuit breaker is at "I" position. Charge the batteries, perform battery test and
check if the alarm is removed.
9.9. Emergency power off active Alarm
It means that Emergency stop (EPO) is activated (digital input “UPS OFF” is set high). Check the "EPO"
input
9.10. Input Circuit Breaker Blown Out
If the input circuit breaker blows; it points out that there is output short circuit on Bypass Operation
or UPS might be breakdown. Please look at also
Section 9.1. Output Short Circuit Alarm
UPS performs this feature if it is working in Online or Battery Operation.
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...