background image

 

 

11

SunLight Series UPS User Manual 

 
 
 
 
 
 

IV.  OPERATING   PROCEDURE 

 
 

4.1     6 - 7,5 - 10 kVA

 

 

4.1.1  Turn On procedure 

 

1 .

 Turn on  the Main Switch  on the rear panel to "

1

"  position. 

(There is line voltage at the output.)

  

2 .

  Turn on  the On-Off Switch PK1  on  the rear panel to  the "

1

"  position. Turn on the power switches on  

your critical load after the "Inverter" indicator (green light) is turned on. 

(There is inverter voltage at the 

output.)

 

 
 

4.1.2   Turn Off procedure 

 
1 .

  Turn off all the power switches on your critical equipments that are connected to the UPS. 

2 .

 Turn off the On-Off switch PK1 and the Main Switch to "

0

" position. 

 

CAUTION

 

A-

  For  daily   TURN   ON / TURN   OFF   operation,  it  is  recommended  to keep  the Main switch  at "

1

"      

     position  to  ensure  proper  battery  operation. 

B-

  If  the  Main  switch   is  in   "

1

"  position   the  line  power will be supplied   to output receptacles  

     directly. DO NOT insert objects other than equipment  power cords into outlets. 
 

 
 

4.2     15-20-30  kVA

 

 

4.2.1  Turn On Procedure 

 
1 .

  Turn On Main Switch PK1 on the front  panel from position "

0

" to "

3

" step by step as in the instructions  

      given in chapter 3.4.2 

2 .

  Turn on the power switches on your critical load after the "Inverter" indicator (green light) is turned on.   

      You will have an uninterrupted AC supply voltage at the UPS outputs only if this green light is "

ON

"     

      and  if you have a by-pass supply connected to your unit. 
 
 

4.2.2  Turn Off Procedure 

 
1 .

 Turn off all the power switches on your critical equipments that are connected to the UPS . 

2 .

 Turn off the Main switch PK1 "

0

" position step by step. 

 

CAUTION

 

A .

  Regardless of the position of PK1 , the battery charger is active as long as the battery fuse and AC  

       circuit breakers are closed. 

B .

  For  daily   TURN   ON / TURN   OFF    operation ,   it  is recommended to keep the Main switch PK1  

       in "

0

" position. 

 
 

4.3  When Utility Power Is Interrupted 

 
In case the utility power is interrupted, the UPS converts the built-in battery source to output terminals 
immediately to protect your critical loads from loss of data or damage. 

Summary of Contents for SunLight -210

Page 1: ...USER MANUAL UNINTERRUPTIBLE POWER SUPPLIES 3 Phase Input 1 Phase Output info rise TECHNOLOGIES SunLight 206 6 kVA SunLight 207 7 5 kVA SunLight 210 10 kVA SunLight 215 15 kVA SunLight 220 20 kVA SunL...

Page 2: ...edure 11 4 2 2 Turn Off Procedure 11 4 3 When Utility Power Is Interrupted 11 4 4 Operator Control Panel 12 4 4 1 Push Buttons 12 4 4 2 First Message Line Of The LCD 12 4 4 3 Second M L ALARMS Of The...

Page 3: ...ified service personnel The output may be energized when the unit is not connected to a mains supply Risk of electric shock hazardous live parts inside this unit are energized from the battery supply...

Page 4: ...and maintenance by pass LCD Liquid Crystal Display display Alarm history Memory for max 64 alarms Automatic battery testing optional High quality maintenance free lead acid type batteries High nonline...

Page 5: ...ransfer Switch static by pass Static transfer switch is an electronically controlled switching circuit checked by main controller board In case of inverter overload or any other faults STS transfers t...

Page 6: ...Frequency 50 Hz Line Synchronized 1 Output Frequency Tolerance Free Running 0 2 Efficiency 100 Load 85 87 Crest Factor 3 1 Overload capacity 100 125 Load 2 5 min 125 150 Load 10 sec 150 instant by pa...

Page 7: ...ections Battery Fuse AC Output 220V AC 50Hz 10A max DB9 Port PK1 On Off Switch Main Switch Figure 2 2 1 6 7 5 10 kVA Rear view Figure 2 2 2 Front views Main Switch PK1 On Off Switch UPS Electrical Con...

Page 8: ...ocation Selection The UPS is designed to be installed in a protected environment The following conditions should be prohibited 1 Blocking the airflow intake and outlet It is recommended to retain 10 c...

Page 9: ...ioned and secured connect the power cables as described in the following section It is recommended that the UPS should be connected to the line voltage protected by a circuit breaker 1 Before connecti...

Page 10: ...give the inverter power to the output 3 Disconnect the input power The LINE FAILURE indicator will be on and audible alarm will sound intermittently Now the output receptacles are supplied from the ba...

Page 11: ...ion as well 4 Position 3 When PK1 is turned to this position the Load is supplied again by line voltage at during start up and after a short delay inverter starts running this can be seen by observing...

Page 12: ...wer cords into outlets 4 2 15 20 30 kVA 4 2 1 Turn On Procedure 1 Turn On Main Switch PK1 on the front panel from position 0 to 3 step by step as in the instructions given in chapter 3 4 2 2 Turn on t...

Page 13: ...onal sections LED indications and control and display As can be seen the upper section consists of leds which indicate the operation mode This panel shows the systems operation such as input and outpu...

Page 14: ...LINE MODE UPS operating mode LINE FAILURE You have no AC input at the UPS input BATTERY TEST Performing battery test BAT AUTONOMY END Battery autonomy has finished BATTERY LOW UPS battery voltage is b...

Page 15: ...g the batteries FAULT 7 Rectifier fault Please call service for checking the UPS FAULT 8 Line voltage out of tolerance 4 5 Automatic battery test system optional There are some conditions to make this...

Page 16: ...oftware the UPS and the computer system communicate so that the computer system is warned of impending UPS shutdown Software RUPS RUPSII UPSILON SNMP devices is available for most operating systems an...

Page 17: ...d to your network through SNMPVIEW Software supplied with the module or it is possible to monitor the UPS through an Internet Browser It is possible to shutdown the servers or users with Client mate S...

Page 18: ...PS system from several different locations at the same time 5 5 UPS Port Sharer Multiple server shut down unit Using one of this units you can automatic shut down of 4 8 servers or PC where without LA...

Page 19: ...18 SunLight Series UPS User Manual...

Page 20: ...19 SunLight Series UPS User Manual Connection Diagram Of The RMP COM1...

Page 21: ...persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the service 1 Did you follow the operation proced...

Page 22: ...not apply if the product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited...

Reviews: