CABLE DIAMETER CALCULATION AND LIGHTNING & SURGE PROTECTION   

 

Relation between 24VAC Cable Diameter and Transmission Distance 

 

In general, the maximum allowable voltage loss rate is 10% for AC-powered devices. The 
table below shows the relationship between transmission power and maximum transmission 
distance under a certain specified cable diameter, on condition that the 24VAC voltage loss 
rate is below 10%. According to the table, if a device rated at 50W is installed 17-meter away 
from the transformer, the minimum cable diameter shall be 0.8000mm. A lower diameter 
value tends to cause voltage loss and even system instability.   
 

 

0.8000

 

1.000

 

1.250

 

2.000

 

10 283 

(86) 

451 

(137)

 716 

(218) 

1811 

(551)

 

20 

141 (42) 

225 (68) 

358 (109) 

905 (275) 

30 94 

(28) 

150 (45) 

238 (72) 

603 (183) 

40 

70 (21) 

112 (34) 

179 (54) 

452 (137) 

50 

56 (17) 

90 (27) 

143 (43) 

362 (110) 

60 

47 (14) 

75 (22) 

119 (36) 

301 (91) 

70 

40 (12) 

64 (19) 

102 (31) 

258 (78) 

80 

35 (10) 

56 (17) 

89 (27) 

226 (68) 

90 

31 (9) 

50 (15) 

79 (24) 

201 (61) 

100 

28 (8) 

45 (13) 

71 (21) 

181 (55) 

110 

25 (7) 

41 (12) 

65 (19) 

164 (49) 

120 

23 (7) 

37 (11) 

59 (17) 

150 (45) 

130 

21 (6) 

34 (10) 

55 (16) 

139 (42) 

140 

20 (6) 

32 (9) 

51 (15) 

129 (39) 

150 

18 (5) 

30 (9) 

47 (14) 

120 (36) 

160 

17 (5) 

28 (8) 

44 (13) 

113 (34) 

170 

16 (4) 

26 (7) 

42 (12) 

106 (32) 

180 

15 (4) 

25 (7) 

39 (11) 

100 (30) 

190 

14 (4) 

23 (7) 

37 (11) 

95 (28) 

200 

14 (4) 

22 (6) 

35 (10) 

90 (27) 

Power (W)

Diameter (mm)

Distance (ft / m)

 

Summary of Contents for N3787XA

Page 1: ...FIBER OPTIC TRANSMISSION SYSTEM 1 SERIES 10 100 1000Mbps Ethernet Transceiver User Manual Infinova ...

Page 2: ......

Page 3: ...ERVICE NOTICE 1 PRODUCT DESCRIPTION 2 MAIN FEATURES 3 INSTALLATION 4 POWER SUPPLY 4 N3787XA XB GE PANEL 5 N3787XA 8FE PANEL 6 SPECIFICATIONS 7 SYSTEM DIAGRAM 8 CABLE DIAMETER CALCULATION AND LIGHTNING SURGE PROTECTION 10 ...

Page 4: ......

Page 5: ...plied in accordance with good engineering practices and that products are proved by our examination to be defective This warranty does not extend to any Infinova products which have been subject to acts of accident misuse abuse neglect improper application or installation improper operation or maintenance connection to an improper voltage supply or to materials which have been altered or repaired ...

Page 6: ...00m transmission for the electrical Ethernet signal which no longer meets the actual need in transmission distance and coverage scope While fiber communication with its large capacity high security light weight small size no relay and long transmission distance is widely used in WAN and other large scale network It s applied for remote 1000M Ethernet data switch with large capacity Peer to Peer tr...

Page 7: ... polarity at the physical layer Support IEEE802 1Q protocol Support 1000M optical port The Ethernet optical ports support full half duplex self adaptive Support IEEE 802 3x full duplex flow control and back pressure half duplex flow control Support MAC address self learning and update Support 802 1P protocol and QoS mechanism Compact structure for easy installation Hot swapping design With status ...

Page 8: ...P cables to transmit Ethernet data The RJ45 connector is applied for the Ethernet port POWER SUPPLY The N3787 series is powered by a plug in 24VAC 830mA power supply with 2 pin terminal block connector Figure 1 External power supply Note When the series is powered together with other devices cameras and etc by a single 24VAC power source please make sure that the related device has a full wave bri...

Page 9: ...supply PWR Red Off No power supply On Optical link loss alarming OP Red Off Optical link connected Off 10M 100M Ethernet disconnected On 10M 100M Ethernet connected without data transmission 10 100 Green Flickering 10M 100M Ethernet connected with data transmission Off 1000M Ethernet disconnected On 1000M Ethernet connected without data transmission Ethernet Port 1000 Green Flickering 1000M Ethern...

Page 10: ...or Status Indication On Normal power supply PWR Red Off No power supply On Optical link loss alarming OP Red Off Optical link connected Off 10M 100M Ethernet disconnected On 10M 100M Ethernet connected without data transmission Ethernet Port 10 100 Green Flickering 10M 100M Ethernet connected with data transmission Table 2 Indicator Instruction for N3787XA 8FE ...

Page 11: ...Environment Operating Temperature 40 F 165 2 F 40 C 74 C Storage Temperature 40 F 185 F 40 C 85 C Operating Humidity 0 95 non condensing Mechanical Parameters Dimension 2 slots module W H D 1 73 6 22 7 56 44mm 158mm 197mm Dimension 2 slots card W H D 1 58 5 08 6 58 40mm 129mm 167mm Dimension 1 slot module W H D 0 95 6 22 7 56 24mm 158mm 197mm Dimension 1 slot card W H D 0 79 5 08 6 58 20mm 129mm 1...

Page 12: ...DIAGRAM Figure 4 System Diagram for N3787XA XB GE 20 40 80 Fiber Switch IP Camera Monitor PWR OP N3787XA 8FE 20 40 80 N3787XB GE 20 40 80 Figure 5 System Diagram for N3787XA 8FE 20 40 80 and N3787XB GE 20 40 80 ...

Page 13: ...9 SYSTEM DIAGRAM Figure 6 System Diagram for N3787XA 8FE 20 40 80 and third party FC switch ...

Page 14: ... shall be 0 8000mm A lower diameter value tends to cause voltage loss and even system instability 0 8000 1 000 1 250 2 000 10 283 86 451 137 716 218 1811 551 20 141 42 225 68 358 109 905 275 30 94 28 150 45 238 72 603 183 40 70 21 112 34 179 54 452 137 50 56 17 90 27 143 43 362 110 60 47 14 75 22 119 36 301 91 70 40 12 64 19 102 31 258 78 80 35 10 56 17 89 27 226 68 90 31 9 50 15 79 24 201 61 100 ...

Page 15: ...e Use shielded cables or thread the cables through metal tubes for burial thus to ensure the electric connection to the metal tube In case it s difficult to thread the cable through the tube all the way it s acceptable to use tube threaded cables only at both ends of the transmission line yet the length in burial should be no less than 15 meters The cable sheath and the tube should be connected to...

Page 16: ...51 Stouts Lane Monmouth Junction NJ 08852 U S A Tel 1 888 685 2002 toll free USA 1 732 355 9100 Fax 1 732 355 9101 E mail sales infinova com ...

Reviews: